GTG incident on 2022-10-04 — NC
Operator
Piedmont Natural Gas Co Inc
Cause
Corrosion Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$400,000
Incident datetime
2022-10-04 17:19
Report number
Location
NC
Narrative
While performing nearby survey work, contractor notified the operation center of the smell of natural gas on line 1.The leak was not directly observed but rather discovered by dead vegetation on the pipeline right of way. The segment was isolated and blown down prior to excavation to allow for safe digging, so an exact leak point was not directly observed. Corrosion was observed on the leak clamp following excavation. Pipe was cut out and replaced with a new section of pipe.
Detailed record list
Report Received Date
2022-11-01 00:00:00
Iyear
2022
Report Number
20220114
Supplemental Number
38738
Report Type
Supplemental Final
Operator Id
15518
Name
Piedmont Natural Gas Co Inc
Operator Street Address
525 South Tryon Street
Operator City Name
Charlotte
Operator State Abbreviation
NC
Operator Postal Code
28202
Local Datetime
2022-10-04 17:19:00
Time Zone
Eastern
Daylight Savings Ind
No
Location Latitude
34.945133
Location Longitude
-79.85217
Nrc Rpt Num
1349128
Nrc Rpt Datetime
2022-10-05 17:27:00
Additional Nrc Report Numbers
1349268
Commodity Released Type
Natural Gas
Unintentional Release
0.01
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-10-07 17:37:00
Restart Datetime
2022-10-09 20:36:00
Communication State Fed Ind
No
Ignite Ind
No
Upstream Action Taken
Operational Control
Upstream Oprtnl Cntrl Detail
Leak Identified By Customer Field Operations. To Isolate Leaking Section.
Downstream Action Taken
Operational Control
Downstream Oprtnl Cntrl Detail
Leak Identified By Customer Field Operations. To Isolate Leaking Section.
Num Pub Evacuated
0
Incident Identified Datetime
2022-10-04 17:19:00
On Site Datetime
2022-10-04 18:15:00
On Off Shore
Onshore
Onshore State Abbreviation
Nc
Onshore Postal Code
28379
Onshore City Name
Rockingham
Onshore County Name
Richmond
Designated Location
Not Applicable
Pipe Fac Name
Line 1
Segment Name
Line 1 Section 3
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
56
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Intrastate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Repair Sleeve Or Clamp
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Class Location Type
Class 1 Location
Could Be Hca
No
Not Flammable Ind
Not Flammable
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
0
Est Cost Intentional Release
0
Est Cost Prop Damage
400000
Est Cost Emergency
40000
Est Cost Other
0
Gas Cost In Mcf
8.49
Prpty
440000
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
518
Gas Flow In Pipe In Mcf
45000
Mop Psig
630
Mop Cfr Section
192.619(A)(3)
Maop Established Date
2016-01-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
Yes
Gas Odorized Ind
Yes
Length Segment Isolated
31680
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
There were no gas control indications of the minor leak. Leak was discovered via reports of dead vegetation on the pipeline right of way.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
Localized Pitting
Galvanic Corrosion Ind
Yes
Field Exam Basis Ind
Yes
Underground Location
Yes
Under Cathodic Protection Ind
Yes
Cathodic Pro Start Year
1970
Shielding Evident
Yes
Cathodic Survey Type
Yes
Cp Annual Survey Ind
Yes
Close Interval Survey Ind
Yes
Cp Annual Survey Year
2022
Close Interval Survey Year
2022
Prior Damage
N/a Bare/ineffectively Coated Pipe
Preparer Name
C********** R******
Preparer Title
Gas Regulatory Compliance Analyst
Preparer Email
C******************@d**********.com
Preparer Telephone
704-731-4680
Authorizer Name
F***** B****
Authorizer Title
Manager- Pipeline Safety
Authorizer Telephone
704-731-4618
Authorizer Email
F***********@d**********.com
Narrative
While performing nearby survey work, contractor notified the operation center of the smell of natural gas on line 1.The leak was not directly observed but rather discovered by dead vegetation on the pipeline right of way. The segment was isolated and blown down prior to excavation to allow for safe digging, so an exact leak point was not directly observed. Corrosion was observed on the leak clamp following excavation. Pipe was cut out and replaced with a new section of pipe.
| Report Received Date | 2022-11-01 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220114 |
| Supplemental Number | 38738 |
| Report Type | Supplemental Final |
| Operator Id | 15518 PHMSA Enforcement |
| Name | Piedmont Natural Gas Co Inc |
| Operator Street Address | 525 South Tryon Street |
| Operator City Name | Charlotte |
| Operator State Abbreviation | NC |
| Operator Postal Code | 28202 |
| Local Datetime | 2022-10-04 17:19:00 |
| Time Zone | Eastern |
| Daylight Savings Ind | No |
| Location Latitude | 34.945133 Google Maps OpenStreetMap |
| Location Longitude | -79.85217 Google Maps OpenStreetMap |
| Nrc Rpt Num | 1349128 NRC Report How to search |
| Nrc Rpt Datetime | 2022-10-05 17:27:00 |
| Additional Nrc Report Numbers | 1349268 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 0.01 |
| Intentional Release | 0 |
| Accompanying Liquid | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Status When Identified | Normal Operation, Includes Pauses During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-10-07 17:37:00 |
| Restart Datetime | 2022-10-09 20:36:00 |
| Communication State Fed Ind | No |
| Ignite Ind | No |
| Upstream Action Taken | Operational Control |
| Upstream Oprtnl Cntrl Detail | Leak Identified By Customer Field Operations. To Isolate Leaking Section. |
| Downstream Action Taken | Operational Control |
| Downstream Oprtnl Cntrl Detail | Leak Identified By Customer Field Operations. To Isolate Leaking Section. |
| Num Pub Evacuated | 0 |
| Incident Identified Datetime | 2022-10-04 17:19:00 |
| On Site Datetime | 2022-10-04 18:15:00 |
| On Off Shore | Onshore |
| Onshore State Abbreviation | Nc |
| Onshore Postal Code | 28379 |
| Onshore City Name | Rockingham |
| Onshore County Name | Richmond |
| Designated Location | Not Applicable |
| Pipe Fac Name | Line 1 |
| Segment Name | Line 1 Section 3 |
| Federal | No |
| Location Type | Pipeline Right-Of-Way |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Soil |
| Depth Of Cover | 56 |
| Other Underground Facilities | No |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| Item Involved | Repair Sleeve Or Clamp |
| Installation Year | Unknown |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Pinhole |
| Class Location Type | Class 1 Location |
| Could Be Hca | No |
| Not Flammable Ind | Not Flammable |
| Heat Damage Ind | No |
| Non Heat Damage Ind | No |
| Did Occur In Mca Ind | No |
| Est Cost Oper Paid | 0 |
| Est Cost Unintentional Release | 0 |
| Est Cost Intentional Release | 0 |
| Est Cost Prop Damage | 400000 |
| Est Cost Emergency | 40000 |
| Est Cost Other | 0 |
| Gas Cost In Mcf | 8.49 |
| Prpty | 440000 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Wildlife Impact Ind | No |
| Accident Psig | 518 |
| Gas Flow In Pipe In Mcf | 45000 |
| Mop Psig | 630 |
| Mop Cfr Section | 192.619(A)(3) View CFR 49 §192 |
| Maop Established Date | 2016-01-01 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Pressure Restriction Ind | No |
| Gas Required Odorized Ind | Yes |
| Gas Odorized Ind | Yes |
| Length Segment Isolated | 31680 |
| Internal Inspection Ind | Yes |
| Operation Complications Ind | No |
| Pipeline Function | Transmission System |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Contractor Working For The Operator |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | There were no gas control indications of the minor leak. Leak was discovered via reports of dead vegetation on the pipeline right of way. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | External Corrosion |
| Internal External | External Corrosion |
| Visual Exam Results | Localized Pitting |
| Galvanic Corrosion Ind | Yes |
| Field Exam Basis Ind | Yes |
| Underground Location | Yes |
| Under Cathodic Protection Ind | Yes |
| Cathodic Pro Start Year | 1970 |
| Shielding Evident | Yes |
| Cathodic Survey Type | Yes |
| Cp Annual Survey Ind | Yes |
| Close Interval Survey Ind | Yes |
| Cp Annual Survey Year | 2022 |
| Close Interval Survey Year | 2022 |
| Prior Damage | N/a Bare/ineffectively Coated Pipe |
| Preparer Name | C********** R****** |
| Preparer Title | Gas Regulatory Compliance Analyst |
| Preparer Email | C******************@d**********.com |
| Preparer Telephone | 704-731-4680 |
| Authorizer Name | F***** B**** |
| Authorizer Title | Manager- Pipeline Safety |
| Authorizer Telephone | 704-731-4618 |
| Authorizer Email | F***********@d**********.com |
| Narrative | While performing nearby survey work, contractor notified the operation center of the smell of natural gas on line 1.The leak was not directly observed but rather discovered by dead vegetation on the pipeline right of way. The segment was isolated and blown down prior to excavation to allow for safe digging, so an exact leak point was not directly observed. Corrosion was observed on the leak clamp following excavation. Pipe was cut out and replaced with a new section of pipe. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA