HL incident on 2022-08-01 — OK

Operator
Magellan Pipeline Company, Lp
Cause
Equipment Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$100,000
Incident datetime
2022-08-01 16:47
Report number
Location
OK
Narrative
At 16:47 on august 1, 2022, magellan operations personnel arrived at paola station to perform a line locate when product was discovered leaking from the unit #6 control valve. The valve was isolated and cleanup activities were initiated. The control valve was removed and blind flanges were installed. The #5-12" paola - kansas city line was then placed back into service, bypassing the unit at paola station. The failure analysis determined the upper and lower shaft bushings were both worn, allowing for shaft misalignment, which in turn allowed for excessive wear on the follower shaft seal on one side. The source of the release was the follower shaft seal on the outboard side (non-drive end) of the control valve. To prevent reoccurrence, the valve was replaced with a new, modern control valve. Additionally, a lessons-learned bulletin was created and shared within the company which illustrates the signs of shaft misalignment for field personnel to recognize and advise on the potential need to repair or replace the control valve beyond replacing the follower shaft seal. 2/13/2023 supplemental parts g, h
Detailed record list
Report Received Date
2022-08-31 00:00:00
Iyear
2022
Report Number
20220199
Supplemental Number
37705
Report Type
Supplemental Final
Operator Id
Name
Magellan Pipeline Company, Lp
Operator Street Address
100 West 5th Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2022-08-01 16:47:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
59
Recovered Bbls
36
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2022-08-01 16:47:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-08-01 17:00:00
Restart Datetime
2022-08-01 23:11:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-08-01 19:00:00
On Site Datetime
2022-08-01 16:47:00
Confirmed Discovery Datetime
2022-08-01 16:47:00
Nrc Rpt Datetime
2022-08-01 20:30:00
Nrc Rpt Num
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2022-08-01 16:47:00
Oil Spill Removal Org Ind
Yes
Osro Activated Datetime
2022-08-01 16:51:00
Osro Arrived On Site Dt
8/1/2022 18:15
Num Pub Evacuated
0
Pipe Fac Name
Paola Pump Station
Segment Name
Fac Id 540
Onshore State Abbreviation
Ks
Onshore Postal Code
66071
Onshore City Name
Paola
Onshore County Name
Miami
Designated Location
Milepost
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Valve
Valve Type
Mainline
Valve Mainline Type
Other
Valve Mainline Details
V Ball Control Valve
Valve Manufacturer
Fisher
Installation Year
1995
Manufactured Year
1995
Material Involved
Material Other Than Carbon Steel
Material Details
Soft Goods, Seal
Release Type
Leak
Leak Type
Seal Or Packing
Wildlife Impact Ind
Yes
Fish Aquatic Impact Ind
Yes
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Groundwater Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
15960
Est Cost Prop Damage
100000
Est Cost Emergency
350000
Est Cost Environmental
0
Est Cost Other
0
Prpty
465960
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
1100
Mop Psig
2160
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
1995-01-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The event occurred during normal operations and was not caused by or contributed to from the ops control controller. In addition, the event was below detectable thresholds within the scada/cpm systems.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
Seal (Not Pump Seal) Or Packing
Ief Addl Misalignment Ind
Yes
Preparer Name
C******* R******
Preparer Title
Strategic Data Engineer
Preparer Email
C***************@m*********.com
Preparer Telephone
9185747065
Prepared Date
2023-02-13 00:00:00
Authorizer Name
G**** R****
Authorizer Telephone
9185747165
Authorizer Title
Supervisor Integrity Management
Authorizer Email
G**********@m*********.com
Narrative
At 16:47 on august 1, 2022, magellan operations personnel arrived at paola station to perform a line locate when product was discovered leaking from the unit #6 control valve. The valve was isolated and cleanup activities were initiated. The control valve was removed and blind flanges were installed. The #5-12" paola - kansas city line was then placed back into service, bypassing the unit at paola station. The failure analysis determined the upper and lower shaft bushings were both worn, allowing for shaft misalignment, which in turn allowed for excessive wear on the follower shaft seal on one side. The source of the release was the follower shaft seal on the outboard side (non-drive end) of the control valve. To prevent reoccurrence, the valve was replaced with a new, modern control valve. Additionally, a lessons-learned bulletin was created and shared within the company which illustrates the signs of shaft misalignment for field personnel to recognize and advise on the potential need to repair or replace the control valve beyond replacing the follower shaft seal. 2/13/2023 supplemental parts g, h
Report Received Date 2022-08-31 00:00:00
Iyear 2022
Report Number 20220199
Supplemental Number 37705
Report Type Supplemental Final
Operator Id 22610 PHMSA Enforcement
Name Magellan Pipeline Company, Lp
Operator Street Address 100 West 5th Street
Operator City Name Tulsa
Operator State Abbreviation OK
Operator Postal Code 74103
Local Datetime 2022-08-01 16:47:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 38.502944 Google Maps OpenStreetMap
Location Longitude -94.869218 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Gasoline (Non-Ethanol)
Unintentional Release Bbls 59
Recovered Bbls 36
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2022-08-01 16:47:00
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Shutdown Datetime 2022-08-01 17:00:00
Restart Datetime 2022-08-01 23:11:00
Communication State Fed Ind Yes
Party Initiated Communication Operator
Initial Responder Com Datetime 2022-08-01 19:00:00
On Site Datetime 2022-08-01 16:47:00
Confirmed Discovery Datetime 2022-08-01 16:47:00
Nrc Rpt Datetime 2022-08-01 20:30:00
Nrc Rpt Num 1343267 NRC Report How to search
Ignite Ind No
Notify Qualified Indiv Ind Yes
Qualified Indiv Notif Datetime 2022-08-01 16:47:00
Oil Spill Removal Org Ind Yes
Osro Activated Datetime 2022-08-01 16:51:00
Osro Arrived On Site Dt 8/1/2022 18:15
Num Pub Evacuated 0
Pipe Fac Name Paola Pump Station
Segment Name Fac Id 540
Onshore State Abbreviation Ks
Onshore Postal Code 66071
Onshore City Name Paola
Onshore County Name Miami
Designated Location Milepost
Designated Name 0
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Valve
Valve Type Mainline
Valve Mainline Type Other
Valve Mainline Details V Ball Control Valve
Valve Manufacturer Fisher
Installation Year 1995
Manufactured Year 1995
Material Involved Material Other Than Carbon Steel
Material Details Soft Goods, Seal
Release Type Leak
Leak Type Seal Or Packing
Wildlife Impact Ind Yes
Fish Aquatic Impact Ind Yes
Soil Contamination Yes
Long Term Assessment No
Remediation Ind Yes
Groundwater Remed Ind Yes
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 15960
Est Cost Prop Damage 100000
Est Cost Emergency 350000
Est Cost Environmental 0
Est Cost Other 0
Prpty 465960
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 1100
Mop Psig 2160
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 1995-01-01 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function < 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The event occurred during normal operations and was not caused by or contributed to from the ops control controller. In addition, the event was below detectable thresholds within the scada/cpm systems.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Non-Threaded Connection Failure
Eq Failure Type Non-Threaded Connection Failure
Other Non Threaded Ind Seal (Not Pump Seal) Or Packing
Ief Addl Misalignment Ind Yes
Preparer Name C******* R******
Preparer Title Strategic Data Engineer
Preparer Email C***************@m*********.com
Preparer Telephone 9185747065
Prepared Date 2023-02-13 00:00:00
Authorizer Name G**** R****
Authorizer Telephone 9185747165
Authorizer Title Supervisor Integrity Management
Authorizer Email G**********@m*********.com
Narrative At 16:47 on august 1, 2022, magellan operations personnel arrived at paola station to perform a line locate when product was discovered leaking from the unit #6 control valve. The valve was isolated and cleanup activities were initiated. The control valve was removed and blind flanges were installed. The #5-12" paola - kansas city line was then placed back into service, bypassing the unit at paola station. The failure analysis determined the upper and lower shaft bushings were both worn, allowing for shaft misalignment, which in turn allowed for excessive wear on the follower shaft seal on one side. The source of the release was the follower shaft seal on the outboard side (non-drive end) of the control valve. To prevent reoccurrence, the valve was replaced with a new, modern control valve. Additionally, a lessons-learned bulletin was created and shared within the company which illustrates the signs of shaft misalignment for field personnel to recognize and advise on the potential need to repair or replace the control valve beyond replacing the follower shaft seal. 2/13/2023 supplemental parts g, h