GTG incident on 2022-08-16 — TX

Operator
Enable Gas Transmission, Llc
Cause
Material Failure Of Pipe Or Weld
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$69,351
Incident datetime
2022-08-16 16:15
Report number
Location
TX
Narrative
A emergency locate request was sent in from summit utilities at approximately (15:45) on august 16, 2022. Our operations technician responded to the scene at (16:15) and discovered a gas reading of 3% lel in the atmosphere....More technicians arrived and began bar hole testing which revealed readings as high as 50% gas. The pipeline (bm-21) is in the vicinity of 2 duplexes and runs under 2 concrete driveways to these duplexes; the suspected leak was under one of these concrete driveways. The decision was made to evacuate the residents of the 2 duplexes as a precaution; this decision was made at approximately 18:40 on august 16, 2022. After evacuating the residents, operations personnel formed a perimeter and monitored gas levels while waiting for equipment to arrive to isolate and blow down the affected pipeline segment. Operations isolated 8,661' of pipe by placing a stopple plug in a stopple fitting located at line plus 540+95 and by closing block valve 43120 at greenbrier town boarder station located at line plus 627+56; the line was blown flat at 22:50 on august 16, 2022. Contractors mobilized to the site on the morning of august 17, 2022....After heavy rain moved out of the area, the contractors began removing both concrete driveways. The pipe was uncovered on the afternoon (august 17th) and a small pinhole leak was discovered in a girth weld. The pipe was cutout and 44' of 0.237: wt, 4.5" dia, x52 grade pipe was installed in its place. The pipe was purged and loaded and then brought back into service on the morning of august 18th, 2022.
Detailed record list
Report Received Date
2022-08-29 00:00:00
Iyear
2022
Report Number
20220092
Supplemental Number
37039
Report Type
Original Final
Operator Id
Name
Enable Gas Transmission, Llc
Operator Street Address
1300 Main Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2022-08-16 18:46:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Nrc Rpt Num
Nrc Rpt Datetime
2022-08-16 18:53:00
Additional Nrc Report Numbers
1344853
Commodity Released Type
Natural Gas
Unintentional Release
1
Intentional Release
14.6
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-08-16 22:50:00
Restart Datetime
2022-08-18 11:27:00
Communication State Fed Ind
Yes
Party Initiated Communication
Local/state/federal Emergency Responder
Initial Responder Com Datetime
2022-08-16 07:11:00
Ignite Ind
No
Upstream Action Taken
Valve Closure
Upstream Valve Close Datetime
2022-08-16 22:40:00
Downstream Action Taken
Valve Closure
Downstream Vlv Close Datetime
2022-08-16 22:50:00
Num Pub Evacuated
4
Incident Identified Datetime
2022-08-16 16:15:00
On Site Datetime
2022-08-16 16:15:00
On Off Shore
Onshore
Onshore State Abbreviation
Ar
Onshore Postal Code
72058
Onshore City Name
Greenbrier
Onshore County Name
Faulkner
Designated Location
Not Applicable
Pipe Fac Name
Bm-21
Segment Name
Pipeline
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
36
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
4
Puddle Weld Ind
No
Pipe Wall Thickness
0.188
Pipe Smys
30000
Pipe Specification
Unknown
Pipe Seam Type
Furnace Butt Welded
Pipe Manufacturer
Unknown
Pipe Coating Type
Coal Tar
Coating Applied Ind
Unknown
Installation Year
1957
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Class Location Type
Class 3 Location
Could Be Hca
Yes
Determination Method
Method2
Pir Radius
55
Heat Damage Ind
No
Non Heat Damage Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
9
Est Cost Intentional Release
135
Est Cost Prop Damage
69351
Est Cost Emergency
0
Est Cost Other
852
Est Cost Other Details
Hotel Stays For Those Evacuated.
Gas Cost In Mcf
9.28
Prpty
70347
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
2
Num Business Building Affctd
1
Wildlife Impact Ind
No
Accident Psig
260
Gas Flow In Pipe In Mcf
3534
Mop Psig
310
Mop Cfr Section
192.619(A)(2)
Maop Established Date
2012-03-30 00:00:00
Maop Reversal Flow Ind
Bi-Directional
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
Yes
Gas Odorized Ind
Yes
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Length Segment Isolated
8661
Internal Inspection Ind
No
Unsuitable Mainline Ind
Yes
Other Restrictions Ind
Yes
Other Inspection Ind
Yes
Internal Inspection Details
No Launcher/receiver; Dead Legs Are Present
Operation Complications Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
No
Accident Identifier
Other
Accident Details
An Emergency Locate Request Was Submitted By Summit Utilities.
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The leak was very small (pin hole) and not something a controller would be able to identify.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Material Failure Of Pipe Or Weld
Cause Details
Design-, Construction-, Installation-, Or Fabrication-Related
Pwjf Failure Type
Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind
Yes
Other Factor
Yes
Other Factor Details
Pin Hole In Weld
Pwf Additional Other Ind
Yes
Additional Other Details
Pin Hole In Weld
Post Constr Pressure Test Val
Unknown
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
Yes
Hydrtst Most Rcnt Year
2018
Hydrtst Most Rcnt Pressure
388
Direct Asmnt Conducted
Yes, But The Point Of The Accident Was Not Identified As A Dig Site
Direct Asmnt Pnt Not Idntf Yr
2020
Asmnt Ecda Rcnt Year
2020
Asmnt Icda Rcnt Year
2020
Asmnt Ecda Rcnt Ind
Yes
Asmnt Icda Rcnt Ind
Yes
Non Destructive Exam Ind
No
Extrnl Cor Galvanic Ind
Yes
Preparer Name
D***** A******
Preparer Title
Sr. Dot Specialist
Preparer Email
D*************@e*************.com
Preparer Telephone
501-472-5065
Local Contact Name
B****** B***
Local Contact Email
B***********@e*************.com
Local Contact Telephone
870-769-2435
Authorizer Name
J**** C****
Authorizer Title
Sr. Manager Regulatory Compliance
Authorizer Telephone
318-426-2515
Authorizer Email
J**********@e*************.com
Narrative
A emergency locate request was sent in from summit utilities at approximately (15:45) on august 16, 2022. Our operations technician responded to the scene at (16:15) and discovered a gas reading of 3% lel in the atmosphere....More technicians arrived and began bar hole testing which revealed readings as high as 50% gas. The pipeline (bm-21) is in the vicinity of 2 duplexes and runs under 2 concrete driveways to these duplexes; the suspected leak was under one of these concrete driveways. The decision was made to evacuate the residents of the 2 duplexes as a precaution; this decision was made at approximately 18:40 on august 16, 2022. After evacuating the residents, operations personnel formed a perimeter and monitored gas levels while waiting for equipment to arrive to isolate and blow down the affected pipeline segment. Operations isolated 8,661' of pipe by placing a stopple plug in a stopple fitting located at line plus 540+95 and by closing block valve 43120 at greenbrier town boarder station located at line plus 627+56; the line was blown flat at 22:50 on august 16, 2022. Contractors mobilized to the site on the morning of august 17, 2022....After heavy rain moved out of the area, the contractors began removing both concrete driveways. The pipe was uncovered on the afternoon (august 17th) and a small pinhole leak was discovered in a girth weld. The pipe was cutout and 44' of 0.237: wt, 4.5" dia, x52 grade pipe was installed in its place. The pipe was purged and loaded and then brought back into service on the morning of august 18th, 2022.
Report Received Date 2022-08-29 00:00:00
Iyear 2022
Report Number 20220092
Supplemental Number 37039
Report Type Original Final
Operator Id 602 PHMSA Enforcement
Name Enable Gas Transmission, Llc
Operator Street Address 1300 Main Street
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2022-08-16 18:46:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 35.22697 Google Maps OpenStreetMap
Location Longitude -92.398986 Google Maps OpenStreetMap
Nrc Rpt Num 1344682 NRC Report How to search
Nrc Rpt Datetime 2022-08-16 18:53:00
Additional Nrc Report Numbers 1344853
Commodity Released Type Natural Gas
Unintentional Release 1
Intentional Release 14.6
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind Yes
Shutdown Datetime 2022-08-16 22:50:00
Restart Datetime 2022-08-18 11:27:00
Communication State Fed Ind Yes
Party Initiated Communication Local/state/federal Emergency Responder
Initial Responder Com Datetime 2022-08-16 07:11:00
Ignite Ind No
Upstream Action Taken Valve Closure
Upstream Valve Close Datetime 2022-08-16 22:40:00
Downstream Action Taken Valve Closure
Downstream Vlv Close Datetime 2022-08-16 22:50:00
Num Pub Evacuated 4
Incident Identified Datetime 2022-08-16 16:15:00
On Site Datetime 2022-08-16 16:15:00
On Off Shore Onshore
Onshore State Abbreviation Ar
Onshore Postal Code 72058
Onshore City Name Greenbrier
Onshore County Name Faulkner
Designated Location Not Applicable
Pipe Fac Name Bm-21
Segment Name Pipeline
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Pavement
Depth Of Cover 36
Other Underground Facilities No
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Pipeline, Including Valve Sites
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 4
Puddle Weld Ind No
Pipe Wall Thickness 0.188
Pipe Smys 30000
Pipe Specification Unknown
Pipe Seam Type Furnace Butt Welded
Pipe Manufacturer Unknown
Pipe Coating Type Coal Tar
Coating Applied Ind Unknown
Installation Year 1957
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Class Location Type Class 3 Location
Could Be Hca Yes
Determination Method Method2
Pir Radius 55
Heat Damage Ind No
Non Heat Damage Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 9
Est Cost Intentional Release 135
Est Cost Prop Damage 69351
Est Cost Emergency 0
Est Cost Other 852
Est Cost Other Details Hotel Stays For Those Evacuated.
Gas Cost In Mcf 9.28
Prpty 70347
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 2
Num Business Building Affctd 1
Wildlife Impact Ind No
Accident Psig 260
Gas Flow In Pipe In Mcf 3534
Mop Psig 310
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 2012-03-30 00:00:00
Maop Reversal Flow Ind Bi-Directional
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind Yes
Gas Odorized Ind Yes
Upstream Valve Type Ind Manual
Downstream Valve Type Ind Manual
Length Segment Isolated 8661
Internal Inspection Ind No
Unsuitable Mainline Ind Yes
Other Restrictions Ind Yes
Other Inspection Ind Yes
Internal Inspection Details No Launcher/receiver; Dead Legs Are Present
Operation Complications Ind No
Pipeline Function Transmission System
Scada In Place Ind No
Accident Identifier Other
Accident Details An Emergency Locate Request Was Submitted By Summit Utilities.
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The leak was very small (pin hole) and not something a controller would be able to identify.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Material Failure Of Pipe Or Weld
Cause Details Design-, Construction-, Installation-, Or Fabrication-Related
Pwjf Failure Type Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind Yes
Other Factor Yes
Other Factor Details Pin Hole In Weld
Pwf Additional Other Ind Yes
Additional Other Details Pin Hole In Weld
Post Constr Pressure Test Val Unknown
Collected Data Ind No
Has Hydrtst Conduc Before Ind Yes
Hydrtst Most Rcnt Year 2018
Hydrtst Most Rcnt Pressure 388
Direct Asmnt Conducted Yes, But The Point Of The Accident Was Not Identified As A Dig Site
Direct Asmnt Pnt Not Idntf Yr 2020
Asmnt Ecda Rcnt Year 2020
Asmnt Icda Rcnt Year 2020
Asmnt Ecda Rcnt Ind Yes
Asmnt Icda Rcnt Ind Yes
Non Destructive Exam Ind No
Extrnl Cor Galvanic Ind Yes
Preparer Name D***** A******
Preparer Title Sr. Dot Specialist
Preparer Email D*************@e*************.com
Preparer Telephone 501-472-5065
Local Contact Name B****** B***
Local Contact Email B***********@e*************.com
Local Contact Telephone 870-769-2435
Authorizer Name J**** C****
Authorizer Title Sr. Manager Regulatory Compliance
Authorizer Telephone 318-426-2515
Authorizer Email J**********@e*************.com
Narrative A emergency locate request was sent in from summit utilities at approximately (15:45) on august 16, 2022. Our operations technician responded to the scene at (16:15) and discovered a gas reading of 3% lel in the atmosphere....More technicians arrived and began bar hole testing which revealed readings as high as 50% gas. The pipeline (bm-21) is in the vicinity of 2 duplexes and runs under 2 concrete driveways to these duplexes; the suspected leak was under one of these concrete driveways. The decision was made to evacuate the residents of the 2 duplexes as a precaution; this decision was made at approximately 18:40 on august 16, 2022. After evacuating the residents, operations personnel formed a perimeter and monitored gas levels while waiting for equipment to arrive to isolate and blow down the affected pipeline segment. Operations isolated 8,661' of pipe by placing a stopple plug in a stopple fitting located at line plus 540+95 and by closing block valve 43120 at greenbrier town boarder station located at line plus 627+56; the line was blown flat at 22:50 on august 16, 2022. Contractors mobilized to the site on the morning of august 17, 2022....After heavy rain moved out of the area, the contractors began removing both concrete driveways. The pipe was uncovered on the afternoon (august 17th) and a small pinhole leak was discovered in a girth weld. The pipe was cutout and 44' of 0.237: wt, 4.5" dia, x52 grade pipe was installed in its place. The pipe was purged and loaded and then brought back into service on the morning of august 18th, 2022.