Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2022-07-26 — OK
Operator
Explorer Pipeline Co
Cause
Natural Force Damage
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2022-07-26 09:00
Report number
Location
OK
Narrative
On july 26, 2022, the east saint louis, missori area received historic record rainfall that resulted in subsequent flash flooding. Delivery to the east saint louis meter station was terminated and the pipeline was isolated from the 14-inch mainline at 04:40. A high sump alarm became active at 04:47, and a notification was provided from the control center to the local field representative. Due to high water levels, the local field representative was not able to access the east st. Louis station area until approximately 09:00. Upon arrival, the local field representative was assessing the flooded meter station and no visible release was present. However, it was later indicated that the station sump that was flooded could have contained some residual product based on scada data levels. The scada data level of the product in the sump was the volume that was reported as being released from the pipeline sump. An oil spill removal organization (osro) was dispatched to assist with the cleaning-up, and an aerial survey was conducted to assist with the site assessment.
Detailed record list
Report Received Date
2022-08-25 00:00:00
Iyear
2022
Report Number
20220192
Supplemental Number
37795
Report Type
Supplemental Final
Operator Id
4805
Name
Explorer Pipeline Co
Operator Street Address
Po Box 2650
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74101
Local Datetime
2022-07-26 09:00:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
38.58472981
Location Longitude
-90.18695537
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Mixture Of Refined Products (Transmix Or Other Mixture)
Unintentional Release Bbls
5.13
Recovered Bbls
0.7
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2022-07-26 09:00:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-07-26 04:40:00
Restart Datetime
2022-07-29 15:25:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-07-26 13:22:00
On Site Datetime
2022-07-26 10:46:00
Confirmed Discovery Datetime
2022-07-26 09:00:00
Nrc Rpt Datetime
2022-07-26 13:22:00
Nrc Rpt Num
1342615
Additional Nrc Report Numbers
1342822
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2022-07-26 08:30:00
Oil Spill Removal Org Ind
Yes
Osro Activated Datetime
2022-07-26 10:46:00
Osro Arrived On Site Dt
7/26/2022 13:00
Num Pub Evacuated
0
Pipe Fac Name
East Saint Louis Station
Segment Name
East Saint Louis Station
Onshore State Abbreviation
Il
Onshore Postal Code
62201
Onshore City Name
Sauget
Onshore County Name
St Clair
Designated Location
Milepost
Designated Name
19.9
Federal
No
Location Type
Originated On Operator-Controlled Property, But Then Flowed Or Migrated Off The Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Sump
Installation Year
1972
Manufactured Year
1972
Material Involved
Carbon Steel
Release Type
Overfill Or Overflow
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
450
Est Cost Prop Damage
0
Est Cost Emergency
15000
Est Cost Environmental
10000
Est Cost Other
0
Prpty
25450
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
0
Mop Psig
0
Mop Cfr Section
Other
Maop Established Date
1972-01-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
=< 20% Smys Regulated Gathering
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
Yes
Cpm Conf Ind
Yes
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Natural Force Damage
Cause Details
Heavy Rains/floods
Natural Force Type
Heavy Rains/floods
Heavy Rains Subtype
Flotation
Nf Extreme Weather Ind
Yes
Nf Other Ind
Yes
Nf Extreme Weather Details
Flash Flooding Associated With A 100-Year Rain Event.
Preparer Name
K**** E* B****
Preparer Title
Manager Dot And Regulatory Compliance
Preparer Email
K*****@e***.com
Preparer Telephone
9184935104
Prepared Date
2023-03-07 00:00:00
Local Contact Name
R***** M****
Local Contact Email
Area Manager
Local Contact Telephone
9185913182
Authorizer Name
L***** S******
Authorizer Telephone
9183595471
Authorizer Title
Vice President Hsse
Authorizer Email
L*******@e***.com
Narrative
On july 26, 2022, the east saint louis, missori area received historic record rainfall that resulted in subsequent flash flooding. Delivery to the east saint louis meter station was terminated and the pipeline was isolated from the 14-inch mainline at 04:40. A high sump alarm became active at 04:47, and a notification was provided from the control center to the local field representative. Due to high water levels, the local field representative was not able to access the east st. Louis station area until approximately 09:00. Upon arrival, the local field representative was assessing the flooded meter station and no visible release was present. However, it was later indicated that the station sump that was flooded could have contained some residual product based on scada data levels. The scada data level of the product in the sump was the volume that was reported as being released from the pipeline sump. An oil spill removal organization (osro) was dispatched to assist with the cleaning-up, and an aerial survey was conducted to assist with the site assessment.
| Report Received Date | 2022-08-25 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220192 |
| Supplemental Number | 37795 |
| Report Type | Supplemental Final |
| Operator Id | 4805 PHMSA Enforcement |
| Name | Explorer Pipeline Co |
| Operator Street Address | Po Box 2650 |
| Operator City Name | Tulsa |
| Operator State Abbreviation | OK |
| Operator Postal Code | 74101 |
| Local Datetime | 2022-07-26 09:00:00 |
| Time Zone | Central |
| Daylight Savings Ind | Yes |
| Location Latitude | 38.58472981 Google Maps OpenStreetMap |
| Location Longitude | -90.18695537 Google Maps OpenStreetMap |
| Commodity Released Type | Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions |
| Commodity Subtype | Mixture Of Refined Products (Transmix Or Other Mixture) |
| Unintentional Release Bbls | 5.13 |
| Recovered Bbls | 0.7 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2022-07-26 09:00:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-07-26 04:40:00 |
| Restart Datetime | 2022-07-29 15:25:00 |
| Communication State Fed Ind | Yes |
| Party Initiated Communication | Operator |
| Initial Responder Com Datetime | 2022-07-26 13:22:00 |
| On Site Datetime | 2022-07-26 10:46:00 |
| Confirmed Discovery Datetime | 2022-07-26 09:00:00 |
| Nrc Rpt Datetime | 2022-07-26 13:22:00 |
| Nrc Rpt Num | 1342615 NRC Report How to search |
| Additional Nrc Report Numbers | 1342822 |
| Ignite Ind | No |
| Notify Qualified Indiv Ind | Yes |
| Qualified Indiv Notif Datetime | 2022-07-26 08:30:00 |
| Oil Spill Removal Org Ind | Yes |
| Osro Activated Datetime | 2022-07-26 10:46:00 |
| Osro Arrived On Site Dt | 7/26/2022 13:00 |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | East Saint Louis Station |
| Segment Name | East Saint Louis Station |
| Onshore State Abbreviation | Il |
| Onshore Postal Code | 62201 |
| Onshore City Name | Sauget |
| Onshore County Name | St Clair |
| Designated Location | Milepost |
| Designated Name | 19.9 |
| Federal | No |
| Location Type | Originated On Operator-Controlled Property, But Then Flowed Or Migrated Off The Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Sump |
| Installation Year | 1972 |
| Manufactured Year | 1972 |
| Material Involved | Carbon Steel |
| Release Type | Overfill Or Overflow |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| High Pop Ind | Yes |
| High Pop Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 450 |
| Est Cost Prop Damage | 0 |
| Est Cost Emergency | 15000 |
| Est Cost Environmental | 10000 |
| Est Cost Other | 0 |
| Prpty | 25450 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 0 |
| Mop Psig | 0 |
| Mop Cfr Section | Other View CFR 49 §192 |
| Maop Established Date | 1972-01-01 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | =< 20% Smys Regulated Gathering |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | Yes |
| Cpm Conf Ind | Yes |
| Investigation Status | Yes, specify investigation result(s): (select all that apply) |
| Invest Schedule Ind | Yes |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Natural Force Damage |
| Cause Details | Heavy Rains/floods |
| Natural Force Type | Heavy Rains/floods |
| Heavy Rains Subtype | Flotation |
| Nf Extreme Weather Ind | Yes |
| Nf Other Ind | Yes |
| Nf Extreme Weather Details | Flash Flooding Associated With A 100-Year Rain Event. |
| Preparer Name | K**** E* B**** |
| Preparer Title | Manager Dot And Regulatory Compliance |
| Preparer Email | K*****@e***.com |
| Preparer Telephone | 9184935104 |
| Prepared Date | 2023-03-07 00:00:00 |
| Local Contact Name | R***** M**** |
| Local Contact Email | Area Manager |
| Local Contact Telephone | 9185913182 |
| Authorizer Name | L***** S****** |
| Authorizer Telephone | 9183595471 |
| Authorizer Title | Vice President Hsse |
| Authorizer Email | L*******@e***.com |
| Narrative | On july 26, 2022, the east saint louis, missori area received historic record rainfall that resulted in subsequent flash flooding. Delivery to the east saint louis meter station was terminated and the pipeline was isolated from the 14-inch mainline at 04:40. A high sump alarm became active at 04:47, and a notification was provided from the control center to the local field representative. Due to high water levels, the local field representative was not able to access the east st. Louis station area until approximately 09:00. Upon arrival, the local field representative was assessing the flooded meter station and no visible release was present. However, it was later indicated that the station sump that was flooded could have contained some residual product based on scada data levels. The scada data level of the product in the sump was the volume that was reported as being released from the pipeline sump. An oil spill removal organization (osro) was dispatched to assist with the cleaning-up, and an aerial survey was conducted to assist with the site assessment. |