Incident details
Operator, cause, commodity and consequences with raw source fields.
GTG incident on 2022-09-29 — TX
Operator
Anr Pipeline Co
Cause
Incorrect Operation
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities
1 injury
Property damage (nominal)
$1,300,000
Incident datetime
2022-09-29 15:40
Report number
Location
TX
Narrative
On 29 september 2022, tc energy technicians were performing a corrective work order to replace the hydraulic fluid in the 501-45a-34 valve. While performing the work, an incident occurred resulting in injuries and a release of gas. The incident was reported to the national response center, #1348627. The anr 2-501 pipeline mp582.6 to mp585.1 - 2-501 loop south end to mainline valve 46 (isolated segment), has been blown down and isolated. In addition, tc energy has suspended qualifications on covered tasks associated with the work being performed associated with the incident and conducted drug testing. The pipeline segment remained out of service until repair of the pipeline was completed. Repair to the pipeline included the replacement of the valve and valve operator. The pipeline was restarted and returned to full service on january 13, 2023 at 11:39 cst. The primary cause of the failure has been determined to be the result of the technician failing to confirm manufacturer's repair procedure and opening the valve during corrective maintenance to replace the hydraulic hand pump. Following the repair, when the valve was actuated using the hand pump, hydraulic oil began to move to the open side of the valve stem and the valve gate disengaged and moved in an uncontrolled manner. The result of this action caused a failure in the valve actuator connection and a release of pipeline fluids and hydraulic oil to the surrounding area.
Detailed record list
Report Received Date
2022-10-28 00:00:00
Iyear
2022
Report Number
20220113
Supplemental Number
37725
Report Type
Supplemental Final
Operator Id
Name
Anr Pipeline Co
Operator Street Address
700 Louisiana Street Suite 700
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-09-29 15:40:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
37.59644
Location Longitude
-87.43407
Nrc Rpt Num
1348627
Nrc Rpt Datetime
2022-09-29 16:30:00
Additional Nrc Report Numbers
1348783
Commodity Released Type
Natural Gas
Unintentional Release
189
Intentional Release
3677
Accompanying Liquid
0.1
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
1
Num Contr Injuries
0
Num Er Injuries
0
Num Worker Injuries
0
Num Gp Injuries
0
Injure
1
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-09-29 18:39:00
Restart Datetime
2023-01-13 11:39:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-09-29 16:30:00
Ignite Ind
No
Upstream Action Taken
Valve Closure
Upstream Valve Close Datetime
2022-09-29 16:46:00
Downstream Action Taken
Valve Closure
Downstream Vlv Close Datetime
2022-09-29 16:39:00
Num Pub Evacuated
1
Incident Identified Datetime
2022-09-29 15:40:00
On Site Datetime
2022-09-29 15:40:00
On Off Shore
Onshore
Onshore State Abbreviation
Ky
Onshore Postal Code
42327
Onshore City Name
Not Within A Municipality
Onshore County Name
Mclean
Designated Location
Milepost
Designated Name
582.6
Pipe Fac Name
Mainline Valve 45a
Segment Name
8245501-Anr Mainline Loop 2 2-501 Mlv 45
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
20
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Valve
Valve Type
Auxiliary Or Other Valve
Installation Year
1986
Manufactured Year
1986
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Valve Failure
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
830
Heat Damage Ind
No
Non Heat Damage Ind
No
Hca Fatalities Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
1300
Est Cost Intentional Release
25298
Est Cost Prop Damage
1300000
Est Cost Emergency
10000
Est Cost Other
100000
Est Cost Other Details
Laboratory And Investigation Costs
Gas Cost In Mcf
6.88
Prpty
1436598
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
1
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
580
Gas Flow In Pipe In Mcf
385
Mop Psig
858
Mop Cfr Section
192.619(A)(1)
Maop Established Date
1972-10-12 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Length Segment Isolated
12277
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The incident occurred during maintenance operations while technicians were at the facility.
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
2
Num Employees Failed
0
Cause
Incorrect Operation
Cause Details
Other Incorrect Operation
Operation Type
Other Incorrect Operation
Operation Details
Technician Believed That Valve Needed To Be Closed During The Corrective Maintenance Of Replacing The Dhv Hand Pump. Technician Did Not Become Aware Of The Shafer Dhv Hand Pump Installation Procedure That Included A Note To Have The Valve Open At The Start Of Maintenance.
Related Inadequate Proc Ind
Yes
Related Failure Follow Ind
Yes
Category Type
Other Maintenance
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
R**** R S*****
Preparer Title
Manager Us Regulatory Compliance West
Preparer Email
R***********@t*******.com
Preparer Telephone
16154655123
Local Contact Name
R**** R S*****
Local Contact Email
R***********@t*******.com
Local Contact Telephone
16154655123
Authorizer Name
P*** S******
Authorizer Title
Senior Manager Usgo Regulatory Compliance
Authorizer Telephone
304-357-2245
Authorizer Email
P***********@t*******.com
Narrative
On 29 september 2022, tc energy technicians were performing a corrective work order to replace the hydraulic fluid in the 501-45a-34 valve. While performing the work, an incident occurred resulting in injuries and a release of gas. The incident was reported to the national response center, #1348627. The anr 2-501 pipeline mp582.6 to mp585.1 - 2-501 loop south end to mainline valve 46 (isolated segment), has been blown down and isolated. In addition, tc energy has suspended qualifications on covered tasks associated with the work being performed associated with the incident and conducted drug testing. The pipeline segment remained out of service until repair of the pipeline was completed. Repair to the pipeline included the replacement of the valve and valve operator. The pipeline was restarted and returned to full service on january 13, 2023 at 11:39 cst. The primary cause of the failure has been determined to be the result of the technician failing to confirm manufacturer's repair procedure and opening the valve during corrective maintenance to replace the hydraulic hand pump. Following the repair, when the valve was actuated using the hand pump, hydraulic oil began to move to the open side of the valve stem and the valve gate disengaged and moved in an uncontrolled manner. The result of this action caused a failure in the valve actuator connection and a release of pipeline fluids and hydraulic oil to the surrounding area.
| Report Received Date | 2022-10-28 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220113 |
| Supplemental Number | 37725 |
| Report Type | Supplemental Final |
| Operator Id | 405 PHMSA Enforcement |
| Name | Anr Pipeline Co |
| Operator Street Address | 700 Louisiana Street Suite 700 |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2022-09-29 15:40:00 |
| Time Zone | Central |
| Daylight Savings Ind | Yes |
| Location Latitude | 37.59644 Google Maps OpenStreetMap |
| Location Longitude | -87.43407 Google Maps OpenStreetMap |
| Nrc Rpt Num | 1348627 NRC Report How to search |
| Nrc Rpt Datetime | 2022-09-29 16:30:00 |
| Additional Nrc Report Numbers | 1348783 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 189 |
| Intentional Release | 3677 |
| Accompanying Liquid | 0.1 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | Yes |
| Num Emp Injuries | 1 |
| Num Contr Injuries | 0 |
| Num Er Injuries | 0 |
| Num Worker Injuries | 0 |
| Num Gp Injuries | 0 |
| Injure | 1 |
| Status When Identified | Normal Operation, Includes Pauses During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-09-29 18:39:00 |
| Restart Datetime | 2023-01-13 11:39:00 |
| Communication State Fed Ind | Yes |
| Party Initiated Communication | Operator |
| Initial Responder Com Datetime | 2022-09-29 16:30:00 |
| Ignite Ind | No |
| Upstream Action Taken | Valve Closure |
| Upstream Valve Close Datetime | 2022-09-29 16:46:00 |
| Downstream Action Taken | Valve Closure |
| Downstream Vlv Close Datetime | 2022-09-29 16:39:00 |
| Num Pub Evacuated | 1 |
| Incident Identified Datetime | 2022-09-29 15:40:00 |
| On Site Datetime | 2022-09-29 15:40:00 |
| On Off Shore | Onshore |
| Onshore State Abbreviation | Ky |
| Onshore Postal Code | 42327 |
| Onshore City Name | Not Within A Municipality |
| Onshore County Name | Mclean |
| Designated Location | Milepost |
| Designated Name | 582.6 |
| Pipe Fac Name | Mainline Valve 45a |
| Segment Name | 8245501-Anr Mainline Loop 2 2-501 Mlv 45 |
| Federal | No |
| Location Type | Operator-Controlled Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Soil |
| Depth Of Cover | 20 |
| Other Underground Facilities | No |
| Crossing | No |
| Pipe Facility Type | Interstate |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| Item Involved | Valve |
| Valve Type | Auxiliary Or Other Valve |
| Installation Year | 1986 |
| Manufactured Year | 1986 |
| Material Involved | Carbon Steel |
| Release Type | Other |
| Release Type Details | Valve Failure |
| Class Location Type | Class 1 Location |
| Could Be Hca | No |
| Pir Radius | 830 |
| Heat Damage Ind | No |
| Non Heat Damage Ind | No |
| Hca Fatalities Ind | No |
| Did Occur In Mca Ind | No |
| Est Cost Oper Paid | 0 |
| Est Cost Unintentional Release | 1300 |
| Est Cost Intentional Release | 25298 |
| Est Cost Prop Damage | 1300000 |
| Est Cost Emergency | 10000 |
| Est Cost Other | 100000 |
| Est Cost Other Details | Laboratory And Investigation Costs |
| Gas Cost In Mcf | 6.88 |
| Prpty | 1436598 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 1 |
| Num Business Building Affctd | 0 |
| Wildlife Impact Ind | No |
| Accident Psig | 580 |
| Gas Flow In Pipe In Mcf | 385 |
| Mop Psig | 858 |
| Mop Cfr Section | 192.619(A)(1) View CFR 49 §192 |
| Maop Established Date | 1972-10-12 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Pressure Restriction Ind | No |
| Gas Required Odorized Ind | No |
| Upstream Valve Type Ind | Manual |
| Downstream Valve Type Ind | Manual |
| Length Segment Isolated | 12277 |
| Internal Inspection Ind | Yes |
| Operation Complications Ind | No |
| Pipeline Function | Transmission System |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | The incident occurred during maintenance operations while technicians were at the facility. |
| Employee Drug Test Ind | Yes |
| Contractor Drug Test Ind | No |
| Num Employees Tested | 2 |
| Num Employees Failed | 0 |
| Cause | Incorrect Operation |
| Cause Details | Other Incorrect Operation |
| Operation Type | Other Incorrect Operation |
| Operation Details | Technician Believed That Valve Needed To Be Closed During The Corrective Maintenance Of Replacing The Dhv Hand Pump. Technician Did Not Become Aware Of The Shafer Dhv Hand Pump Installation Procedure That Included A Note To Have The Valve Open At The Start Of Maintenance. |
| Related Inadequate Proc Ind | Yes |
| Related Failure Follow Ind | Yes |
| Category Type | Other Maintenance |
| Operator Qualification Ind | Yes |
| Qualified Individuals | Yes, They Were Qualified For The Task(S) |
| Preparer Name | R**** R S***** |
| Preparer Title | Manager Us Regulatory Compliance West |
| Preparer Email | R***********@t*******.com |
| Preparer Telephone | 16154655123 |
| Local Contact Name | R**** R S***** |
| Local Contact Email | R***********@t*******.com |
| Local Contact Telephone | 16154655123 |
| Authorizer Name | P*** S****** |
| Authorizer Title | Senior Manager Usgo Regulatory Compliance |
| Authorizer Telephone | 304-357-2245 |
| Authorizer Email | P***********@t*******.com |
| Narrative | On 29 september 2022, tc energy technicians were performing a corrective work order to replace the hydraulic fluid in the 501-45a-34 valve. While performing the work, an incident occurred resulting in injuries and a release of gas. The incident was reported to the national response center, #1348627. The anr 2-501 pipeline mp582.6 to mp585.1 - 2-501 loop south end to mainline valve 46 (isolated segment), has been blown down and isolated. In addition, tc energy has suspended qualifications on covered tasks associated with the work being performed associated with the incident and conducted drug testing. The pipeline segment remained out of service until repair of the pipeline was completed. Repair to the pipeline included the replacement of the valve and valve operator. The pipeline was restarted and returned to full service on january 13, 2023 at 11:39 cst. The primary cause of the failure has been determined to be the result of the technician failing to confirm manufacturer's repair procedure and opening the valve during corrective maintenance to replace the hydraulic hand pump. Following the repair, when the valve was actuated using the hand pump, hydraulic oil began to move to the open side of the valve stem and the valve gate disengaged and moved in an uncontrolled manner. The result of this action caused a failure in the valve actuator connection and a release of pipeline fluids and hydraulic oil to the surrounding area. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company