HL incident on 2022-06-14 — TX

Operator
Inland Corporation
Cause
Equipment Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$500
Incident datetime
2022-06-14 15:20
Report number
Location
TX
Narrative
On 6/14/2022 at approximately 15:20, station operator reported an appearance of gasoline throughout the yard. This corresponded with a shutdown as well as a product change. Operator shutdown and isolated the station. Osros were dispatched to support the clean-up and repair efforts. After excavation of the area an underground flanged connect was found to be leaking due to an aged paper gasket failure. Replaced paper gasket with standard gasket. The line was static pressure tested to ensure no additional leaks were present and ultimately returned to service. Clean up of the affected soil and gravel continued by removing all from the station for proper disposal. Clean soil and gravel were brought in.
Detailed record list
Report Received Date
2022-07-14 00:00:00
Iyear
2022
Report Number
20220148
Supplemental Number
36858
Report Type
Original Final
Operator Id
Name
Inland Corporation
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-06-14 15:20:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
75.5
Recovered Bbls
54
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2022-06-14 15:20:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-06-14 15:20:00
Restart Datetime
2022-06-16 13:15:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-06-14 20:14:00
On Site Datetime
2022-06-14 16:30:00
Confirmed Discovery Datetime
2022-06-14 15:20:00
Nrc Rpt Datetime
2022-06-14 19:11:00
Nrc Rpt Num
Additional Nrc Report Numbers
1338962
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2022-06-14 16:02:00
Oil Spill Removal Org Ind
Yes
Osro Activated Datetime
2022-06-14 21:00:00
Osro Arrived On Site Dt
6/14/2022 21:00
Num Pub Evacuated
0
Pipe Fac Name
Lima Station
Segment Name
13212 Sl10 10" Lima To Columbus
Onshore State Abbreviation
Oh
Onshore Postal Code
45804
Onshore City Name
Lima
Onshore County Name
Allen
Designated Location
Survey Station No.
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
40
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Flange Assembly
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Material Other Than Carbon Steel
Material Details
Paper Gasket
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
7000
Est Cost Prop Damage
500
Est Cost Emergency
85000
Est Cost Environmental
0
Est Cost Other
0
Prpty
92500
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
150
Mop Psig
720
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
1964-01-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
A review of the event determined there were no control room actions that led to or contributed to the failure.
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
1
Num Employees Failed
0
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
Gasket
Eq Additional Other Ind
Yes
Eq Additional Other Details
Age Related Deterioration Of Paper Gasket At Underground Flanged Connection.
Io Equipment Overpressure Ind
Yes
Preparer Name
T*** N*******
Preparer Title
Director - Regulatory Compliance
Preparer Email
T************@e*************.com
Preparer Telephone
713-989-7126
Prepared Date
2022-07-14 00:00:00
Authorizer Name
T*** N*******
Authorizer Telephone
713-989-7126
Authorizer Title
Director - Regulatory Compliance
Authorizer Email
T************@e*************.com
Narrative
On 6/14/2022 at approximately 15:20, station operator reported an appearance of gasoline throughout the yard. This corresponded with a shutdown as well as a product change. Operator shutdown and isolated the station. Osros were dispatched to support the clean-up and repair efforts. After excavation of the area an underground flanged connect was found to be leaking due to an aged paper gasket failure. Replaced paper gasket with standard gasket. The line was static pressure tested to ensure no additional leaks were present and ultimately returned to service. Clean up of the affected soil and gravel continued by removing all from the station for proper disposal. Clean soil and gravel were brought in.
Report Received Date 2022-07-14 00:00:00
Iyear 2022
Report Number 20220148
Supplemental Number 36858
Report Type Original Final
Operator Id 32683 PHMSA Enforcement
Name Inland Corporation
Operator Street Address 1300 Main Street
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2022-06-14 15:20:00
Time Zone Eastern
Daylight Savings Ind Yes
Location Latitude 40.709248 Google Maps OpenStreetMap
Location Longitude -84.13135 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Gasoline (Non-Ethanol)
Unintentional Release Bbls 75.5
Recovered Bbls 54
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2022-06-14 15:20:00
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind Yes
Shutdown Datetime 2022-06-14 15:20:00
Restart Datetime 2022-06-16 13:15:00
Communication State Fed Ind Yes
Party Initiated Communication Operator
Initial Responder Com Datetime 2022-06-14 20:14:00
On Site Datetime 2022-06-14 16:30:00
Confirmed Discovery Datetime 2022-06-14 15:20:00
Nrc Rpt Datetime 2022-06-14 19:11:00
Nrc Rpt Num 1338773 NRC Report How to search
Additional Nrc Report Numbers 1338962
Ignite Ind No
Notify Qualified Indiv Ind Yes
Qualified Indiv Notif Datetime 2022-06-14 16:02:00
Oil Spill Removal Org Ind Yes
Osro Activated Datetime 2022-06-14 21:00:00
Osro Arrived On Site Dt 6/14/2022 21:00
Num Pub Evacuated 0
Pipe Fac Name Lima Station
Segment Name 13212 Sl10 10" Lima To Columbus
Onshore State Abbreviation Oh
Onshore Postal Code 45804
Onshore City Name Lima
Onshore County Name Allen
Designated Location Survey Station No.
Designated Name 0+00
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 40
Crossing No
Pipe Facility Type Interstate
Item Involved Flange Assembly
Installation Year Unknown
Manufactured Year Unknown
Material Involved Material Other Than Carbon Steel
Material Details Paper Gasket
Release Type Leak
Leak Type Connection Failure
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 7000
Est Cost Prop Damage 500
Est Cost Emergency 85000
Est Cost Environmental 0
Est Cost Other 0
Prpty 92500
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 150
Mop Psig 720
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 1964-01-01 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details A review of the event determined there were no control room actions that led to or contributed to the failure.
Employee Drug Test Ind Yes
Contractor Drug Test Ind No
Num Employees Tested 1
Num Employees Failed 0
Cause Equipment Failure
Cause Details Non-Threaded Connection Failure
Eq Failure Type Non-Threaded Connection Failure
Other Non Threaded Ind Gasket
Eq Additional Other Ind Yes
Eq Additional Other Details Age Related Deterioration Of Paper Gasket At Underground Flanged Connection.
Io Equipment Overpressure Ind Yes
Preparer Name T*** N*******
Preparer Title Director - Regulatory Compliance
Preparer Email T************@e*************.com
Preparer Telephone 713-989-7126
Prepared Date 2022-07-14 00:00:00
Authorizer Name T*** N*******
Authorizer Telephone 713-989-7126
Authorizer Title Director - Regulatory Compliance
Authorizer Email T************@e*************.com
Narrative On 6/14/2022 at approximately 15:20, station operator reported an appearance of gasoline throughout the yard. This corresponded with a shutdown as well as a product change. Operator shutdown and isolated the station. Osros were dispatched to support the clean-up and repair efforts. After excavation of the area an underground flanged connect was found to be leaking due to an aged paper gasket failure. Replaced paper gasket with standard gasket. The line was static pressure tested to ensure no additional leaks were present and ultimately returned to service. Clean up of the affected soil and gravel continued by removing all from the station for proper disposal. Clean soil and gravel were brought in.

All rights reserved. Copyright © by ClearPHMSA