Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2022-08-11 — TX
Operator
Enterprise Products Operating Llc
Cause
Equipment Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$22,700
Incident datetime
2022-08-11 08:20
Report number
Location
TX
Narrative
At 08:20 on august 11, 2022, a landowner called the enterprise control center to report an odor and dead foliage in the vicinity of the right-of-way shared by seminole blue mainline and two other pipelines. Enterprise technician arrived on site at 09:10 and began investigating. At 11:50 lel monitor readings were detected. At that point an emergency one-call was placed in order to excavate the site. At 11:45 on august 12, 2022 a leaking threaded fitting was found on a stopple flange on the seminole blue mainline. The leak was determined to be reportable based on estimated repair costs. At 12:07 the line was shut down, pressure was reduced, and mainline valves closed at coupland and carmine. The leak was repaired by replacing the fitting with a plug, and the line restarted at 17:16. Initial nrc #1344308 48-hour update #1344458
Detailed record list
Report Received Date
2022-09-06 00:00:00
Iyear
2022
Report Number
20220205
Supplemental Number
37082
Report Type
Original Final
Operator Id
31618
Name
Enterprise Products Operating Llc
Operator Street Address
1100 Louisiana Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-08-12 11:45:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
30.45195
Location Longitude
-97.33
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
0.1
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Notification From Public
Incident Identified Datetime
2022-08-11 08:20:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-08-12 12:07:00
Restart Datetime
2022-08-12 17:16:00
Communication State Fed Ind
No
On Site Datetime
2022-08-11 09:10:00
Confirmed Discovery Datetime
2022-08-12 11:45:00
Nrc Rpt Datetime
2022-08-12 12:23:00
Nrc Rpt Num
1344308
Additional Nrc Report Numbers
1344458
Ignite Ind
No
Upstream Action Taken
Operational Control
Upstream Oprtnl Cntrl Detail
Pressure Reduced To 678 Psi At Coupland Pump Station, Line Shut Down, Valve Closed At Coupland.
Downstream Action Taken
Operational Control
Downstream Oprtnl Cntrl Detail
Pressure Reduced To 720 Psi At Carmine Pump Station, Line Shut Down, Valve Closed At Carmine.
Num Pub Evacuated
0
Pipe Fac Name
Seminole Blue Mainline
Segment Name
Lid 1
Onshore State Abbreviation
Tx
Onshore Postal Code
78615
Onshore City Name
Coupland
Onshore County Name
Williamson
Designated Location
Milepost
Designated Name
380
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
60
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Tap Fitting(Stopple, Thread-O-Ring, Weld-O-Let, Etc.)
Installation Year
2008
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
2
Est Cost Prop Damage
22700
Est Cost Emergency
2432
Est Cost Environmental
0
Est Cost Other
0
Prpty
25134
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
890
Mop Psig
1440
Mop Cfr Section
Subpart E Pressure Test �195.406(A)(3)
Maop Established Date
1981-09-21 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Neither controller nor control room contributed to accident.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Threaded Connection/coupling Failure
Eq Failure Type
Threaded Connection/coupling Failure
Other Stripped Ind
Threaded Fitting
Additional Installation Ind
Yes
Preparer Name
T****** A* G********
Preparer Title
Senior Staff Pipeline Compliance Engineer
Preparer Email
T**********@e****.com
Preparer Telephone
713-381-6433
Prepared Date
2022-09-06 00:00:00
Local Contact Name
T****** A* G********
Local Contact Email
T**********@e****.com
Local Contact Telephone
713-381-6433
Authorizer Name
T****** A* G********
Authorizer Telephone
713-381-6433
Authorizer Title
Senior Staff Pipeline Compliance Engineer
Authorizer Email
T**********@e****.com
Narrative
At 08:20 on august 11, 2022, a landowner called the enterprise control center to report an odor and dead foliage in the vicinity of the right-of-way shared by seminole blue mainline and two other pipelines. Enterprise technician arrived on site at 09:10 and began investigating. At 11:50 lel monitor readings were detected. At that point an emergency one-call was placed in order to excavate the site. At 11:45 on august 12, 2022 a leaking threaded fitting was found on a stopple flange on the seminole blue mainline. The leak was determined to be reportable based on estimated repair costs. At 12:07 the line was shut down, pressure was reduced, and mainline valves closed at coupland and carmine. The leak was repaired by replacing the fitting with a plug, and the line restarted at 17:16. Initial nrc #1344308 48-hour update #1344458
| Report Received Date | 2022-09-06 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220205 |
| Supplemental Number | 37082 |
| Report Type | Original Final |
| Operator Id | 31618 PHMSA Enforcement |
| Name | Enterprise Products Operating Llc |
| Operator Street Address | 1100 Louisiana Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2022-08-12 11:45:00 |
| Time Zone | Central |
| Daylight Savings Ind | Yes |
| Location Latitude | 30.45195 Google Maps OpenStreetMap |
| Location Longitude | -97.33 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid) |
| Unintentional Release Bbls | 0.1 |
| Intentional Release Bbls | 0 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Notification From Public |
| Incident Identified Datetime | 2022-08-11 08:20:00 |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| On Off Shore | Onshore |
| Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-08-12 12:07:00 |
| Restart Datetime | 2022-08-12 17:16:00 |
| Communication State Fed Ind | No |
| On Site Datetime | 2022-08-11 09:10:00 |
| Confirmed Discovery Datetime | 2022-08-12 11:45:00 |
| Nrc Rpt Datetime | 2022-08-12 12:23:00 |
| Nrc Rpt Num | 1344308 NRC Report How to search |
| Additional Nrc Report Numbers | 1344458 |
| Ignite Ind | No |
| Upstream Action Taken | Operational Control |
| Upstream Oprtnl Cntrl Detail | Pressure Reduced To 678 Psi At Coupland Pump Station, Line Shut Down, Valve Closed At Coupland. |
| Downstream Action Taken | Operational Control |
| Downstream Oprtnl Cntrl Detail | Pressure Reduced To 720 Psi At Carmine Pump Station, Line Shut Down, Valve Closed At Carmine. |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Seminole Blue Mainline |
| Segment Name | Lid 1 |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 78615 |
| Onshore City Name | Coupland |
| Onshore County Name | Williamson |
| Designated Location | Milepost |
| Designated Name | 380 |
| Federal | No |
| Location Type | Pipeline Right-Of-Way |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Soil |
| Depth Of Cover | 60 |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| Item Involved | Tap Fitting(Stopple, Thread-O-Ring, Weld-O-Let, Etc.) |
| Installation Year | 2008 |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Connection Failure |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 2 |
| Est Cost Prop Damage | 22700 |
| Est Cost Emergency | 2432 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 25134 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 890 |
| Mop Psig | 1440 |
| Mop Cfr Section | Subpart E Pressure Test �195.406(A)(3) View CFR 49 §192 |
| Maop Established Date | 1981-09-21 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Internal Inspection Ind | Yes |
| Operation Complications Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Neither controller nor control room contributed to accident. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Threaded Connection/coupling Failure |
| Eq Failure Type | Threaded Connection/coupling Failure |
| Other Stripped Ind | Threaded Fitting |
| Additional Installation Ind | Yes |
| Preparer Name | T****** A* G******** |
| Preparer Title | Senior Staff Pipeline Compliance Engineer |
| Preparer Email | T**********@e****.com |
| Preparer Telephone | 713-381-6433 |
| Prepared Date | 2022-09-06 00:00:00 |
| Local Contact Name | T****** A* G******** |
| Local Contact Email | T**********@e****.com |
| Local Contact Telephone | 713-381-6433 |
| Authorizer Name | T****** A* G******** |
| Authorizer Telephone | 713-381-6433 |
| Authorizer Title | Senior Staff Pipeline Compliance Engineer |
| Authorizer Email | T**********@e****.com |
| Narrative | At 08:20 on august 11, 2022, a landowner called the enterprise control center to report an odor and dead foliage in the vicinity of the right-of-way shared by seminole blue mainline and two other pipelines. Enterprise technician arrived on site at 09:10 and began investigating. At 11:50 lel monitor readings were detected. At that point an emergency one-call was placed in order to excavate the site. At 11:45 on august 12, 2022 a leaking threaded fitting was found on a stopple flange on the seminole blue mainline. The leak was determined to be reportable based on estimated repair costs. At 12:07 the line was shut down, pressure was reduced, and mainline valves closed at coupland and carmine. The leak was repaired by replacing the fitting with a plug, and the line restarted at 17:16. Initial nrc #1344308 48-hour update #1344458 |