HL incident on 2022-06-02 — TX

Operator
Plains Marketing, L.p.
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$4,500
Incident datetime
2022-06-02 07:45
Report number
Location
TX
Narrative
Approximately 35 gallons of crude oil were released from tank 1014b tank header piping at patoka station. The date and time of the release (part a q4) is indicative of the earliest possible time the release could have started, as it was the last time the incident location had been visited and confirmed to be no release of crude oil. A supplemental report will be submitted pending further investigation into the cause of the incident. Supplemental report: the cause of the release is attributed to internal corrosion as a result of mic. To prevent future incidents, plains performed a low-flow/no-flow assessment and installed isolations in certain areas to drain fluid when tanks are shut in.
Detailed record list
Report Received Date
2022-07-01 00:00:00
Iyear
2022
Report Number
20220136
Supplemental Number
37637
Report Type
Supplemental Final
Operator Id
Name
Plains Marketing, L.p.
Operator Street Address
333 Clay Street, Suite 1900
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-06-02 06:00:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
-89.07414376
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.8
Recovered Bbls
0.8
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2022-06-02 07:45:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Idle
Communication State Fed Ind
No
On Site Datetime
2022-06-02 07:45:00
Confirmed Discovery Datetime
2022-06-02 07:45:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2022-06-02 07:45:00
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Patoka Terminal
Segment Name
Tank 1014b Tank Header
Onshore State Abbreviation
Il
Onshore Postal Code
62892
Onshore City Name
Vernon
Onshore County Name
Marion
Designated Location
Milepost
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pipe
Pipe Type
Pipe Body
Puddle Weld Ind
No
Pipe Diameter
36
Pipe Wall Thickness
0.5
Pipe Smys
24000
Pipe Specification
Unknown
Pipe Seam Type
Other
Pipe Seam Details
Concentric Reducer
Pipe Manufacturer
Unknown
Pipe Coating Type
Epoxy Other Than Fbe
Coating Applied Ind
Yes
Installation Year
2012
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
100
Est Cost Prop Damage
4500
Est Cost Emergency
1500
Est Cost Environmental
0
Est Cost Other
0
Prpty
6100
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
10
Mop Psig
285
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
2012-06-28 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The release was below detectable limits of the cpm leak detection system.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Microbiological Ind
Yes
Int Field Exam Basis Ind
Yes
Int Other Loc Ind
Yes
Corrosion Location Details
Concentric Reducer
Corrosion Inhibitors
No
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
Yes
Exm Handl Ultrasonic Rcnt Year
2019
Exm Other Type
Emat
Exm Other Rcnt Year
2019
Exm Handl Ultrasonic Rcnt Ind
Yes
Exm Other Rcnt Ind
Yes
Preparer Name
N****** G*******
Preparer Title
Hse Compliance Specialist
Preparer Email
N*********@p****.com
Preparer Telephone
7136464376
Prepared Date
2023-01-26 00:00:00
Local Contact Name
N****** G*******
Local Contact Email
N*********@p****.com
Local Contact Telephone
7136464376
Authorizer Name
N***** G*****
Authorizer Telephone
7136464336
Authorizer Title
Hse Mgr Director
Authorizer Email
N******@p****.com
Narrative
Approximately 35 gallons of crude oil were released from tank 1014b tank header piping at patoka station. The date and time of the release (part a q4) is indicative of the earliest possible time the release could have started, as it was the last time the incident location had been visited and confirmed to be no release of crude oil. A supplemental report will be submitted pending further investigation into the cause of the incident. Supplemental report: the cause of the release is attributed to internal corrosion as a result of mic. To prevent future incidents, plains performed a low-flow/no-flow assessment and installed isolations in certain areas to drain fluid when tanks are shut in.
Report Received Date 2022-07-01 00:00:00
Iyear 2022
Report Number 20220136
Supplemental Number 37637
Report Type Supplemental Final
Operator Id 26085 PHMSA Enforcement
Name Plains Marketing, L.p.
Operator Street Address 333 Clay Street, Suite 1900
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2022-06-02 06:00:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 38.79359996 Google Maps OpenStreetMap
Location Longitude -89.07414376 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 0.8
Recovered Bbls 0.8
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2022-06-02 07:45:00
System Part Involved Onshore Terminal/tank Farm Equipment And Piping
On Off Shore Onshore
Status When Identified Idle
Communication State Fed Ind No
On Site Datetime 2022-06-02 07:45:00
Confirmed Discovery Datetime 2022-06-02 07:45:00
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Notify Qualified Indiv Ind Yes
Qualified Indiv Notif Datetime 2022-06-02 07:45:00
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name Patoka Terminal
Segment Name Tank 1014b Tank Header
Onshore State Abbreviation Il
Onshore Postal Code 62892
Onshore City Name Vernon
Onshore County Name Marion
Designated Location Milepost
Designated Name 0+00
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Pipe
Pipe Type Pipe Body
Puddle Weld Ind No
Pipe Diameter 36
Pipe Wall Thickness 0.5
Pipe Smys 24000
Pipe Specification Unknown
Pipe Seam Type Other
Pipe Seam Details Concentric Reducer
Pipe Manufacturer Unknown
Pipe Coating Type Epoxy Other Than Fbe
Coating Applied Ind Yes
Installation Year 2012
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 100
Est Cost Prop Damage 4500
Est Cost Emergency 1500
Est Cost Environmental 0
Est Cost Other 0
Prpty 6100
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 10
Mop Psig 285
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 2012-06-28 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The release was below detectable limits of the cpm leak detection system.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details Internal Corrosion
Internal External Internal Corrosion
Int Visual Exam Results Localized Pitting
Int Microbiological Ind Yes
Int Field Exam Basis Ind Yes
Int Other Loc Ind Yes
Corrosion Location Details Concentric Reducer
Corrosion Inhibitors No
Corrosion Lining No
Cleaning Dewatering Not Applicable - Not Mainline Pipe
Corrosion Coupons Not Applicable - Not Mainline Pipe
Collected Data Ind No
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind Yes
Exm Handl Ultrasonic Rcnt Year 2019
Exm Other Type Emat
Exm Other Rcnt Year 2019
Exm Handl Ultrasonic Rcnt Ind Yes
Exm Other Rcnt Ind Yes
Preparer Name N****** G*******
Preparer Title Hse Compliance Specialist
Preparer Email N*********@p****.com
Preparer Telephone 7136464376
Prepared Date 2023-01-26 00:00:00
Local Contact Name N****** G*******
Local Contact Email N*********@p****.com
Local Contact Telephone 7136464376
Authorizer Name N***** G*****
Authorizer Telephone 7136464336
Authorizer Title Hse Mgr Director
Authorizer Email N******@p****.com
Narrative Approximately 35 gallons of crude oil were released from tank 1014b tank header piping at patoka station. The date and time of the release (part a q4) is indicative of the earliest possible time the release could have started, as it was the last time the incident location had been visited and confirmed to be no release of crude oil. A supplemental report will be submitted pending further investigation into the cause of the incident. Supplemental report: the cause of the release is attributed to internal corrosion as a result of mic. To prevent future incidents, plains performed a low-flow/no-flow assessment and installed isolations in certain areas to drain fluid when tanks are shut in.