Incident details
Operator, cause, commodity and consequences with raw source fields.
GTG incident on 2022-08-06 — TX
Operator
Enterprise Products Operating Llc
Cause
Equipment Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$1,153
Incident datetime
2022-08-06 00:50
Report number
Location
TX
Narrative
On 8-6-2022 at 00:01 cst, enterprise received a shutdown alarm from the mack station compressor unit 1. At 00:50, enterprise arrived at the station and saw that unit 1 was on fire. At 00:51, enterprise isolated and blew down the station by pushing the esd button. The glasscock police department and the stanton volunteer fire department arrived at the station on 00:49 and 01:30, respectively. At 02:25, enterprise determined that the event would meet the definition of an incident based on anticipated costs of the unit 1 fire. Units 1 and 2 are leased by enterprise from archrock and the costs to repair or replace the units are not available to enterprise. The nrc and txrrc were notified of the event by enterprise at 02:47 and 02:52, respectively. On 8-6-2022 at 06:45, the fire self-extinguished. Unit 2, which is adjacent to unit 1, was damaged by the fire; however, no station piping was involved in the fire. Mack station was out of service from 8-6-2022 to 8-28-2022. Unit 1 was removed from mack station and a replacement for unit 1 was placed into service on 8-29-2022. Unit 2 was repaired and placed into service on 9-23-2022. An investigation of the incident determined that an abnormal vibration from the second stage discharge receiver caused bolts on the pipe flanges to loosen which caused a loss of containment. Natural gas made contact with an ignition source and caused a fire.
Detailed record list
Report Received Date
2022-09-01 00:00:00
Iyear
2022
Report Number
20220095
Supplemental Number
37537
Report Type
Supplemental Final
Operator Id
31618
Name
Enterprise Products Operating Llc
Operator Street Address
1100 Louisiana Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-08-06 00:01:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
31.945711
Location Longitude
-101.746446
Nrc Rpt Num
1343686
Nrc Rpt Datetime
2022-08-06 02:47:00
Additional Nrc Report Numbers
1343804
Commodity Released Type
Natural Gas
Unintentional Release
233
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-08-06 00:01:00
Restart Datetime
2022-08-30 11:00:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-08-06 00:50:00
Ignite Ind
Yes
Ignite Datetime
2022-08-06 00:01:00
How Extinguished
Allowed To Burn Out
Gas Consumed By Fire In Mcf
233
Explode Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2022-08-06 00:50:00
On Site Datetime
2022-08-06 00:50:00
On Off Shore
Onshore
Onshore State Abbreviation
Tx
Onshore Postal Code
79706
Onshore City Name
Not Within A Municipality
Onshore County Name
Glasscock
Designated Location
Not Applicable
Pipe Fac Name
Mack Station
Segment Name
Mack Station
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
System Part Involved
Onshore Compressor Station Equipment And Piping
Item Involved
Compressor
Installation Year
2021
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Failure Was Due To Abnormal Vibrations Of Compressor.
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
197
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
2181
Est Cost Intentional Release
0
Est Cost Prop Damage
1153
Est Cost Emergency
0
Est Cost Other
0
Gas Cost In Mcf
9.36
Prpty
3334
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
1031
Gas Flow In Pipe In Mcf
18100
Mop Psig
1280
Mop Cfr Section
192.619(A)(1)
Maop Established Date
2021-08-12 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Type C Gathering
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Mack station is not remotely controlled.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Compressor Or Compressor-Related Equipment
Eq Failure Type
Compressor Or Compressor-Related Equipment
Other Compressor Ind
Other
Other Compressor Details
Failure Was Due To Abnormal Vibrations Of Compressor.
Additional Vibration Ind
Yes
Preparer Name
G***** W*******
Preparer Title
Engineer - Senior Pipeline Compliance
Preparer Email
G*********@e****.com
Preparer Telephone
713-381-6211
Local Contact Name
G***** W*******
Local Contact Email
G*********@e****.com
Local Contact Telephone
713-381-6211
Authorizer Name
G***** W*******
Authorizer Title
Engineer - Senior Pipeline Compliance
Authorizer Telephone
713-381-6211
Authorizer Email
G*********@e****.com
Narrative
On 8-6-2022 at 00:01 cst, enterprise received a shutdown alarm from the mack station compressor unit 1. At 00:50, enterprise arrived at the station and saw that unit 1 was on fire. At 00:51, enterprise isolated and blew down the station by pushing the esd button. The glasscock police department and the stanton volunteer fire department arrived at the station on 00:49 and 01:30, respectively. At 02:25, enterprise determined that the event would meet the definition of an incident based on anticipated costs of the unit 1 fire. Units 1 and 2 are leased by enterprise from archrock and the costs to repair or replace the units are not available to enterprise. The nrc and txrrc were notified of the event by enterprise at 02:47 and 02:52, respectively. On 8-6-2022 at 06:45, the fire self-extinguished. Unit 2, which is adjacent to unit 1, was damaged by the fire; however, no station piping was involved in the fire. Mack station was out of service from 8-6-2022 to 8-28-2022. Unit 1 was removed from mack station and a replacement for unit 1 was placed into service on 8-29-2022. Unit 2 was repaired and placed into service on 9-23-2022. An investigation of the incident determined that an abnormal vibration from the second stage discharge receiver caused bolts on the pipe flanges to loosen which caused a loss of containment. Natural gas made contact with an ignition source and caused a fire.
| Report Received Date | 2022-09-01 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220095 |
| Supplemental Number | 37537 |
| Report Type | Supplemental Final |
| Operator Id | 31618 PHMSA Enforcement |
| Name | Enterprise Products Operating Llc |
| Operator Street Address | 1100 Louisiana Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2022-08-06 00:01:00 |
| Time Zone | Central |
| Daylight Savings Ind | Yes |
| Location Latitude | 31.945711 Google Maps OpenStreetMap |
| Location Longitude | -101.746446 Google Maps OpenStreetMap |
| Nrc Rpt Num | 1343686 NRC Report How to search |
| Nrc Rpt Datetime | 2022-08-06 02:47:00 |
| Additional Nrc Report Numbers | 1343804 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 233 |
| Intentional Release | 0 |
| Accompanying Liquid | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Status When Identified | Normal Operation, Includes Pauses During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-08-06 00:01:00 |
| Restart Datetime | 2022-08-30 11:00:00 |
| Communication State Fed Ind | Yes |
| Party Initiated Communication | Operator |
| Initial Responder Com Datetime | 2022-08-06 00:50:00 |
| Ignite Ind | Yes |
| Ignite Datetime | 2022-08-06 00:01:00 |
| How Extinguished | Allowed To Burn Out |
| Gas Consumed By Fire In Mcf | 233 |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Incident Identified Datetime | 2022-08-06 00:50:00 |
| On Site Datetime | 2022-08-06 00:50:00 |
| On Off Shore | Onshore |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 79706 |
| Onshore City Name | Not Within A Municipality |
| Onshore County Name | Glasscock |
| Designated Location | Not Applicable |
| Pipe Fac Name | Mack Station |
| Segment Name | Mack Station |
| Federal | No |
| Location Type | Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| System Part Involved | Onshore Compressor Station Equipment And Piping |
| Item Involved | Compressor |
| Installation Year | 2021 |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Other |
| Release Type Details | Failure Was Due To Abnormal Vibrations Of Compressor. |
| Class Location Type | Class 1 Location |
| Could Be Hca | No |
| Pir Radius | 197 |
| Heat Damage Ind | No |
| Non Heat Damage Ind | No |
| Did Occur In Mca Ind | No |
| Est Cost Oper Paid | 0 |
| Est Cost Unintentional Release | 2181 |
| Est Cost Intentional Release | 0 |
| Est Cost Prop Damage | 1153 |
| Est Cost Emergency | 0 |
| Est Cost Other | 0 |
| Gas Cost In Mcf | 9.36 |
| Prpty | 3334 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Wildlife Impact Ind | No |
| Accident Psig | 1031 |
| Gas Flow In Pipe In Mcf | 18100 |
| Mop Psig | 1280 |
| Mop Cfr Section | 192.619(A)(1) View CFR 49 §192 |
| Maop Established Date | 2021-08-12 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Pressure Restriction Ind | No |
| Gas Required Odorized Ind | No |
| Pipeline Function | Type C Gathering |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Accident Identifier | Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations) |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Mack station is not remotely controlled. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Compressor Or Compressor-Related Equipment |
| Eq Failure Type | Compressor Or Compressor-Related Equipment |
| Other Compressor Ind | Other |
| Other Compressor Details | Failure Was Due To Abnormal Vibrations Of Compressor. |
| Additional Vibration Ind | Yes |
| Preparer Name | G***** W******* |
| Preparer Title | Engineer - Senior Pipeline Compliance |
| Preparer Email | G*********@e****.com |
| Preparer Telephone | 713-381-6211 |
| Local Contact Name | G***** W******* |
| Local Contact Email | G*********@e****.com |
| Local Contact Telephone | 713-381-6211 |
| Authorizer Name | G***** W******* |
| Authorizer Title | Engineer - Senior Pipeline Compliance |
| Authorizer Telephone | 713-381-6211 |
| Authorizer Email | G*********@e****.com |
| Narrative | On 8-6-2022 at 00:01 cst, enterprise received a shutdown alarm from the mack station compressor unit 1. At 00:50, enterprise arrived at the station and saw that unit 1 was on fire. At 00:51, enterprise isolated and blew down the station by pushing the esd button. The glasscock police department and the stanton volunteer fire department arrived at the station on 00:49 and 01:30, respectively. At 02:25, enterprise determined that the event would meet the definition of an incident based on anticipated costs of the unit 1 fire. Units 1 and 2 are leased by enterprise from archrock and the costs to repair or replace the units are not available to enterprise. The nrc and txrrc were notified of the event by enterprise at 02:47 and 02:52, respectively. On 8-6-2022 at 06:45, the fire self-extinguished. Unit 2, which is adjacent to unit 1, was damaged by the fire; however, no station piping was involved in the fire. Mack station was out of service from 8-6-2022 to 8-28-2022. Unit 1 was removed from mack station and a replacement for unit 1 was placed into service on 8-29-2022. Unit 2 was repaired and placed into service on 9-23-2022. An investigation of the incident determined that an abnormal vibration from the second stage discharge receiver caused bolts on the pipe flanges to loosen which caused a loss of containment. Natural gas made contact with an ignition source and caused a fire. |