Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2022-08-25 — TX
Operator
Energy Transfer Company
Cause
Incorrect Operation
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$500,000
Incident datetime
2022-08-25 11:14
Report number
Location
TX
Narrative
On august 25, 2022 at approximately 11:14 a release of natural gas liquids (ngl) occurred at the gateway pump station 1 from the meter skid filter that feeds the s505 tx ngl w tx gateway pegasus to jackson, located 17 miles west of midkiff, tx. Measurement techs were on site doing a point-to-point check on the meter station. When valve mov-0201 moved to the open position, the ngl hit the filters causing an abrupt pressure change on the filter vessel door which then caused the door to release and damage the filter vessel and it's associated piping. This caused the release of 1600 barrels of ngl before the meter could be isolated. The filter vessel was never commissioned and used thus the reason that the door was not locked and pinned properly. The filter vessel was removed and on september 1, 2022 at approximately 13:30, the meter station was put back into service. To prevent this from occurring in the future, operations will blind flange any vessels that has not been put into service and use proper lock out/tag out practices and procedures.
Detailed record list
Report Received Date
2022-09-21 00:00:00
Iyear
2022
Report Number
20220216
Supplemental Number
37144
Report Type
Original Final
Operator Id
32099
Name
Energy Transfer Company
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-08-25 11:14:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
31.66344
Location Longitude
-102.12748
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
1600
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2022-08-25 11:14:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-08-25 11:14:00
Restart Datetime
2022-09-01 13:30:00
Communication State Fed Ind
No
On Site Datetime
2022-08-25 11:14:00
Confirmed Discovery Datetime
2022-08-25 11:14:00
Nrc Rpt Datetime
2022-08-25 13:54:00
Nrc Rpt Num
1345529
Additional Nrc Report Numbers
1345995
Ignite Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Gateway Pump Station 1
Segment Name
S505 Tx Ngl W Tx Gateway Pegasus To Jackson
Onshore State Abbreviation
Tx
Onshore Postal Code
79755
Onshore City Name
Midkiff
Onshore County Name
Midland
Designated Location
Milepost
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Filter/strainer/separator
Installation Year
2017
Manufactured Year
2017
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Filter Door Opened Under Pressure Causing Damage To The Filter Vessel And Associated Piping
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
74208
Est Cost Prop Damage
500000
Est Cost Emergency
25000
Est Cost Environmental
0
Est Cost Other
0
Prpty
599208
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
794
Mop Psig
1480
Mop Cfr Section
Internal Design Pressure �195.406(A)(1)
Maop Established Date
2017-06-09 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Incorrect Operation
Cause Details
Damage By Operator Or Operator's Contractor Not Related To Excavation And Not Due To Motorized Vehicle/equipment Damage
Operation Type
Damage By Operator Or Operator's Contractor Not Related To Excavation And Not Due To Motorized Vehicle/equipment Damage
Related No Proc Ind
Yes
Category Type
Routine Maintenance
Operator Qualification Ind
No
Preparer Name
C********** P******
Preparer Title
Specialist Regulatory Compliance
Preparer Email
C******************@e*************.com
Preparer Telephone
713-989-4464
Prepared Date
2022-09-21 00:00:00
Authorizer Name
C**** K*****
Authorizer Telephone
713-989-7077
Authorizer Title
Manager - Regulatory Compliance
Authorizer Email
C***********@e*************.com
Narrative
On august 25, 2022 at approximately 11:14 a release of natural gas liquids (ngl) occurred at the gateway pump station 1 from the meter skid filter that feeds the s505 tx ngl w tx gateway pegasus to jackson, located 17 miles west of midkiff, tx. Measurement techs were on site doing a point-to-point check on the meter station. When valve mov-0201 moved to the open position, the ngl hit the filters causing an abrupt pressure change on the filter vessel door which then caused the door to release and damage the filter vessel and it's associated piping. This caused the release of 1600 barrels of ngl before the meter could be isolated. The filter vessel was never commissioned and used thus the reason that the door was not locked and pinned properly. The filter vessel was removed and on september 1, 2022 at approximately 13:30, the meter station was put back into service. To prevent this from occurring in the future, operations will blind flange any vessels that has not been put into service and use proper lock out/tag out practices and procedures.
| Report Received Date | 2022-09-21 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220216 |
| Supplemental Number | 37144 |
| Report Type | Original Final |
| Operator Id | 32099 PHMSA Enforcement |
| Name | Energy Transfer Company |
| Operator Street Address | 1300 Main Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2022-08-25 11:14:00 |
| Time Zone | Central |
| Daylight Savings Ind | Yes |
| Location Latitude | 31.66344 Google Maps OpenStreetMap |
| Location Longitude | -102.12748 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid) |
| Unintentional Release Bbls | 1600 |
| Intentional Release Bbls | 0 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2022-08-25 11:14:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-08-25 11:14:00 |
| Restart Datetime | 2022-09-01 13:30:00 |
| Communication State Fed Ind | No |
| On Site Datetime | 2022-08-25 11:14:00 |
| Confirmed Discovery Datetime | 2022-08-25 11:14:00 |
| Nrc Rpt Datetime | 2022-08-25 13:54:00 |
| Nrc Rpt Num | 1345529 NRC Report How to search |
| Additional Nrc Report Numbers | 1345995 |
| Ignite Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Gateway Pump Station 1 |
| Segment Name | S505 Tx Ngl W Tx Gateway Pegasus To Jackson |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 79755 |
| Onshore City Name | Midkiff |
| Onshore County Name | Midland |
| Designated Location | Milepost |
| Designated Name | 0+00 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| Item Involved | Filter/strainer/separator |
| Installation Year | 2017 |
| Manufactured Year | 2017 |
| Material Involved | Carbon Steel |
| Release Type | Other |
| Release Type Details | Filter Door Opened Under Pressure Causing Damage To The Filter Vessel And Associated Piping |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 74208 |
| Est Cost Prop Damage | 500000 |
| Est Cost Emergency | 25000 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 599208 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 794 |
| Mop Psig | 1480 |
| Mop Cfr Section | Internal Design Pressure �195.406(A)(1) View CFR 49 §192 |
| Maop Established Date | 2017-06-09 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | < 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Cpm In Place Ind | No |
| Investigation Status | Yes, specify investigation result(s): (select all that apply) |
| Invest No Control Room Ind | Yes |
| Invest No Controller Ind | Yes |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Incorrect Operation |
| Cause Details | Damage By Operator Or Operator's Contractor Not Related To Excavation And Not Due To Motorized Vehicle/equipment Damage |
| Operation Type | Damage By Operator Or Operator's Contractor Not Related To Excavation And Not Due To Motorized Vehicle/equipment Damage |
| Related No Proc Ind | Yes |
| Category Type | Routine Maintenance |
| Operator Qualification Ind | No |
| Preparer Name | C********** P****** |
| Preparer Title | Specialist Regulatory Compliance |
| Preparer Email | C******************@e*************.com |
| Preparer Telephone | 713-989-4464 |
| Prepared Date | 2022-09-21 00:00:00 |
| Authorizer Name | C**** K***** |
| Authorizer Telephone | 713-989-7077 |
| Authorizer Title | Manager - Regulatory Compliance |
| Authorizer Email | C***********@e*************.com |
| Narrative | On august 25, 2022 at approximately 11:14 a release of natural gas liquids (ngl) occurred at the gateway pump station 1 from the meter skid filter that feeds the s505 tx ngl w tx gateway pegasus to jackson, located 17 miles west of midkiff, tx. Measurement techs were on site doing a point-to-point check on the meter station. When valve mov-0201 moved to the open position, the ngl hit the filters causing an abrupt pressure change on the filter vessel door which then caused the door to release and damage the filter vessel and it's associated piping. This caused the release of 1600 barrels of ngl before the meter could be isolated. The filter vessel was never commissioned and used thus the reason that the door was not locked and pinned properly. The filter vessel was removed and on september 1, 2022 at approximately 13:30, the meter station was put back into service. To prevent this from occurring in the future, operations will blind flange any vessels that has not been put into service and use proper lock out/tag out practices and procedures. |