HL incident on 2022-06-08 — TX

Operator
Mobil Pipe Line Company
Cause
Corrosion Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$0
Incident datetime
2022-06-08 15:25
Report number
Location
TX
Narrative
At 3:15 pm on june 8, 2022, the mont belvieu operation first line supervisor (fls) received a call from oneok stating that there was a release occurring inside of purity station. Fls called operations control center, and they remotely isolated the inlet and outlet of the facility. Fls and technician arrived to site, accessed upwind, and isolated the system closer to the leak source using manual valves. The isolated section of pipe was allowed to bleed off until line pressure reached 0 psig, resulting in a 184.32-pound release of isobutane to atmosphere. Atmospheric corrosion was located on the bottom of piping at interface with pipe support, causing a pinhole leak. To prevent recurrence, operations removed the pipe spool and installed pressure rated blind flanges. As part of its mitigation plan, mobil pipe line will have a qualified corrosion inspector, from outside the operational area, perform a new atmospheric corrosion inspection within the storage area of operation, including pipe supports. Per our atmospheric corrosion program, we will develop a repair plan for anomalies, if any, found during the cold-eyes review. Area management will also purchase handheld mirrors to assist corrosion technicians with inspections in hard to reach areas, including to pipe to support interfaces. In addition, corrosion technician will be requalified with a skills demonstration on perform atmospheric inspections to confirm inspections are meeting our corrosion control program practices.
Detailed record list
Report Received Date
2022-07-07 00:00:00
Iyear
2022
Report Number
20220144
Supplemental Number
37801
Report Type
Supplemental Final
Operator Id
Name
Mobil Pipe Line Company
Operator Street Address
22777 Springwoods Village Parkway E2.2b-Emp
Operator City Name
Spring
Operator State Abbreviation
TX
Operator Postal Code
77389
Local Datetime
2022-06-08 20:06:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
0.96
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Other
Accident Details
Third-Party Was Working In The Area.
Incident Identified Datetime
2022-06-08 15:25:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Status When Identified
Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
Pipeline Was Down, Awaiting Batch Change.
Communication State Fed Ind
No
On Site Datetime
2022-06-08 15:25:00
Confirmed Discovery Datetime
2022-06-08 20:06:00
Nrc Rpt Datetime
2022-06-08 16:47:00
Nrc Rpt Num
Additional Nrc Report Numbers
1338395
Ignite Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Mont Belvieu Purity Station
Segment Name
Mpl-118 Hull - Mont Belvieu Lpg Purity
Onshore State Abbreviation
Tx
Onshore Postal Code
77580
Onshore City Name
Mont Belvieu
Onshore County Name
Chambers
Designated Location
Survey Station No.
Designated Name
85+45
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Meter/prover
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Other Pop Ind
Yes
Other Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
68
Est Cost Prop Damage
0
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
1875
Est Cost Other Details
Labor Cost To Remove The Pipe Segment And Install Blind Flanges.
Prpty
1943
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
362
Mop Psig
660
Mop Cfr Section
Subpart E Pressure Test �195.406(A)(3)
Maop Established Date
1976-07-30 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
Yes
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
Localized Pitting
Atmosphere Corrosion Ind
Yes
Field Exam Basis Ind
Yes
Underground Location
No
Externally Coated
Yes
Prior Damage
Yes
Preparer Name
D**** R* S*****
Preparer Title
Pipeline Safety Advisor
Preparer Email
D*************@e*********.com
Preparer Telephone
832-624-7531
Prepared Date
2022-07-27 00:00:00
Authorizer Name
T****** H* B*****
Authorizer Telephone
832-624-7775
Authorizer Title
Regulatory Compliance Supervisor
Authorizer Email
T***************@e*********.com
Narrative
At 3:15 pm on june 8, 2022, the mont belvieu operation first line supervisor (fls) received a call from oneok stating that there was a release occurring inside of purity station. Fls called operations control center, and they remotely isolated the inlet and outlet of the facility. Fls and technician arrived to site, accessed upwind, and isolated the system closer to the leak source using manual valves. The isolated section of pipe was allowed to bleed off until line pressure reached 0 psig, resulting in a 184.32-pound release of isobutane to atmosphere. Atmospheric corrosion was located on the bottom of piping at interface with pipe support, causing a pinhole leak. To prevent recurrence, operations removed the pipe spool and installed pressure rated blind flanges. As part of its mitigation plan, mobil pipe line will have a qualified corrosion inspector, from outside the operational area, perform a new atmospheric corrosion inspection within the storage area of operation, including pipe supports. Per our atmospheric corrosion program, we will develop a repair plan for anomalies, if any, found during the cold-eyes review. Area management will also purchase handheld mirrors to assist corrosion technicians with inspections in hard to reach areas, including to pipe to support interfaces. In addition, corrosion technician will be requalified with a skills demonstration on perform atmospheric inspections to confirm inspections are meeting our corrosion control program practices.
Report Received Date 2022-07-07 00:00:00
Iyear 2022
Report Number 20220144
Supplemental Number 37801
Report Type Supplemental Final
Operator Id 12628 PHMSA Enforcement
Name Mobil Pipe Line Company
Operator Street Address 22777 Springwoods Village Parkway E2.2b-Emp
Operator City Name Spring
Operator State Abbreviation TX
Operator Postal Code 77389
Local Datetime 2022-06-08 20:06:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 29.861793 Google Maps OpenStreetMap
Location Longitude -94.888812 Google Maps OpenStreetMap
Commodity Released Type Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls 0.96
Intentional Release Bbls 0
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Other
Accident Details Third-Party Was Working In The Area.
Incident Identified Datetime 2022-06-08 15:25:00
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Status When Identified Normal Operation, Includes Pauses Between Batches And During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain Pipeline Was Down, Awaiting Batch Change.
Communication State Fed Ind No
On Site Datetime 2022-06-08 15:25:00
Confirmed Discovery Datetime 2022-06-08 20:06:00
Nrc Rpt Datetime 2022-06-08 16:47:00
Nrc Rpt Num 1338176 NRC Report How to search
Additional Nrc Report Numbers 1338395
Ignite Ind No
Num Pub Evacuated 0
Pipe Fac Name Mont Belvieu Purity Station
Segment Name Mpl-118 Hull - Mont Belvieu Lpg Purity
Onshore State Abbreviation Tx
Onshore Postal Code 77580
Onshore City Name Mont Belvieu
Onshore County Name Chambers
Designated Location Survey Station No.
Designated Name 85+45
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Intrastate
Item Involved Meter/prover
Installation Year Unknown
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
Other Pop Ind Yes
Other Pop Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 68
Est Cost Prop Damage 0
Est Cost Emergency 0
Est Cost Environmental 0
Est Cost Other 1875
Est Cost Other Details Labor Cost To Remove The Pipe Segment And Install Blind Flanges.
Prpty 1943
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 362
Mop Psig 660
Mop Cfr Section Subpart E Pressure Test �195.406(A)(3) View CFR 49 §192
Maop Established Date 1976-07-30 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind Yes
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind Yes
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details External Corrosion
Internal External External Corrosion
Visual Exam Results Localized Pitting
Atmosphere Corrosion Ind Yes
Field Exam Basis Ind Yes
Underground Location No
Externally Coated Yes
Prior Damage Yes
Preparer Name D**** R* S*****
Preparer Title Pipeline Safety Advisor
Preparer Email D*************@e*********.com
Preparer Telephone 832-624-7531
Prepared Date 2022-07-27 00:00:00
Authorizer Name T****** H* B*****
Authorizer Telephone 832-624-7775
Authorizer Title Regulatory Compliance Supervisor
Authorizer Email T***************@e*********.com
Narrative At 3:15 pm on june 8, 2022, the mont belvieu operation first line supervisor (fls) received a call from oneok stating that there was a release occurring inside of purity station. Fls called operations control center, and they remotely isolated the inlet and outlet of the facility. Fls and technician arrived to site, accessed upwind, and isolated the system closer to the leak source using manual valves. The isolated section of pipe was allowed to bleed off until line pressure reached 0 psig, resulting in a 184.32-pound release of isobutane to atmosphere. Atmospheric corrosion was located on the bottom of piping at interface with pipe support, causing a pinhole leak. To prevent recurrence, operations removed the pipe spool and installed pressure rated blind flanges. As part of its mitigation plan, mobil pipe line will have a qualified corrosion inspector, from outside the operational area, perform a new atmospheric corrosion inspection within the storage area of operation, including pipe supports. Per our atmospheric corrosion program, we will develop a repair plan for anomalies, if any, found during the cold-eyes review. Area management will also purchase handheld mirrors to assist corrosion technicians with inspections in hard to reach areas, including to pipe to support interfaces. In addition, corrosion technician will be requalified with a skills demonstration on perform atmospheric inspections to confirm inspections are meeting our corrosion control program practices.