Incident details
Operator, cause, commodity and consequences with raw source fields.
GTG incident on 2022-10-06 — TX
Operator
Hooks Gas Pipeline, Llc
Cause
Equipment Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities
2 injuries
Property damage (nominal)
$27,500
Incident datetime
2022-10-06 14:48
Report number
Location
TX
Narrative
It is centric's opinion that the primary root cause of the incident was equipment failure (hydraulic squeezers). Through investigation it was reported that something malfunctioned in the hydraulic pump, causing the jaws of the squeezers to release and allow gas to enter the hole. Broadhead has requested maintenance records from equipment supplier gajeske, inc. But these records have not yet been provided by gajeske, inc. Centric was initially informed that no clamps were provided with the rental. After follow-up questioning centric received the following from broadheads lawyer "the locking devices were provided but they were not used." leading US to identify this as a contributing factor. Other contributing factors include that the contractors were not wearing appropriate ppe (in contravention to their contract with centric), and hazard recognition was inadequate by the contractor staff on scene.
Detailed record list
Report Received Date
2022-11-07 00:00:00
Iyear
2022
Report Number
20220118
Supplemental Number
37588
Report Type
Supplemental Final
Operator Id
32459
Name
Hooks Gas Pipeline, Llc
Operator Street Address
9950 Woodloch Forest Dr
Operator City Name
The Woodlands
Operator State Abbreviation
TX
Operator Postal Code
77380
Local Datetime
2022-10-06 14:48:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
29.674861
Location Longitude
-98.022913
Nrc Rpt Num
1349227
Nrc Rpt Datetime
2022-10-06 15:54:00
Additional Nrc Report Numbers
1349376
Commodity Released Type
Natural Gas
Unintentional Release
210
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
2
Num Er Injuries
0
Num Worker Injuries
0
Num Gp Injuries
0
Injure
2
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-10-06 15:35:00
Restart Datetime
2022-10-18 07:00:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-10-06 14:48:00
Ignite Ind
Yes
Ignite Datetime
2022-10-06 14:48:00
How Extinguished
Allowed To Burn Out
Gas Consumed By Fire In Mcf
210
Explode Ind
No
Upstream Action Taken
Valve Closure
Upstream Valve Close Datetime
2022-10-06 15:35:00
Downstream Action Taken
Operational Control
Downstream Oprtnl Cntrl Detail
The Eol Of This System Has No Customers Allowed The Downstream Portion To Burn Off.
Num Pub Evacuated
0
Incident Identified Datetime
2022-10-06 14:48:00
On Site Datetime
2022-10-06 15:35:00
On Off Shore
Onshore
Onshore State Abbreviation
Tx
Onshore Postal Code
78130
Onshore City Name
New Braunfels
Onshore County Name
Guadalupe County
Designated Location
Not Applicable
Pipe Fac Name
Hooks Gas Pipeline, Llc
Segment Name
Navarro Ranch
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Exposed Due To Excavation
Other Underground Facilities
Yes
Crossing
No
Pipe Facility Type
Intrastate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
8
Puddle Weld Ind
No
Plastic Type
Polyethylene (Pe)
Plastic Sdr
11
Material Pe Pipe Code
3408
Installation Year
2021
Manufactured Year
Unknown
Material Involved
Plastic
Release Type
Other
Release Type Details
Due To The Contractors Squeezers Failing, Gas Was Released Into The Hole The Contractor Was Working In.
Class Location Type
Class 3 Location
Could Be Hca
No
Pir Radius
62
Heat Damage Ind
No
Non Heat Damage Ind
No
Hca Fatalities Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
3150
Est Cost Intentional Release
0
Est Cost Prop Damage
27500
Est Cost Emergency
0
Est Cost Other
0
Gas Cost In Mcf
15
Prpty
30650
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
48
Gas Flow In Pipe In Mcf
0
Mop Psig
100
Mop Cfr Section
192.619(A)(2)
Maop Established Date
2021-10-20 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Upstream Valve Type Ind
Manual
Length Segment Isolated
21000
Internal Inspection Ind
No
Other Inspection Ind
Yes
Internal Inspection Details
8" Hdpe Poly
Operation Complications Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Other Equipment Failure
Eq Failure Type
Other Equipment Failure
Eq Failure Details
The Hydraulic Pump Used To Close The Jaws Of The Squeezer Failed. This Failure Caused The Jaws To Open On The Squeezers The Contractor Rented.
Eq Additional Other Ind
Yes
Eq Additional Other Details
Failure To Utilize Saddle Clamp
Io Follow Procedure Ind
Yes
Preparer Name
K*** K****
Preparer Title
Regulatory Inspector
Preparer Email
K*********@c*********.com
Preparer Telephone
8323492538
Preparer Fax
2812529252
Authorizer Name
A** D****
Authorizer Title
Director Of Regulatory Compliance
Authorizer Telephone
2812526700
Authorizer Email
A********@c*********.com
Narrative
It is centric's opinion that the primary root cause of the incident was equipment failure (hydraulic squeezers). Through investigation it was reported that something malfunctioned in the hydraulic pump, causing the jaws of the squeezers to release and allow gas to enter the hole. Broadhead has requested maintenance records from equipment supplier gajeske, inc. But these records have not yet been provided by gajeske, inc. Centric was initially informed that no clamps were provided with the rental. After follow-up questioning centric received the following from broadheads lawyer "the locking devices were provided but they were not used." leading US to identify this as a contributing factor. Other contributing factors include that the contractors were not wearing appropriate ppe (in contravention to their contract with centric), and hazard recognition was inadequate by the contractor staff on scene.
| Report Received Date | 2022-11-07 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220118 |
| Supplemental Number | 37588 |
| Report Type | Supplemental Final |
| Operator Id | 32459 PHMSA Enforcement |
| Name | Hooks Gas Pipeline, Llc |
| Operator Street Address | 9950 Woodloch Forest Dr |
| Operator City Name | The Woodlands |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77380 |
| Local Datetime | 2022-10-06 14:48:00 |
| Time Zone | Central |
| Daylight Savings Ind | Yes |
| Location Latitude | 29.674861 Google Maps OpenStreetMap |
| Location Longitude | -98.022913 Google Maps OpenStreetMap |
| Nrc Rpt Num | 1349227 NRC Report How to search |
| Nrc Rpt Datetime | 2022-10-06 15:54:00 |
| Additional Nrc Report Numbers | 1349376 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 210 |
| Intentional Release | 0 |
| Accompanying Liquid | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | Yes |
| Num Emp Injuries | 0 |
| Num Contr Injuries | 2 |
| Num Er Injuries | 0 |
| Num Worker Injuries | 0 |
| Num Gp Injuries | 0 |
| Injure | 2 |
| Status When Identified | Normal Operation, Includes Pauses During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-10-06 15:35:00 |
| Restart Datetime | 2022-10-18 07:00:00 |
| Communication State Fed Ind | Yes |
| Party Initiated Communication | Operator |
| Initial Responder Com Datetime | 2022-10-06 14:48:00 |
| Ignite Ind | Yes |
| Ignite Datetime | 2022-10-06 14:48:00 |
| How Extinguished | Allowed To Burn Out |
| Gas Consumed By Fire In Mcf | 210 |
| Explode Ind | No |
| Upstream Action Taken | Valve Closure |
| Upstream Valve Close Datetime | 2022-10-06 15:35:00 |
| Downstream Action Taken | Operational Control |
| Downstream Oprtnl Cntrl Detail | The Eol Of This System Has No Customers Allowed The Downstream Portion To Burn Off. |
| Num Pub Evacuated | 0 |
| Incident Identified Datetime | 2022-10-06 14:48:00 |
| On Site Datetime | 2022-10-06 15:35:00 |
| On Off Shore | Onshore |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 78130 |
| Onshore City Name | New Braunfels |
| Onshore County Name | Guadalupe County |
| Designated Location | Not Applicable |
| Pipe Fac Name | Hooks Gas Pipeline, Llc |
| Segment Name | Navarro Ranch |
| Federal | No |
| Location Type | Pipeline Right-Of-Way |
| Incident Area Type | Underground |
| Incident Area Subtype | Exposed Due To Excavation |
| Other Underground Facilities | Yes |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| Item Involved | Pipe |
| Pipe Type | Pipe Body |
| Pipe Diameter | 8 |
| Puddle Weld Ind | No |
| Plastic Type | Polyethylene (Pe) |
| Plastic Sdr | 11 |
| Material Pe Pipe Code | 3408 |
| Installation Year | 2021 |
| Manufactured Year | Unknown |
| Material Involved | Plastic |
| Release Type | Other |
| Release Type Details | Due To The Contractors Squeezers Failing, Gas Was Released Into The Hole The Contractor Was Working In. |
| Class Location Type | Class 3 Location |
| Could Be Hca | No |
| Pir Radius | 62 |
| Heat Damage Ind | No |
| Non Heat Damage Ind | No |
| Hca Fatalities Ind | No |
| Did Occur In Mca Ind | No |
| Est Cost Oper Paid | 0 |
| Est Cost Unintentional Release | 3150 |
| Est Cost Intentional Release | 0 |
| Est Cost Prop Damage | 27500 |
| Est Cost Emergency | 0 |
| Est Cost Other | 0 |
| Gas Cost In Mcf | 15 |
| Prpty | 30650 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Wildlife Impact Ind | No |
| Accident Psig | 48 |
| Gas Flow In Pipe In Mcf | 0 |
| Mop Psig | 100 |
| Mop Cfr Section | 192.619(A)(2) View CFR 49 §192 |
| Maop Established Date | 2021-10-20 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Pressure Restriction Ind | No |
| Gas Required Odorized Ind | No |
| Upstream Valve Type Ind | Manual |
| Length Segment Isolated | 21000 |
| Internal Inspection Ind | No |
| Other Inspection Ind | Yes |
| Internal Inspection Details | 8" Hdpe Poly |
| Operation Complications Ind | No |
| Pipeline Function | Transmission System |
| Scada In Place Ind | No |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Contractor Working For The Operator |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Other Equipment Failure |
| Eq Failure Type | Other Equipment Failure |
| Eq Failure Details | The Hydraulic Pump Used To Close The Jaws Of The Squeezer Failed. This Failure Caused The Jaws To Open On The Squeezers The Contractor Rented. |
| Eq Additional Other Ind | Yes |
| Eq Additional Other Details | Failure To Utilize Saddle Clamp |
| Io Follow Procedure Ind | Yes |
| Preparer Name | K*** K**** |
| Preparer Title | Regulatory Inspector |
| Preparer Email | K*********@c*********.com |
| Preparer Telephone | 8323492538 |
| Preparer Fax | 2812529252 |
| Authorizer Name | A** D**** |
| Authorizer Title | Director Of Regulatory Compliance |
| Authorizer Telephone | 2812526700 |
| Authorizer Email | A********@c*********.com |
| Narrative | It is centric's opinion that the primary root cause of the incident was equipment failure (hydraulic squeezers). Through investigation it was reported that something malfunctioned in the hydraulic pump, causing the jaws of the squeezers to release and allow gas to enter the hole. Broadhead has requested maintenance records from equipment supplier gajeske, inc. But these records have not yet been provided by gajeske, inc. Centric was initially informed that no clamps were provided with the rental. After follow-up questioning centric received the following from broadheads lawyer "the locking devices were provided but they were not used." leading US to identify this as a contributing factor. Other contributing factors include that the contractors were not wearing appropriate ppe (in contravention to their contract with centric), and hazard recognition was inadequate by the contractor staff on scene. |