GTG incident on 2022-10-20 — TX

Operator
Southern Natural Gas Co
Cause
Equipment Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$30,000
Incident datetime
2022-10-20 08:28
Report number
Location
TX
Narrative
On october 20th, 2022 at 8:28am, a southern natural gas (sng) technician was manually operating a valve contactor on the discharge side of unit 4 at the gallion compressor station. While the technician was operating the valve contactor, a neighboring check valve caught fire. Immediately the technician initiated the station emergency shutdown to isolate the station. The station was isolated at 8:55am. The technician on site sustained burns requiring treatment in a medical facility but not requiring overnight in-patient hospitalization. The event was determined to be non-reportable, and the internal incident investigation commenced. On october 26th, 2022, after investigating the incident further, data indicated that additional gas was vented due to a faulty check valve located in the valve pneumatic system which did not seal properly leading to additional gas volume released. Therefore, the incident was deemed reportable and reported to the nrc. In order to prevent reoccurrence sng operations will be replacing all gallion station pneumatic system check valves.
Detailed record list
Report Received Date
2022-11-18 00:00:00
Iyear
2022
Report Number
20220122
Supplemental Number
37367
Report Type
Original Final
Operator Id
Name
Southern Natural Gas Co
Operator Street Address
1001 Louisiana St, Ste 1000 Suite 1000
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-10-26 09:50:00
Time Zone
Central
Daylight Savings Ind
No
Location Latitude
Location Longitude
Nrc Rpt Num
Nrc Rpt Datetime
2022-10-26 10:44:00
Additional Nrc Report Numbers
1351034
Commodity Released Type
Natural Gas
Unintentional Release
38468
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-10-20 08:33:00
Restart Datetime
2022-10-25 09:00:00
Communication State Fed Ind
No
Ignite Ind
Yes
Ignite Datetime
2022-10-20 08:28:00
How Extinguished
Allowed To Burn Out
Gas Consumed By Fire In Mcf
500
Explode Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2022-10-20 08:28:00
On Site Datetime
2022-10-20 08:28:00
On Off Shore
Onshore
Onshore State Abbreviation
Al
Onshore Postal Code
36742
Onshore City Name
Gallion
Onshore County Name
Hale County
Designated Location
Milepost
Designated Name
138.858
Pipe Fac Name
Gallion Compressor Station
Segment Name
South Mains
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Compressor Station Equipment And Piping
Item Involved
Esd System, But Excluding Product Drain Lines And Tubing
Installation Year
1989
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Other
Leak Type Other
Check Valve Seal Failure
Class Location Type
Class 2 Location
Could Be Hca
No
Pir Radius
344
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
Yes
Mca Buildng Human Occupy Ind
Yes
Est Cost Oper Paid
0
Est Cost Unintentional Release
210805
Est Cost Intentional Release
0
Est Cost Prop Damage
30000
Est Cost Emergency
109
Est Cost Other
0
Gas Cost In Mcf
5.48
Prpty
240914
Num Persons Hosp Not Ovnght
1
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
939
Gas Flow In Pipe In Mcf
0
Mop Psig
1200
Mop Cfr Section
192.619(A)(1)
Maop Established Date
2003-09-08 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Operator deemed incident independent of controller's actions
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
1
Num Employees Failed
0
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Check Valve Ind
Yes
Eq Additional Other Ind
Yes
Eq Additional Other Details
Not Applicable
Preparer Name
V****** R****
Preparer Title
Pipeline Engineer
Preparer Email
V************@k***********.com
Preparer Telephone
2817705911
Authorizer Name
J**** L****
Authorizer Title
Manager Engineer
Authorizer Telephone
7134204675
Authorizer Email
J**********@k***********.com
Narrative
On october 20th, 2022 at 8:28am, a southern natural gas (sng) technician was manually operating a valve contactor on the discharge side of unit 4 at the gallion compressor station. While the technician was operating the valve contactor, a neighboring check valve caught fire. Immediately the technician initiated the station emergency shutdown to isolate the station. The station was isolated at 8:55am. The technician on site sustained burns requiring treatment in a medical facility but not requiring overnight in-patient hospitalization. The event was determined to be non-reportable, and the internal incident investigation commenced. On october 26th, 2022, after investigating the incident further, data indicated that additional gas was vented due to a faulty check valve located in the valve pneumatic system which did not seal properly leading to additional gas volume released. Therefore, the incident was deemed reportable and reported to the nrc. In order to prevent reoccurrence sng operations will be replacing all gallion station pneumatic system check valves.
Report Received Date 2022-11-18 00:00:00
Iyear 2022
Report Number 20220122
Supplemental Number 37367
Report Type Original Final
Operator Id 18516 PHMSA Enforcement
Name Southern Natural Gas Co
Operator Street Address 1001 Louisiana St, Ste 1000 Suite 1000
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2022-10-26 09:50:00
Time Zone Central
Daylight Savings Ind No
Location Latitude 32.499577 Google Maps OpenStreetMap
Location Longitude -87.714553 Google Maps OpenStreetMap
Nrc Rpt Num 1360890 NRC Report How to search
Nrc Rpt Datetime 2022-10-26 10:44:00
Additional Nrc Report Numbers 1351034
Commodity Released Type Natural Gas
Unintentional Release 38468
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind Yes
Shutdown Datetime 2022-10-20 08:33:00
Restart Datetime 2022-10-25 09:00:00
Communication State Fed Ind No
Ignite Ind Yes
Ignite Datetime 2022-10-20 08:28:00
How Extinguished Allowed To Burn Out
Gas Consumed By Fire In Mcf 500
Explode Ind No
Num Pub Evacuated 0
Incident Identified Datetime 2022-10-20 08:28:00
On Site Datetime 2022-10-20 08:28:00
On Off Shore Onshore
Onshore State Abbreviation Al
Onshore Postal Code 36742
Onshore City Name Gallion
Onshore County Name Hale County
Designated Location Milepost
Designated Name 138.858
Pipe Fac Name Gallion Compressor Station
Segment Name South Mains
Federal No
Location Type Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Compressor Station Equipment And Piping
Item Involved Esd System, But Excluding Product Drain Lines And Tubing
Installation Year 1989
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Other
Leak Type Other Check Valve Seal Failure
Class Location Type Class 2 Location
Could Be Hca No
Pir Radius 344
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind Yes
Mca Buildng Human Occupy Ind Yes
Est Cost Oper Paid 0
Est Cost Unintentional Release 210805
Est Cost Intentional Release 0
Est Cost Prop Damage 30000
Est Cost Emergency 109
Est Cost Other 0
Gas Cost In Mcf 5.48
Prpty 240914
Num Persons Hosp Not Ovnght 1
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 939
Gas Flow In Pipe In Mcf 0
Mop Psig 1200
Mop Cfr Section 192.619(A)(1) View CFR 49 §192
Maop Established Date 2003-09-08 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Operator deemed incident independent of controller's actions
Employee Drug Test Ind Yes
Contractor Drug Test Ind No
Num Employees Tested 1
Num Employees Failed 0
Cause Equipment Failure
Cause Details Malfunction Of Control/relief Equipment
Eq Failure Type Malfunction Of Control/relief Equipment
Check Valve Ind Yes
Eq Additional Other Ind Yes
Eq Additional Other Details Not Applicable
Preparer Name V****** R****
Preparer Title Pipeline Engineer
Preparer Email V************@k***********.com
Preparer Telephone 2817705911
Authorizer Name J**** L****
Authorizer Title Manager Engineer
Authorizer Telephone 7134204675
Authorizer Email J**********@k***********.com
Narrative On october 20th, 2022 at 8:28am, a southern natural gas (sng) technician was manually operating a valve contactor on the discharge side of unit 4 at the gallion compressor station. While the technician was operating the valve contactor, a neighboring check valve caught fire. Immediately the technician initiated the station emergency shutdown to isolate the station. The station was isolated at 8:55am. The technician on site sustained burns requiring treatment in a medical facility but not requiring overnight in-patient hospitalization. The event was determined to be non-reportable, and the internal incident investigation commenced. On october 26th, 2022, after investigating the incident further, data indicated that additional gas was vented due to a faulty check valve located in the valve pneumatic system which did not seal properly leading to additional gas volume released. Therefore, the incident was deemed reportable and reported to the nrc. In order to prevent reoccurrence sng operations will be replacing all gallion station pneumatic system check valves.

All rights reserved. Copyright © by ClearPHMSA