HL incident on 2022-06-29 — TX

Operator
Kinder Morgan Liquid Terminals, Llc
Cause
Incorrect Operation
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$56,000
Incident datetime
2022-06-29 11:30
Report number
Location
TX
Narrative
At 09:52 a control room controller received a movement alarm on tank 170-4. The circulating pump was shut down and local operator was dispatched to walkout the lineup. At 11:30 a local operator confirmed a leak on 170-4 36" tank line inside of the vault containment. The flange on the pipe side of the tank valve was determined to be the source. Valve exv-46027 was isolated by the control room to stop the leak. Vault was pumped out and rinsed. Line was stripped in order to allow for maintenance to change the gasket. It was identified that the flange was not properly sealed during the initial bolt process that occurred in march 2022. Upon initial use of the 36" tank line, the leak occurred. Tank line piping cut and refitted to allow for proper seal on flange. In order to prevent recurrence, kinder morgan is in the process of updating engineering procedure cs40052426 (handling, installing, welding and testing of DOT regulated pipe) to include flange makeup tolerances. Additionally, kinder morgan terminals project managers were retrained regarding the requirement of using oq qualified contractors for these types of projects.
Detailed record list
Report Received Date
2022-07-28 00:00:00
Iyear
2022
Report Number
20220163
Supplemental Number
37745
Report Type
Supplemental Final
Operator Id
Name
Kinder Morgan Liquid Terminals, Llc
Operator Street Address
1001 Louisiana St, Suite 1000
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-06-29 11:30:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls
1020
Recovered Bbls
1020
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Incident Identified Datetime
2022-06-29 11:30:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Tank Secured
Communication State Fed Ind
No
On Site Datetime
2022-06-29 11:30:00
Confirmed Discovery Datetime
2022-06-29 11:30:00
Nrc Rpt Datetime
2022-06-29 16:38:00
Nrc Rpt Num
Additional Nrc Report Numbers
1340195
Ignite Ind
No
Notify Qualified Indiv Ind
No
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Pasadena Terminal
Segment Name
170-4 36" Tank Line
Onshore State Abbreviation
Tx
Onshore Postal Code
77506
Onshore City Name
Pasadena
Onshore County Name
Harris
Designated Location
Survey Station No.
Designated Name
Tank 170-4
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Flange Assembly
Installation Year
2022
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Commercially Nav Ind
Yes
Commercially Nav Yes No
Yes
Other Pop Ind
Yes
Other Pop Yes No
Yes
Usa Drinking Ind
Yes
Usa Drinking Yes No
Yes
Usa Ecological Ind
Yes
Usa Ecological Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
16000
Est Cost Prop Damage
56000
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
72000
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
25
Mop Psig
285
Mop Cfr Section
Mop Cfr Section Details
Flange Rating, Ansi 150
Maop Established Date
2022-03-01 00:00:00
Maop Reversal Flow Ind
Bi-Directional
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind
Yes
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Incorrect Operation
Cause Details
Equipment Not Installed Properly
Operation Type
Equipment Not Installed Properly
Related Inadequate Proc Ind
Yes
Category Type
Other Maintenance
Operator Qualification Ind
No
Preparer Name
A**** R*****
Preparer Title
Manager
Preparer Email
A***********@k***********.com
Preparer Telephone
7134206325
Prepared Date
2023-02-23 00:00:00
Local Contact Name
A**** R*****
Local Contact Email
A***********@k***********.com
Local Contact Telephone
7136206325
Authorizer Name
A**** R*****
Authorizer Telephone
7136206325
Authorizer Title
Manager
Authorizer Email
A***********@k***********.com
Narrative
At 09:52 a control room controller received a movement alarm on tank 170-4. The circulating pump was shut down and local operator was dispatched to walkout the lineup. At 11:30 a local operator confirmed a leak on 170-4 36" tank line inside of the vault containment. The flange on the pipe side of the tank valve was determined to be the source. Valve exv-46027 was isolated by the control room to stop the leak. Vault was pumped out and rinsed. Line was stripped in order to allow for maintenance to change the gasket. It was identified that the flange was not properly sealed during the initial bolt process that occurred in march 2022. Upon initial use of the 36" tank line, the leak occurred. Tank line piping cut and refitted to allow for proper seal on flange. In order to prevent recurrence, kinder morgan is in the process of updating engineering procedure cs40052426 (handling, installing, welding and testing of DOT regulated pipe) to include flange makeup tolerances. Additionally, kinder morgan terminals project managers were retrained regarding the requirement of using oq qualified contractors for these types of projects.
Report Received Date 2022-07-28 00:00:00
Iyear 2022
Report Number 20220163
Supplemental Number 37745
Report Type Supplemental Final
Operator Id 26041 PHMSA Enforcement
Name Kinder Morgan Liquid Terminals, Llc
Operator Street Address 1001 Louisiana St, Suite 1000
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2022-06-29 11:30:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 29.721793 Google Maps OpenStreetMap
Location Longitude -95.202653 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls 1020
Recovered Bbls 1020
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Incident Identified Datetime 2022-06-29 11:30:00
System Part Involved Onshore Terminal/tank Farm Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain Tank Secured
Communication State Fed Ind No
On Site Datetime 2022-06-29 11:30:00
Confirmed Discovery Datetime 2022-06-29 11:30:00
Nrc Rpt Datetime 2022-06-29 16:38:00
Nrc Rpt Num 1340162 NRC Report How to search
Additional Nrc Report Numbers 1340195
Ignite Ind No
Notify Qualified Indiv Ind No
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name Pasadena Terminal
Segment Name 170-4 36" Tank Line
Onshore State Abbreviation Tx
Onshore Postal Code 77506
Onshore City Name Pasadena
Onshore County Name Harris
Designated Location Survey Station No.
Designated Name Tank 170-4
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Intrastate
Item Involved Flange Assembly
Installation Year 2022
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Connection Failure
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
Commercially Nav Ind Yes
Commercially Nav Yes No Yes
Other Pop Ind Yes
Other Pop Yes No Yes
Usa Drinking Ind Yes
Usa Drinking Yes No Yes
Usa Ecological Ind Yes
Usa Ecological Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 16000
Est Cost Prop Damage 56000
Est Cost Emergency 0
Est Cost Environmental 0
Est Cost Other 0
Prpty 72000
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 25
Mop Psig 285
Mop Cfr Section Other View CFR 49 §192
Mop Cfr Section Details Flange Rating, Ansi 150
Maop Established Date 2022-03-01 00:00:00
Maop Reversal Flow Ind Bi-Directional
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Cpm In Place Ind No
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind Yes
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Incorrect Operation
Cause Details Equipment Not Installed Properly
Operation Type Equipment Not Installed Properly
Related Inadequate Proc Ind Yes
Category Type Other Maintenance
Operator Qualification Ind No
Preparer Name A**** R*****
Preparer Title Manager
Preparer Email A***********@k***********.com
Preparer Telephone 7134206325
Prepared Date 2023-02-23 00:00:00
Local Contact Name A**** R*****
Local Contact Email A***********@k***********.com
Local Contact Telephone 7136206325
Authorizer Name A**** R*****
Authorizer Telephone 7136206325
Authorizer Title Manager
Authorizer Email A***********@k***********.com
Narrative At 09:52 a control room controller received a movement alarm on tank 170-4. The circulating pump was shut down and local operator was dispatched to walkout the lineup. At 11:30 a local operator confirmed a leak on 170-4 36" tank line inside of the vault containment. The flange on the pipe side of the tank valve was determined to be the source. Valve exv-46027 was isolated by the control room to stop the leak. Vault was pumped out and rinsed. Line was stripped in order to allow for maintenance to change the gasket. It was identified that the flange was not properly sealed during the initial bolt process that occurred in march 2022. Upon initial use of the 36" tank line, the leak occurred. Tank line piping cut and refitted to allow for proper seal on flange. In order to prevent recurrence, kinder morgan is in the process of updating engineering procedure cs40052426 (handling, installing, welding and testing of DOT regulated pipe) to include flange makeup tolerances. Additionally, kinder morgan terminals project managers were retrained regarding the requirement of using oq qualified contractors for these types of projects.

All rights reserved. Copyright © by ClearPHMSA