HL incident on 2022-07-25 — OK

Operator
Magellan Pipeline Company, Lp
Cause
Incorrect Operation
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$0
Incident datetime
2022-07-25 05:00
Report number
Location
OK
Narrative
At 5:00 on july 25, 2022, magellan operations personnel were conducting a daily facility inspection when product was discovered leaking from 1/2" tubing on mov-410. The tubing was isolated and cleanup activities were initiated. Upon further investigation, it was determined the tubing was not properly installed by the contractor. The tubing was properly re-installed and the asset was placed back in service. To prevent a recurrence, all similar assets installed by the contractor were re-inspected to ensure proper installation. Supplemental/final (02-16-2023): part d7
Detailed record list
Report Received Date
2022-08-24 00:00:00
Iyear
2022
Report Number
20220190
Supplemental Number
39290
Report Type
Supplemental Final
Operator Id
Name
Magellan Pipeline Company, Lp
Operator Street Address
100 West 5th Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2022-07-25 05:00:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
5
Recovered Bbls
1.82
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2022-07-25 05:00:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Pipeline Was Already Shut Down At The Time Of The Incident
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-07-25 07:10:00
On Site Datetime
2022-07-25 05:00:00
Confirmed Discovery Datetime
2022-07-25 05:00:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2022-07-25 05:30:00
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Hearne Station
Segment Name
Fac Id 761
Onshore State Abbreviation
Tx
Onshore Postal Code
77859
Onshore City Name
Hearne
Onshore County Name
Robertson
Designated Location
Milepost
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Tubing
Tubing Material
Stainless Steel
Tubing Type
Rigid
Installation Year
2022
Manufactured Year
2022
Material Involved
Material Other Than Carbon Steel
Material Details
316ss
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Other Pop Ind
Yes
Other Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
910
Est Cost Prop Damage
0
Est Cost Emergency
42700
Est Cost Environmental
0
Est Cost Other
0
Prpty
43610
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
40
Mop Psig
275
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2022-01-03 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The leak was inside the facility on an asset that operations control does not monitor and was below leak detection thresholds that would have caused alarming in the control room.
Employee Drug Test Ind
No
Contractor Drug Test Ind
Yes
Num Contractors Tested
2
Num Contractors Failed
0
Cause
Incorrect Operation
Cause Details
Equipment Not Installed Properly
Operation Type
Equipment Not Installed Properly
Related Failure Follow Ind
Yes
Category Type
Construction
Operator Qualification Ind
Yes
Qualified Individuals
No, They Were Not Qualified For The Task(S) Nor Were They Performing The Task(S) Under The Direction And Observation Of A Qualified Individual
Preparer Name
C******* R******
Preparer Title
Strategic Data Engineer
Preparer Email
C***************@o****.com
Preparer Telephone
9185747065
Prepared Date
2024-03-06 00:00:00
Authorizer Name
T***** K***
Authorizer Telephone
9185747191
Authorizer Title
Supv. Integrity Mgmt And Regulatory Compliance
Authorizer Email
T**********@o****.com
Narrative
At 5:00 on july 25, 2022, magellan operations personnel were conducting a daily facility inspection when product was discovered leaking from 1/2" tubing on mov-410. The tubing was isolated and cleanup activities were initiated. Upon further investigation, it was determined the tubing was not properly installed by the contractor. The tubing was properly re-installed and the asset was placed back in service. To prevent a recurrence, all similar assets installed by the contractor were re-inspected to ensure proper installation. Supplemental/final (02-16-2023): part d7
Report Received Date 2022-08-24 00:00:00
Iyear 2022
Report Number 20220190
Supplemental Number 39290
Report Type Supplemental Final
Operator Id 22610 PHMSA Enforcement
Name Magellan Pipeline Company, Lp
Operator Street Address 100 West 5th Street
Operator City Name Tulsa
Operator State Abbreviation OK
Operator Postal Code 74103
Local Datetime 2022-07-25 05:00:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 30.864358 Google Maps OpenStreetMap
Location Longitude -96.577833 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Gasoline (Non-Ethanol)
Unintentional Release Bbls 5
Recovered Bbls 1.82
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2022-07-25 05:00:00
System Part Involved Onshore Terminal/tank Farm Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain Pipeline Was Already Shut Down At The Time Of The Incident
Communication State Fed Ind Yes
Party Initiated Communication Operator
Initial Responder Com Datetime 2022-07-25 07:10:00
On Site Datetime 2022-07-25 05:00:00
Confirmed Discovery Datetime 2022-07-25 05:00:00
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Notify Qualified Indiv Ind Yes
Qualified Indiv Notif Datetime 2022-07-25 05:30:00
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name Hearne Station
Segment Name Fac Id 761
Onshore State Abbreviation Tx
Onshore Postal Code 77859
Onshore City Name Hearne
Onshore County Name Robertson
Designated Location Milepost
Designated Name 0
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Tubing
Tubing Material Stainless Steel
Tubing Type Rigid
Installation Year 2022
Manufactured Year 2022
Material Involved Material Other Than Carbon Steel
Material Details 316ss
Release Type Leak
Leak Type Connection Failure
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
Other Pop Ind Yes
Other Pop Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 910
Est Cost Prop Damage 0
Est Cost Emergency 42700
Est Cost Environmental 0
Est Cost Other 0
Prpty 43610
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 40
Mop Psig 275
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 2022-01-03 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function < 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The leak was inside the facility on an asset that operations control does not monitor and was below leak detection thresholds that would have caused alarming in the control room.
Employee Drug Test Ind No
Contractor Drug Test Ind Yes
Num Contractors Tested 2
Num Contractors Failed 0
Cause Incorrect Operation
Cause Details Equipment Not Installed Properly
Operation Type Equipment Not Installed Properly
Related Failure Follow Ind Yes
Category Type Construction
Operator Qualification Ind Yes
Qualified Individuals No, They Were Not Qualified For The Task(S) Nor Were They Performing The Task(S) Under The Direction And Observation Of A Qualified Individual
Preparer Name C******* R******
Preparer Title Strategic Data Engineer
Preparer Email C***************@o****.com
Preparer Telephone 9185747065
Prepared Date 2024-03-06 00:00:00
Authorizer Name T***** K***
Authorizer Telephone 9185747191
Authorizer Title Supv. Integrity Mgmt And Regulatory Compliance
Authorizer Email T**********@o****.com
Narrative At 5:00 on july 25, 2022, magellan operations personnel were conducting a daily facility inspection when product was discovered leaking from 1/2" tubing on mov-410. The tubing was isolated and cleanup activities were initiated. Upon further investigation, it was determined the tubing was not properly installed by the contractor. The tubing was properly re-installed and the asset was placed back in service. To prevent a recurrence, all similar assets installed by the contractor were re-inspected to ensure proper installation. Supplemental/final (02-16-2023): part d7

All rights reserved. Copyright © by ClearPHMSA