HL incident on 2022-08-25 — TX

Operator
Energy Transfer Company
Cause
Incorrect Operation
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$500,000
Incident datetime
2022-08-25 11:14
Report number
Location
TX
Narrative
On august 25, 2022 at approximately 11:14 a release of natural gas liquids (ngl) occurred at the gateway pump station 1 from the meter skid filter that feeds the s505 tx ngl w tx gateway pegasus to jackson, located 17 miles west of midkiff, tx. Measurement techs were on site doing a point-to-point check on the meter station. When valve mov-0201 moved to the open position, the ngl hit the filters causing an abrupt pressure change on the filter vessel door which then caused the door to release and damage the filter vessel and it's associated piping. This caused the release of 1600 barrels of ngl before the meter could be isolated. The filter vessel was never commissioned and used thus the reason that the door was not locked and pinned properly. The filter vessel was removed and on september 1, 2022 at approximately 13:30, the meter station was put back into service. To prevent this from occurring in the future, operations will blind flange any vessels that has not been put into service and use proper lock out/tag out practices and procedures.
Detailed record list
Report Received Date
2022-09-21 00:00:00
Iyear
2022
Report Number
20220216
Supplemental Number
37144
Report Type
Original Final
Operator Id
Name
Energy Transfer Company
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-08-25 11:14:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
1600
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2022-08-25 11:14:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-08-25 11:14:00
Restart Datetime
2022-09-01 13:30:00
Communication State Fed Ind
No
On Site Datetime
2022-08-25 11:14:00
Confirmed Discovery Datetime
2022-08-25 11:14:00
Nrc Rpt Datetime
2022-08-25 13:54:00
Nrc Rpt Num
Additional Nrc Report Numbers
1345995
Ignite Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Gateway Pump Station 1
Segment Name
S505 Tx Ngl W Tx Gateway Pegasus To Jackson
Onshore State Abbreviation
Tx
Onshore Postal Code
79755
Onshore City Name
Midkiff
Onshore County Name
Midland
Designated Location
Milepost
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Filter/strainer/separator
Installation Year
2017
Manufactured Year
2017
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Filter Door Opened Under Pressure Causing Damage To The Filter Vessel And Associated Piping
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
74208
Est Cost Prop Damage
500000
Est Cost Emergency
25000
Est Cost Environmental
0
Est Cost Other
0
Prpty
599208
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
794
Mop Psig
1480
Mop Cfr Section
Internal Design Pressure �195.406(A)(1)
Maop Established Date
2017-06-09 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Incorrect Operation
Cause Details
Damage By Operator Or Operator's Contractor Not Related To Excavation And Not Due To Motorized Vehicle/equipment Damage
Operation Type
Damage By Operator Or Operator's Contractor Not Related To Excavation And Not Due To Motorized Vehicle/equipment Damage
Related No Proc Ind
Yes
Category Type
Routine Maintenance
Operator Qualification Ind
No
Preparer Name
C********** P******
Preparer Title
Specialist Regulatory Compliance
Preparer Email
C******************@e*************.com
Preparer Telephone
713-989-4464
Prepared Date
2022-09-21 00:00:00
Authorizer Name
C**** K*****
Authorizer Telephone
713-989-7077
Authorizer Title
Manager - Regulatory Compliance
Authorizer Email
C***********@e*************.com
Narrative
On august 25, 2022 at approximately 11:14 a release of natural gas liquids (ngl) occurred at the gateway pump station 1 from the meter skid filter that feeds the s505 tx ngl w tx gateway pegasus to jackson, located 17 miles west of midkiff, tx. Measurement techs were on site doing a point-to-point check on the meter station. When valve mov-0201 moved to the open position, the ngl hit the filters causing an abrupt pressure change on the filter vessel door which then caused the door to release and damage the filter vessel and it's associated piping. This caused the release of 1600 barrels of ngl before the meter could be isolated. The filter vessel was never commissioned and used thus the reason that the door was not locked and pinned properly. The filter vessel was removed and on september 1, 2022 at approximately 13:30, the meter station was put back into service. To prevent this from occurring in the future, operations will blind flange any vessels that has not been put into service and use proper lock out/tag out practices and procedures.
Report Received Date 2022-09-21 00:00:00
Iyear 2022
Report Number 20220216
Supplemental Number 37144
Report Type Original Final
Operator Id 32099 PHMSA Enforcement
Name Energy Transfer Company
Operator Street Address 1300 Main Street
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2022-08-25 11:14:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 31.66344 Google Maps OpenStreetMap
Location Longitude -102.12748 Google Maps OpenStreetMap
Commodity Released Type Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls 1600
Intentional Release Bbls 0
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2022-08-25 11:14:00
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Shutdown Datetime 2022-08-25 11:14:00
Restart Datetime 2022-09-01 13:30:00
Communication State Fed Ind No
On Site Datetime 2022-08-25 11:14:00
Confirmed Discovery Datetime 2022-08-25 11:14:00
Nrc Rpt Datetime 2022-08-25 13:54:00
Nrc Rpt Num 1345529 NRC Report How to search
Additional Nrc Report Numbers 1345995
Ignite Ind No
Num Pub Evacuated 0
Pipe Fac Name Gateway Pump Station 1
Segment Name S505 Tx Ngl W Tx Gateway Pegasus To Jackson
Onshore State Abbreviation Tx
Onshore Postal Code 79755
Onshore City Name Midkiff
Onshore County Name Midland
Designated Location Milepost
Designated Name 0+00
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Intrastate
Item Involved Filter/strainer/separator
Installation Year 2017
Manufactured Year 2017
Material Involved Carbon Steel
Release Type Other
Release Type Details Filter Door Opened Under Pressure Causing Damage To The Filter Vessel And Associated Piping
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 74208
Est Cost Prop Damage 500000
Est Cost Emergency 25000
Est Cost Environmental 0
Est Cost Other 0
Prpty 599208
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 794
Mop Psig 1480
Mop Cfr Section Internal Design Pressure �195.406(A)(1) View CFR 49 §192
Maop Established Date 2017-06-09 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function < 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Cpm In Place Ind No
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Incorrect Operation
Cause Details Damage By Operator Or Operator's Contractor Not Related To Excavation And Not Due To Motorized Vehicle/equipment Damage
Operation Type Damage By Operator Or Operator's Contractor Not Related To Excavation And Not Due To Motorized Vehicle/equipment Damage
Related No Proc Ind Yes
Category Type Routine Maintenance
Operator Qualification Ind No
Preparer Name C********** P******
Preparer Title Specialist Regulatory Compliance
Preparer Email C******************@e*************.com
Preparer Telephone 713-989-4464
Prepared Date 2022-09-21 00:00:00
Authorizer Name C**** K*****
Authorizer Telephone 713-989-7077
Authorizer Title Manager - Regulatory Compliance
Authorizer Email C***********@e*************.com
Narrative On august 25, 2022 at approximately 11:14 a release of natural gas liquids (ngl) occurred at the gateway pump station 1 from the meter skid filter that feeds the s505 tx ngl w tx gateway pegasus to jackson, located 17 miles west of midkiff, tx. Measurement techs were on site doing a point-to-point check on the meter station. When valve mov-0201 moved to the open position, the ngl hit the filters causing an abrupt pressure change on the filter vessel door which then caused the door to release and damage the filter vessel and it's associated piping. This caused the release of 1600 barrels of ngl before the meter could be isolated. The filter vessel was never commissioned and used thus the reason that the door was not locked and pinned properly. The filter vessel was removed and on september 1, 2022 at approximately 13:30, the meter station was put back into service. To prevent this from occurring in the future, operations will blind flange any vessels that has not been put into service and use proper lock out/tag out practices and procedures.