GTG incident on 2022-06-30 — NE

Operator
Northern Natural Gas Co
Cause
Material Failure Of Pipe Or Weld
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$198,500
Incident datetime
2022-06-30 17:00
Report number
Location
NE
Narrative
A 157 ppm leak was indicated via aerial patrol on the m433b wakefield-to-marquette mainline at milepost 63.57 on 6/30/2022. On 7/1/2022, a grade 3 leak was confirmed and thought to be from a flanged connection of a stopple fitting. On 7/5/2022, the flanged connection of the stopple was examined and determined not to be the source of the leak. It was determined that this leak would be an incident since the repair costs would likely exceed the $122k reporting threshold. The leak was examined on 7/13/2022. The leak was on a girth weld, which was 8-1/2-inches downstream of the stopple installed in 2020. The leak was in the centerline of the girth weld at the 5:00 position and was approximately 3-inches long. The leak was secured with a temporary repair until a type-b sleeve was installed. The next downstream girth weld was also reinforced with a type-b sleeve to mitigate concern of movement caused by the 2020 construction. Updates to this report: 01/13/2023 - time zone corrected to eastern time. 01/31/2023 - corrected the date the leak was examined. 05/23/2023 - submitted as final
Detailed record list
Report Received Date
2022-07-28 00:00:00
Iyear
2022
Report Number
20220076
Supplemental Number
38102
Report Type
Supplemental Final
Operator Id
Name
Northern Natural Gas Co
Operator Street Address
1111 South 103rd Street
Operator City Name
Omaha
Operator State Abbreviation
NE
Operator Postal Code
68124
Local Datetime
2022-07-05 09:25:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Nrc Rpt Num
Nrc Rpt Datetime
2022-07-05 09:57:00
Additional Nrc Report Numbers
1340749
Commodity Released Type
Natural Gas
Unintentional Release
1
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
No
Shutdown Explain
A Temporary Clamp Was Installed To Stop The Leak
Communication State Fed Ind
No
Ignite Ind
No
Upstream Action Taken
Operational Control
Upstream Oprtnl Cntrl Detail
Pressure Reduction
Downstream Action Taken
Operational Control
Downstream Oprtnl Cntrl Detail
Pressure Reduction
Num Pub Evacuated
0
Incident Identified Datetime
2022-06-30 17:00:00
On Site Datetime
2022-07-01 13:00:00
On Off Shore
Onshore
Onshore State Abbreviation
Mi
Onshore Postal Code
49967
Onshore City Name
Not Within A Municipality
Onshore County Name
Houghton
Designated Location
Milepost
Designated Name
63.57
Pipe Fac Name
Wakefield To Marquette
Segment Name
M433b
Federal
No
Location Type
Pipeline Right-Of-Way
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
48
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Weld/fusion, Including Heat-Affected Zone
Pipe Diameter
16
Pipe Wall Thickness
0.203
Pipe Smys
60000
Pipe Specification
Api 5lx
Pipe Seam Type
Longitudinal Erw - Low Frequency
Pipe Manufacturer
Youngstown
Pipe Coating Type
Cold Applied Tape
Coating Applied Ind
Yes
Weld Subtype
Pipe Girth Weld
Different Girth Weld Ind
No
Installation Year
1965
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
359
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
6
Est Cost Intentional Release
0
Est Cost Prop Damage
198500
Est Cost Emergency
1500
Est Cost Other
0
Gas Cost In Mcf
6.09
Prpty
200006
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
740
Gas Flow In Pipe In Mcf
1
Mop Psig
945
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1965-12-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Length Segment Isolated
105600
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Air Patrol
Operator Type
Contractor Working For The Operator
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The leak was not discernable from scada.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Material Failure Of Pipe Or Weld
Cause Details
Design-, Construction-, Installation-, Or Fabrication-Related
Pwjf Failure Type
Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind
Yes
Mechanical Stress
Yes
Additional Crack Ind
Yes
Post Constr Pressure Test Val
1202
Collected Data Ind
Yes
Axial Magnetic Flx Lkg Ind
Yes
Cir Trn Wave Mgn Flx Lkg Ind
Yes
Geometry Deformation Ind
Yes
Emat Ind
Yes
Axial Recent Year
2021
Axial Rcnt Propul Method
Free Swimming
Axial Rcnt Attuned Detect
Metal Loss
Axial Rcnt Atnd Dtct Metal
High Resolution
Axial Previous Year
2018
Axial Prev Propul Method
Free Swimming
Axial Prev Attuned Detect
Metal Loss
Axial Prev Atnd Dtct Metal
High Resolution
Circ Wave Recent Year
2021
Circ Wv Rcnt Propul Method
Free Swimming
Circ Wv Rcnt Resolution
High Resolution
Circ Wv Previous Year
2018
Circ Wv Prev Propul Method
Free Swimming
Circ Wv Prev Resolution
High Resolution
Geometry Recent Year
2021
Geometry Rcnt Propul Method
Free Swimming
Geometry Rcnt Resolution
High Resolution
Geometrt Rcnt Measur Cups
Inside Ili Cups
Geometry Previous Year
2018
Geometry Prev Propul Method
Free Swimming
Geometry Prev Resolution
High Resolution
Geometrt Prev Measur Cups
Inside Ili Cups
Emat Recent Year
2018
Emat Rcnt Propul Method
Free Swimming
Emat Previous Year
2014
Emat Prev Propul Method
Free Swimming
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Pwf Construction Ind
Yes
Preparer Name
D**** C*******
Preparer Email
D*************@n****.com
Preparer Telephone
402-398-7439
Local Contact Name
G*** K******
Local Contact Email
G***********@n****.com
Local Contact Telephone
402-398-7274
Authorizer Name
T** C******
Authorizer Telephone
402-398-7715
Authorizer Email
T*************@n****.com
Narrative
A 157 ppm leak was indicated via aerial patrol on the m433b wakefield-to-marquette mainline at milepost 63.57 on 6/30/2022. On 7/1/2022, a grade 3 leak was confirmed and thought to be from a flanged connection of a stopple fitting. On 7/5/2022, the flanged connection of the stopple was examined and determined not to be the source of the leak. It was determined that this leak would be an incident since the repair costs would likely exceed the $122k reporting threshold. The leak was examined on 7/13/2022. The leak was on a girth weld, which was 8-1/2-inches downstream of the stopple installed in 2020. The leak was in the centerline of the girth weld at the 5:00 position and was approximately 3-inches long. The leak was secured with a temporary repair until a type-b sleeve was installed. The next downstream girth weld was also reinforced with a type-b sleeve to mitigate concern of movement caused by the 2020 construction. Updates to this report: 01/13/2023 - time zone corrected to eastern time. 01/31/2023 - corrected the date the leak was examined. 05/23/2023 - submitted as final
Report Received Date 2022-07-28 00:00:00
Iyear 2022
Report Number 20220076
Supplemental Number 38102
Report Type Supplemental Final
Operator Id 13750 PHMSA Enforcement
Name Northern Natural Gas Co
Operator Street Address 1111 South 103rd Street
Operator City Name Omaha
Operator State Abbreviation NE
Operator Postal Code 68124
Local Datetime 2022-07-05 09:25:00
Time Zone Eastern
Daylight Savings Ind Yes
Location Latitude 46.4960017 Google Maps OpenStreetMap
Location Longitude -88.7298983 Google Maps OpenStreetMap
Nrc Rpt Num 1340611 NRC Report How to search
Nrc Rpt Datetime 2022-07-05 09:57:00
Additional Nrc Report Numbers 1340749
Commodity Released Type Natural Gas
Unintentional Release 1
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind No
Shutdown Explain A Temporary Clamp Was Installed To Stop The Leak
Communication State Fed Ind No
Ignite Ind No
Upstream Action Taken Operational Control
Upstream Oprtnl Cntrl Detail Pressure Reduction
Downstream Action Taken Operational Control
Downstream Oprtnl Cntrl Detail Pressure Reduction
Num Pub Evacuated 0
Incident Identified Datetime 2022-06-30 17:00:00
On Site Datetime 2022-07-01 13:00:00
On Off Shore Onshore
Onshore State Abbreviation Mi
Onshore Postal Code 49967
Onshore City Name Not Within A Municipality
Onshore County Name Houghton
Designated Location Milepost
Designated Name 63.57
Pipe Fac Name Wakefield To Marquette
Segment Name M433b
Federal No
Location Type Pipeline Right-Of-Way
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 48
Other Underground Facilities No
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Pipeline, Including Valve Sites
Item Involved Weld/fusion, Including Heat-Affected Zone
Pipe Diameter 16
Pipe Wall Thickness 0.203
Pipe Smys 60000
Pipe Specification Api 5lx
Pipe Seam Type Longitudinal Erw - Low Frequency
Pipe Manufacturer Youngstown
Pipe Coating Type Cold Applied Tape
Coating Applied Ind Yes
Weld Subtype Pipe Girth Weld
Different Girth Weld Ind No
Installation Year 1965
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Crack
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 359
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 6
Est Cost Intentional Release 0
Est Cost Prop Damage 198500
Est Cost Emergency 1500
Est Cost Other 0
Gas Cost In Mcf 6.09
Prpty 200006
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 740
Gas Flow In Pipe In Mcf 1
Mop Psig 945
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 1965-12-01 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Length Segment Isolated 105600
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Air Patrol
Operator Type Contractor Working For The Operator
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The leak was not discernable from scada.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Material Failure Of Pipe Or Weld
Cause Details Design-, Construction-, Installation-, Or Fabrication-Related
Pwjf Failure Type Design-, Construction-, Installation-, Or Fabrication-Related
Field Exam Ind Yes
Mechanical Stress Yes
Additional Crack Ind Yes
Post Constr Pressure Test Val 1202
Collected Data Ind Yes
Axial Magnetic Flx Lkg Ind Yes
Cir Trn Wave Mgn Flx Lkg Ind Yes
Geometry Deformation Ind Yes
Emat Ind Yes
Axial Recent Year 2021
Axial Rcnt Propul Method Free Swimming
Axial Rcnt Attuned Detect Metal Loss
Axial Rcnt Atnd Dtct Metal High Resolution
Axial Previous Year 2018
Axial Prev Propul Method Free Swimming
Axial Prev Attuned Detect Metal Loss
Axial Prev Atnd Dtct Metal High Resolution
Circ Wave Recent Year 2021
Circ Wv Rcnt Propul Method Free Swimming
Circ Wv Rcnt Resolution High Resolution
Circ Wv Previous Year 2018
Circ Wv Prev Propul Method Free Swimming
Circ Wv Prev Resolution High Resolution
Geometry Recent Year 2021
Geometry Rcnt Propul Method Free Swimming
Geometry Rcnt Resolution High Resolution
Geometrt Rcnt Measur Cups Inside Ili Cups
Geometry Previous Year 2018
Geometry Prev Propul Method Free Swimming
Geometry Prev Resolution High Resolution
Geometrt Prev Measur Cups Inside Ili Cups
Emat Recent Year 2018
Emat Rcnt Propul Method Free Swimming
Emat Previous Year 2014
Emat Prev Propul Method Free Swimming
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Pwf Construction Ind Yes
Preparer Name D**** C*******
Preparer Email D*************@n****.com
Preparer Telephone 402-398-7439
Local Contact Name G*** K******
Local Contact Email G***********@n****.com
Local Contact Telephone 402-398-7274
Authorizer Name T** C******
Authorizer Telephone 402-398-7715
Authorizer Email T*************@n****.com
Narrative A 157 ppm leak was indicated via aerial patrol on the m433b wakefield-to-marquette mainline at milepost 63.57 on 6/30/2022. On 7/1/2022, a grade 3 leak was confirmed and thought to be from a flanged connection of a stopple fitting. On 7/5/2022, the flanged connection of the stopple was examined and determined not to be the source of the leak. It was determined that this leak would be an incident since the repair costs would likely exceed the $122k reporting threshold. The leak was examined on 7/13/2022. The leak was on a girth weld, which was 8-1/2-inches downstream of the stopple installed in 2020. The leak was in the centerline of the girth weld at the 5:00 position and was approximately 3-inches long. The leak was secured with a temporary repair until a type-b sleeve was installed. The next downstream girth weld was also reinforced with a type-b sleeve to mitigate concern of movement caused by the 2020 construction. Updates to this report: 01/13/2023 - time zone corrected to eastern time. 01/31/2023 - corrected the date the leak was examined. 05/23/2023 - submitted as final

All rights reserved. Copyright © by ClearPHMSA