Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2022-06-27 — OH
Operator
Marathon Pipe Line Llc
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2022-06-27 21:15
Report number
Location
OH
Narrative
On june 27, 2022 at 21:15 hrs. Mt, the mpl control room was completing routine camera checks of the ft. Laramie station and noticed a crude oil release that was entirely contained within the station near pump unit #1. Immediate actions were taken by the controller to shut down the wamsutter-ft. Laramie 8-inch pipeline and to notify local operations. Local operations personnel immediately dispatched to the station, arriving on june 28th at 1:00 hrs. Mt. Upon arrival, mpl operations confirmed the release and took actions to clean it up. A failed stud on the valve cylinder cap of the pump was identified as the source of the leak. It was determined that the stud failed because it had been manufactured out of round by 15 thousandths of an inch, an indication that the stud had been over-torqued during the manufacturing process. Mpl worked with the manufacturer to ensure that appropriate actions were taken to replace the faulty studs. Once the studs were replaced and it was determined that the pump had been adequately repaired, the pipeline was restarted on july 1, 2022 at 18:33 hrs mt. August 9, 2022 update - no additional changes, report is submitted as final.
Detailed record list
Report Received Date
2022-07-08 00:00:00
Iyear
2022
Report Number
20220145
Supplemental Number
36990
Report Type
Supplemental Final
Operator Id
32147
Name
Marathon Pipe Line Llc
Operator Street Address
539 South Main Street
Operator City Name
Findlay
Operator State Abbreviation
OH
Operator Postal Code
45840
Local Datetime
2022-06-27 21:15:00
Time Zone
Mountain
Daylight Savings Ind
Yes
Location Latitude
42.208021
Location Longitude
-104.513677
Commodity Released Type
Crude Oil
Unintentional Release Bbls
7.5
Recovered Bbls
7.5
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Controller
Operator Type
Operator Employee
Incident Identified Datetime
2022-06-27 21:15:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-06-27 21:19:00
Restart Datetime
2022-07-01 18:36:00
Communication State Fed Ind
No
On Site Datetime
2022-06-28 01:00:00
Confirmed Discovery Datetime
2022-06-28 01:05:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
No
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Wamsutter-Ft. Laramie 8-Inch Crude (Slcc)
Segment Name
Ft. Laramie Station
Onshore State Abbreviation
Wy
Onshore Postal Code
82223
Onshore City Name
Not Within A Municipality
Onshore County Name
Goshen County
Designated Location
Milepost
Designated Name
Ft Lar. Sta
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pump
Pump Type
Positive Displacement
Pump Service Type
Mainline
Installation Year
2022
Manufactured Year
2021
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Other
Leak Type Other
Stud On Pump Sheared Off.
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
150
Est Cost Prop Damage
0
Est Cost Emergency
0
Est Cost Environmental
16500
Est Cost Other
0
Prpty
16650
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
1616
Mop Psig
2220
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2022-02-18 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The release was attributed to faulty bolts on the piston cap studs on the manufactured pump.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Pump Or Pump-Related Equipment
Eq Failure Type
Pump Or Pump-Related Equipment
Other Pump Ind
Other
Other Pump Details
Stud On Pump Sheared Off.
Additional Defect Ind
Yes
Preparer Name
J*** M*****
Preparer Email
J******@m****************.com
Preparer Telephone
6513489017
Prepared Date
2022-08-18 00:00:00
Authorizer Name
A**** M*******
Authorizer Telephone
12106266343
Authorizer Email
A*********@m****************.com
Narrative
On june 27, 2022 at 21:15 hrs. Mt, the mpl control room was completing routine camera checks of the ft. Laramie station and noticed a crude oil release that was entirely contained within the station near pump unit #1. Immediate actions were taken by the controller to shut down the wamsutter-ft. Laramie 8-inch pipeline and to notify local operations. Local operations personnel immediately dispatched to the station, arriving on june 28th at 1:00 hrs. Mt. Upon arrival, mpl operations confirmed the release and took actions to clean it up. A failed stud on the valve cylinder cap of the pump was identified as the source of the leak. It was determined that the stud failed because it had been manufactured out of round by 15 thousandths of an inch, an indication that the stud had been over-torqued during the manufacturing process. Mpl worked with the manufacturer to ensure that appropriate actions were taken to replace the faulty studs. Once the studs were replaced and it was determined that the pump had been adequately repaired, the pipeline was restarted on july 1, 2022 at 18:33 hrs mt. August 9, 2022 update - no additional changes, report is submitted as final.
| Report Received Date | 2022-07-08 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220145 |
| Supplemental Number | 36990 |
| Report Type | Supplemental Final |
| Operator Id | 32147 PHMSA Enforcement |
| Name | Marathon Pipe Line Llc |
| Operator Street Address | 539 South Main Street |
| Operator City Name | Findlay |
| Operator State Abbreviation | OH |
| Operator Postal Code | 45840 |
| Local Datetime | 2022-06-27 21:15:00 |
| Time Zone | Mountain |
| Daylight Savings Ind | Yes |
| Location Latitude | 42.208021 Google Maps OpenStreetMap |
| Location Longitude | -104.513677 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 7.5 |
| Recovered Bbls | 7.5 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Controller |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2022-06-27 21:15:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Status When Identified | Normal Operation, Includes Pauses Between Batches And During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-06-27 21:19:00 |
| Restart Datetime | 2022-07-01 18:36:00 |
| Communication State Fed Ind | No |
| On Site Datetime | 2022-06-28 01:00:00 |
| Confirmed Discovery Datetime | 2022-06-28 01:05:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Notify Qualified Indiv Ind | No |
| Oil Spill Removal Org Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Wamsutter-Ft. Laramie 8-Inch Crude (Slcc) |
| Segment Name | Ft. Laramie Station |
| Onshore State Abbreviation | Wy |
| Onshore Postal Code | 82223 |
| Onshore City Name | Not Within A Municipality |
| Onshore County Name | Goshen County |
| Designated Location | Milepost |
| Designated Name | Ft Lar. Sta |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Pump |
| Pump Type | Positive Displacement |
| Pump Service Type | Mainline |
| Installation Year | 2022 |
| Manufactured Year | 2021 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Other |
| Leak Type Other | Stud On Pump Sheared Off. |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 150 |
| Est Cost Prop Damage | 0 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 16500 |
| Est Cost Other | 0 |
| Prpty | 16650 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Accident Psig | 1616 |
| Mop Psig | 2220 |
| Mop Cfr Section | Component Design Pressure �195.406(A)(2) View CFR 49 §192 |
| Maop Established Date | 2022-02-18 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | The release was attributed to faulty bolts on the piston cap studs on the manufactured pump. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Pump Or Pump-Related Equipment |
| Eq Failure Type | Pump Or Pump-Related Equipment |
| Other Pump Ind | Other |
| Other Pump Details | Stud On Pump Sheared Off. |
| Additional Defect Ind | Yes |
| Preparer Name | J*** M***** |
| Preparer Email | J******@m****************.com |
| Preparer Telephone | 6513489017 |
| Prepared Date | 2022-08-18 00:00:00 |
| Authorizer Name | A**** M******* |
| Authorizer Telephone | 12106266343 |
| Authorizer Email | A*********@m****************.com |
| Narrative | On june 27, 2022 at 21:15 hrs. Mt, the mpl control room was completing routine camera checks of the ft. Laramie station and noticed a crude oil release that was entirely contained within the station near pump unit #1. Immediate actions were taken by the controller to shut down the wamsutter-ft. Laramie 8-inch pipeline and to notify local operations. Local operations personnel immediately dispatched to the station, arriving on june 28th at 1:00 hrs. Mt. Upon arrival, mpl operations confirmed the release and took actions to clean it up. A failed stud on the valve cylinder cap of the pump was identified as the source of the leak. It was determined that the stud failed because it had been manufactured out of round by 15 thousandths of an inch, an indication that the stud had been over-torqued during the manufacturing process. Mpl worked with the manufacturer to ensure that appropriate actions were taken to replace the faulty studs. Once the studs were replaced and it was determined that the pump had been adequately repaired, the pipeline was restarted on july 1, 2022 at 18:33 hrs mt. August 9, 2022 update - no additional changes, report is submitted as final. |
External Resources