Incident details
Operator, cause, commodity and consequences with raw source fields.
GTG incident on 2022-09-19 — TX
Operator
Enterprise Products Operating Llc
Cause
Corrosion Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$639,000
Incident datetime
2022-09-19 15:50
Report number
Location
TX
Narrative
At about 15:16hrs 19sep2022 enterprise control room was contacted by the nueces county sheriff department concerning a grass fire in the vicinity of an enterprise gas pipeline. The controller immediately dispatched field personnel to investigate. At about 15:50hrs field personnel arrived on site then contacted enterprise control room confirming a pipeline failure and fire. The local fire department were on site already. The fire was allowed to burn-out. At about 16:00hrs field personnel began closing manual valves; the last one (valve #3) was closed at 16:10hrs, totally isolating the rupture site. At about 17:30hrs the fire had extinguished itself, and we were able to safely inspect the site. The fire department did not evacuate landowners or close roads. The failure segment was cut-out; west side on 30sept2022, east side on 07oct2022. Both cut-outs were sent to the lab on 10oct2022. The abandonment of the pipeline was completed on 27feb2023. Based on a metallurgical analysis, external, general corrosion was the cause of the failure. The rrc was contacted on 19sep2022 at 17:06hrs. Trrc incident number 2706
Detailed record list
Report Received Date
2022-10-18 00:00:00
Iyear
2022
Report Number
20220110
Supplemental Number
37812
Report Type
Supplemental Final
Operator Id
31618
Name
Enterprise Products Operating Llc
Operator Street Address
1100 Louisiana Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-09-19 15:16:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
27.591771
Location Longitude
-97.610593
Nrc Rpt Num
1347704
Nrc Rpt Datetime
2022-09-19 17:05:00
Additional Nrc Report Numbers
1347901
Commodity Released Type
Natural Gas
Unintentional Release
390
Intentional Release
0
Accompanying Liquid
11.9
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-09-19 16:10:00
Restart Datetime
2023-02-27 15:00:00
Ignite Ind
Yes
Ignite Datetime
2022-09-19 15:16:00
How Extinguished
Allowed To Burn Out
Gas Consumed By Fire In Mcf
390
Explode Ind
Yes
Upstream Action Taken
Valve Closure
Upstream Valve Close Datetime
2022-09-19 16:00:00
Downstream Action Taken
Valve Closure
Downstream Vlv Close Datetime
2022-09-19 16:10:00
Num Pub Evacuated
2
Incident Identified Datetime
2022-09-19 15:50:00
On Site Datetime
2022-09-19 15:50:00
On Off Shore
Onshore
Onshore State Abbreviation
Tx
Onshore Postal Code
78343
Onshore City Name
Bishop
Onshore County Name
Nueces
Designated Location
Milepost
Designated Name
81+97
Pipe Fac Name
Luby Lateral
Segment Name
9d
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Aboveground
Incident Area Subtype
In Or Spanning An Open Ditch
Crossing
Yes
Water Crossing Ind
Yes
Water Type
Uncased
Water Name
Cotulla Ditch
Water Depth
Unknown
Water Subtype
Shoreline/bank/marsh Crossing
Crossing 100 Feet
No
Pipe Facility Type
Intrastate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
10
Puddle Weld Ind
No
Pipe Wall Thickness
0.219
Pipe Smys
46000
Pipe Specification
Api-5l-X-46-46000
Pipe Seam Type
Longitudinal Erw - Low Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Coal Tar
Coating Applied Ind
Unknown
Installation Year
1967
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Rupture
Rupture Orient
Circumferential
Rupture Length
12
Rupture Width
8
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
298
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
500000
Est Cost Unintentional Release
3175
Est Cost Intentional Release
0
Est Cost Prop Damage
639000
Est Cost Emergency
0
Est Cost Other
0
Gas Cost In Mcf
8.14
Prpty
1142175
Num Persons Hosp Not Ovnght
2
Num Injured Treated By Emt
0
Num Resident Building Affctd
1
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
877
Gas Flow In Pipe In Mcf
149
Mop Psig
1114
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1982-05-19 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Length Segment Isolated
9276
Internal Inspection Ind
No
Other Inspection Ind
Yes
Internal Inspection Details
No Launch And Receiver Facilities
Operation Complications Ind
No
Pipeline Function
Type C Gathering
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
General Corrosion
Atmosphere Corrosion Ind
Yes
Metallurgical Basis Ind
Yes
Underground Location
No
Externally Coated
Yes
Prior Damage
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
Yes
Hydrtst Most Rcnt Year
1982
Hydrtst Most Rcnt Pressure
1225
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
A*** S******
Preparer Title
Sr. Pipeline Compliance Specialist
Preparer Email
A*******@e****.com
Preparer Telephone
713-381-6741
Authorizer Name
N*** T*****
Authorizer Title
Sr. Compliance Manager
Authorizer Telephone
713-381-2493
Authorizer Email
N*******@e****.com
Narrative
At about 15:16hrs 19sep2022 enterprise control room was contacted by the nueces county sheriff department concerning a grass fire in the vicinity of an enterprise gas pipeline. The controller immediately dispatched field personnel to investigate. At about 15:50hrs field personnel arrived on site then contacted enterprise control room confirming a pipeline failure and fire. The local fire department were on site already. The fire was allowed to burn-out. At about 16:00hrs field personnel began closing manual valves; the last one (valve #3) was closed at 16:10hrs, totally isolating the rupture site. At about 17:30hrs the fire had extinguished itself, and we were able to safely inspect the site. The fire department did not evacuate landowners or close roads. The failure segment was cut-out; west side on 30sept2022, east side on 07oct2022. Both cut-outs were sent to the lab on 10oct2022. The abandonment of the pipeline was completed on 27feb2023. Based on a metallurgical analysis, external, general corrosion was the cause of the failure. The rrc was contacted on 19sep2022 at 17:06hrs. Trrc incident number 2706
| Report Received Date | 2022-10-18 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220110 |
| Supplemental Number | 37812 |
| Report Type | Supplemental Final |
| Operator Id | 31618 PHMSA Enforcement |
| Name | Enterprise Products Operating Llc |
| Operator Street Address | 1100 Louisiana Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2022-09-19 15:16:00 |
| Time Zone | Central |
| Daylight Savings Ind | Yes |
| Location Latitude | 27.591771 Google Maps OpenStreetMap |
| Location Longitude | -97.610593 Google Maps OpenStreetMap |
| Nrc Rpt Num | 1347704 NRC Report How to search |
| Nrc Rpt Datetime | 2022-09-19 17:05:00 |
| Additional Nrc Report Numbers | 1347901 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 390 |
| Intentional Release | 0 |
| Accompanying Liquid | 11.9 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Status When Identified | Normal Operation, Includes Pauses During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-09-19 16:10:00 |
| Restart Datetime | 2023-02-27 15:00:00 |
| Ignite Ind | Yes |
| Ignite Datetime | 2022-09-19 15:16:00 |
| How Extinguished | Allowed To Burn Out |
| Gas Consumed By Fire In Mcf | 390 |
| Explode Ind | Yes |
| Upstream Action Taken | Valve Closure |
| Upstream Valve Close Datetime | 2022-09-19 16:00:00 |
| Downstream Action Taken | Valve Closure |
| Downstream Vlv Close Datetime | 2022-09-19 16:10:00 |
| Num Pub Evacuated | 2 |
| Incident Identified Datetime | 2022-09-19 15:50:00 |
| On Site Datetime | 2022-09-19 15:50:00 |
| On Off Shore | Onshore |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 78343 |
| Onshore City Name | Bishop |
| Onshore County Name | Nueces |
| Designated Location | Milepost |
| Designated Name | 81+97 |
| Pipe Fac Name | Luby Lateral |
| Segment Name | 9d |
| Federal | No |
| Location Type | Pipeline Right-Of-Way |
| Incident Area Type | Aboveground |
| Incident Area Subtype | In Or Spanning An Open Ditch |
| Crossing | Yes |
| Water Crossing Ind | Yes |
| Water Type | Uncased |
| Water Name | Cotulla Ditch |
| Water Depth | Unknown |
| Water Subtype | Shoreline/bank/marsh Crossing |
| Crossing 100 Feet | No |
| Pipe Facility Type | Intrastate |
| System Part Involved | Onshore Pipeline, Including Valve Sites |
| Item Involved | Pipe |
| Pipe Type | Pipe Body |
| Pipe Diameter | 10 |
| Puddle Weld Ind | No |
| Pipe Wall Thickness | 0.219 |
| Pipe Smys | 46000 |
| Pipe Specification | Api-5l-X-46-46000 |
| Pipe Seam Type | Longitudinal Erw - Low Frequency |
| Pipe Manufacturer | Unknown |
| Pipe Coating Type | Coal Tar |
| Coating Applied Ind | Unknown |
| Installation Year | 1967 |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Rupture |
| Rupture Orient | Circumferential |
| Rupture Length | 12 |
| Rupture Width | 8 |
| Class Location Type | Class 1 Location |
| Could Be Hca | No |
| Pir Radius | 298 |
| Heat Damage Ind | No |
| Non Heat Damage Ind | No |
| Did Occur In Mca Ind | No |
| Est Cost Oper Paid | 500000 |
| Est Cost Unintentional Release | 3175 |
| Est Cost Intentional Release | 0 |
| Est Cost Prop Damage | 639000 |
| Est Cost Emergency | 0 |
| Est Cost Other | 0 |
| Gas Cost In Mcf | 8.14 |
| Prpty | 1142175 |
| Num Persons Hosp Not Ovnght | 2 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 1 |
| Num Business Building Affctd | 0 |
| Wildlife Impact Ind | No |
| Accident Psig | 877 |
| Gas Flow In Pipe In Mcf | 149 |
| Mop Psig | 1114 |
| Mop Cfr Section | 192.619(A)(2) View CFR 49 §192 |
| Maop Established Date | 1982-05-19 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Pressure Restriction Ind | No |
| Gas Required Odorized Ind | No |
| Upstream Valve Type Ind | Manual |
| Downstream Valve Type Ind | Manual |
| Length Segment Isolated | 9276 |
| Internal Inspection Ind | No |
| Other Inspection Ind | Yes |
| Internal Inspection Details | No Launch And Receiver Facilities |
| Operation Complications Ind | No |
| Pipeline Function | Type C Gathering |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Emergency Responder |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | External Corrosion |
| Internal External | External Corrosion |
| Visual Exam Results | General Corrosion |
| Atmosphere Corrosion Ind | Yes |
| Metallurgical Basis Ind | Yes |
| Underground Location | No |
| Externally Coated | Yes |
| Prior Damage | Yes |
| Collected Data Ind | No |
| Has Hydrtst Conduc Before Ind | Yes |
| Hydrtst Most Rcnt Year | 1982 |
| Hydrtst Most Rcnt Pressure | 1225 |
| Direct Asmnt Conducted | No |
| Non Destructive Exam Ind | No |
| Preparer Name | A*** S****** |
| Preparer Title | Sr. Pipeline Compliance Specialist |
| Preparer Email | A*******@e****.com |
| Preparer Telephone | 713-381-6741 |
| Authorizer Name | N*** T***** |
| Authorizer Title | Sr. Compliance Manager |
| Authorizer Telephone | 713-381-2493 |
| Authorizer Email | N*******@e****.com |
| Narrative | At about 15:16hrs 19sep2022 enterprise control room was contacted by the nueces county sheriff department concerning a grass fire in the vicinity of an enterprise gas pipeline. The controller immediately dispatched field personnel to investigate. At about 15:50hrs field personnel arrived on site then contacted enterprise control room confirming a pipeline failure and fire. The local fire department were on site already. The fire was allowed to burn-out. At about 16:00hrs field personnel began closing manual valves; the last one (valve #3) was closed at 16:10hrs, totally isolating the rupture site. At about 17:30hrs the fire had extinguished itself, and we were able to safely inspect the site. The fire department did not evacuate landowners or close roads. The failure segment was cut-out; west side on 30sept2022, east side on 07oct2022. Both cut-outs were sent to the lab on 10oct2022. The abandonment of the pipeline was completed on 27feb2023. Based on a metallurgical analysis, external, general corrosion was the cause of the failure. The rrc was contacted on 19sep2022 at 17:06hrs. Trrc incident number 2706 |