HL incident on 2022-07-31 — TX
Operator
Energy Transfer Nederland Terminal Llc
Cause
Incorrect Operation
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$50
Incident datetime
2022-07-31 08:00
Report number
Location
TX
Narrative
On 7/31/22 at approximately 07:45, during a tank switch involving a crude oil receipt local operator opened wrong valve causing a pressure spike (<110% of mop) at the texoma manifold, a-bank causing oil leakage from a bolted flange gasket. The pressure was relieved and controlled and the flange was checked and retorqued by a mechanic. The line was static pressure tested and checked for leaks. Subsequent to the successful static check the line was put back into service. A vacuum truck collected the oil/water mixture and disposed of it in the water recycling facility.
Detailed record list
Report Received Date
2022-08-26 00:00:00
Iyear
2022
Report Number
20220197
Supplemental Number
37038
Report Type
Original Final
Operator Id
39706
Name
Energy Transfer Nederland Terminal Llc
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-07-31 07:45:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
29.99529
Location Longitude
-93.99296
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.64
Recovered Bbls
0.64
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2022-07-31 08:00:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Leak Area Was Isolated And Normal Operation Was Able To Continue
Communication State Fed Ind
No
On Site Datetime
2022-07-31 08:00:00
Confirmed Discovery Datetime
2022-07-31 08:00:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
No
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Nederland Terminal
Segment Name
Texoma Manifold
Onshore State Abbreviation
Tx
Onshore Postal Code
77627
Onshore City Name
Nederland
Onshore County Name
Jefferson
Designated Location
Survey Station No.
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Flange Assembly
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Material Other Than Carbon Steel
Material Details
Gasket Material
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
70
Est Cost Prop Damage
50
Est Cost Emergency
1000
Est Cost Environmental
0
Est Cost Other
0
Prpty
1120
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
300
Mop Psig
285
Mop Cfr Section
Subpart E Pressure Test �195.406(A)(3)
Maop Established Date
2018-05-08 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Exceeded Mop, But Did Not Exceed 110% Of Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
A review of the accident determined that there were no control room actions that contributed to the event.
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
1
Num Employees Failed
0
Cause
Incorrect Operation
Cause Details
Pipeline Or Equipment Overpressured
Operation Type
Pipeline Or Equipment Overpressured
Related Failure Follow Ind
Yes
Category Type
Normal Operating Conditions
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
T*** N*******
Preparer Title
Director - Regulatory Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
7139897126
Prepared Date
2022-08-26 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Regulatory Compliance
Authorizer Email
T************@e*************.com
Narrative
On 7/31/22 at approximately 07:45, during a tank switch involving a crude oil receipt local operator opened wrong valve causing a pressure spike (<110% of mop) at the texoma manifold, a-bank causing oil leakage from a bolted flange gasket. The pressure was relieved and controlled and the flange was checked and retorqued by a mechanic. The line was static pressure tested and checked for leaks. Subsequent to the successful static check the line was put back into service. A vacuum truck collected the oil/water mixture and disposed of it in the water recycling facility.
| Report Received Date | 2022-08-26 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220197 |
| Supplemental Number | 37038 |
| Report Type | Original Final |
| Operator Id | 39706 PHMSA Enforcement |
| Name | Energy Transfer Nederland Terminal Llc |
| Operator Street Address | 1300 Main Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2022-07-31 07:45:00 |
| Time Zone | Central |
| Daylight Savings Ind | Yes |
| Location Latitude | 29.99529 Google Maps OpenStreetMap |
| Location Longitude | -93.99296 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 0.64 |
| Recovered Bbls | 0.64 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2022-07-31 08:00:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Leak Area Was Isolated And Normal Operation Was Able To Continue |
| Communication State Fed Ind | No |
| On Site Datetime | 2022-07-31 08:00:00 |
| Confirmed Discovery Datetime | 2022-07-31 08:00:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Notify Qualified Indiv Ind | No |
| Oil Spill Removal Org Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Nederland Terminal |
| Segment Name | Texoma Manifold |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 77627 |
| Onshore City Name | Nederland |
| Onshore County Name | Jefferson |
| Designated Location | Survey Station No. |
| Designated Name | 0+00 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Flange Assembly |
| Installation Year | Unknown |
| Manufactured Year | Unknown |
| Material Involved | Material Other Than Carbon Steel |
| Material Details | Gasket Material |
| Release Type | Leak |
| Leak Type | Connection Failure |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 70 |
| Est Cost Prop Damage | 50 |
| Est Cost Emergency | 1000 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 1120 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 300 |
| Mop Psig | 285 |
| Mop Cfr Section | Subpart E Pressure Test �195.406(A)(3) View CFR 49 §192 |
| Maop Established Date | 2018-05-08 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Exceeded Mop, But Did Not Exceed 110% Of Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | A review of the accident determined that there were no control room actions that contributed to the event. |
| Employee Drug Test Ind | Yes |
| Contractor Drug Test Ind | No |
| Num Employees Tested | 1 |
| Num Employees Failed | 0 |
| Cause | Incorrect Operation |
| Cause Details | Pipeline Or Equipment Overpressured |
| Operation Type | Pipeline Or Equipment Overpressured |
| Related Failure Follow Ind | Yes |
| Category Type | Normal Operating Conditions |
| Operator Qualification Ind | Yes |
| Qualified Individuals | Yes, They Were Qualified For The Task(S) |
| Preparer Name | T*** N******* |
| Preparer Title | Director - Regulatory Compliance |
| Preparer Email | T************@e*************.com |
| Preparer Telephone | 7139897126 |
| Prepared Date | 2022-08-26 00:00:00 |
| Authorizer Name | T*** N******* |
| Authorizer Telephone | 713-989-7126 |
| Authorizer Title | Director - Regulatory Compliance |
| Authorizer Email | T************@e*************.com |
| Narrative | On 7/31/22 at approximately 07:45, during a tank switch involving a crude oil receipt local operator opened wrong valve causing a pressure spike (<110% of mop) at the texoma manifold, a-bank causing oil leakage from a bolted flange gasket. The pressure was relieved and controlled and the flange was checked and retorqued by a mechanic. The line was static pressure tested and checked for leaks. Subsequent to the successful static check the line was put back into service. A vacuum truck collected the oil/water mixture and disposed of it in the water recycling facility. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA