GD incident on 2022-09-28 — IN

Operator
Indiana Gas Co Inc
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$1,381
Incident datetime
2022-09-28 14:24
Report number
Location
IN, JOHNSON
Narrative
A crew from johnson county remc was repairing a buried 3 phase electric service 4' from the home located at 5409 innisbrooke pl, greenwood in when the gas service caught on fire, catching the home on fire. The remc crew had been using a blow torch to heat shrink the repair. The 3-phase electric repair was approximately 7 inches below the gas service line. Remc crew stated they had spotted the gas service, which was correctly located, used a shovel to protect the plastic gas line before introducing flame near it. While using the flame to shrink wrap the repair, there was an ignition of the gas line.
Detailed record list
Occurred At
2022-09-28 14:24:00
Year
2022
Report Received Date
2022-10-19 00:00:00
Iyear
2022.0
Report Number
20220066.0
Supplemental Number
37623.0
Report Type
Supplemental Final
Operator Id
Name
Indiana Gas Co Inc
Operator Street Address
211 Nw Riverside Drive
Operator City Name
Evansville
Operator State Abbreviation
IN
Operator Postal Code
47708
Local Datetime
2022-09-28 14:05:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Street Address
5409 Innisbrooke Place
Location City Name
Greenwood
Location County Name
Johnson
Location State Abbreviation
IN
Location Postal Code
46142
Location Latitude
Location Longitude
Flow Cont Squeeze Off Ind
Yes
Nrc Rpt Datetime
2022-09-28 15:22:00
Nrc Rpt Num
Additional Nrc Report Numbers
1348695
Commodity Released Type
Natural Gas
Unintentional Release
22.08
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Ignite Datetime
2022-09-28 14:05:00
How Extinguished
Other
How Extinguished Other Detail
Fire Extinguished By Operator Squeezing Off The Gas Service Line.
Gas Consumed By Fire In Mcf
22.08
Explode Ind
No
Num Pub Evacuated
1.0
Incident Identified Datetime
2022-09-28 14:24:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-09-28 14:31:00
On Site Datetime
2022-09-28 14:23:00
Federal
No
Location Type
Private Property
Incident Area Type
Underground
Incident Area Subtype
Exposed Due To Excavation
Depth Of Cover
28.0
Other Underground Facilities
Yes
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Service
Installation Year
1992.0
Customer Type
Single Family Residential
Was Efv Installed Before Ind
No
Curb Valve Inst Before Inc Ind
No
Pipe Diameter
1.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Wt Plastic Unknown Ind
Unknown
Material Pe Pipe Code
Unknown
Release Type
Rupture
Rupture Orient
Circumferential
Rupture Length
1
Rupture Width
1
Class Location Type
Class 3 Location
Est Cost Oper Paid
400000.0
Est Cost Prop Damage
1381.0
Est Cost Emergency
2500.0
Est Cost Other
0.0
Gas Cost In Mcf
6.4311
Est Cost Unintentional Release
142.0
Est Cost Intentional Release
0.0
Prpty
404023.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
1.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
1.0
Num Business Building Affctd
0.0
Accident Psig
54.0
Normal Psig
54.0
Mop Psig
60.0
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1992-11-04 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Level
5.2
Scada In Place Ind
No
Accident Identifier
Notification From Third Party That Caused The Incident
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Nearby Industrial, Man-Made, Or Other Fire/explosion As Primary Cause Of Incident
Outside Force Type
Nearby Industrial, Man-Made, Or Other Fire/explosion As Primary Cause Of Incident
Osf Other Underground Ind
Yes
Io Follow Procedure Ind
Yes
Preparer Name
R**** P*****
Preparer Title
Lead Operations Specialist - Gas Compliance
Preparer Email
R***********@c****************.com
Preparer Telephone
317-997-3939
Local Contact Name
R**** P*****
Local Contact Email
Lead Operations Specialist - Gas Compliance
Local Contact Telephone
317-997-3939
Authorizer Name
S***** B***
Authorizer Title
Manager Pipeline Safety And Compliance
Authorizer Telephone
812-4914806
Authorizer Email
S**********@c****************.com
Narrative
A crew from johnson county remc was repairing a buried 3 phase electric service 4' from the home located at 5409 innisbrooke pl, greenwood in when the gas service caught on fire, catching the home on fire. The remc crew had been using a blow torch to heat shrink the repair. The 3-phase electric repair was approximately 7 inches below the gas service line. Remc crew stated they had spotted the gas service, which was correctly located, used a shovel to protect the plastic gas line before introducing flame near it. While using the flame to shrink wrap the repair, there was an ignition of the gas line.
Occurred At 2022-09-28 14:24:00
Year 2022
Report Received Date 2022-10-19 00:00:00
Iyear 2022.0
Report Number 20220066.0
Supplemental Number 37623.0
Report Type Supplemental Final
Operator Id 8070 PHMSA Enforcement
Name Indiana Gas Co Inc
Operator Street Address 211 Nw Riverside Drive
Operator City Name Evansville
Operator State Abbreviation IN
Operator Postal Code 47708
Local Datetime 2022-09-28 14:05:00
Time Zone Eastern
Daylight Savings Ind Yes
Location Street Address 5409 Innisbrooke Place
Location City Name Greenwood
Location County Name Johnson
Location State Abbreviation IN
Location Postal Code 46142
Location Latitude 39.6189 Google Maps OpenStreetMap
Location Longitude -86.2052 Google Maps OpenStreetMap
Flow Cont Squeeze Off Ind Yes
Nrc Rpt Datetime 2022-09-28 15:22:00
Nrc Rpt Num 1348530 NRC Report How to search
Additional Nrc Report Numbers 1348695
Commodity Released Type Natural Gas
Unintentional Release 22.08
Intentional Release 0.0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind Yes
Ignite Datetime 2022-09-28 14:05:00
How Extinguished Other
How Extinguished Other Detail Fire Extinguished By Operator Squeezing Off The Gas Service Line.
Gas Consumed By Fire In Mcf 22.08
Explode Ind No
Num Pub Evacuated 1.0
Incident Identified Datetime 2022-09-28 14:24:00
Communication State Fed Ind Yes
Party Initiated Communication Operator
Initial Responder Com Datetime 2022-09-28 14:31:00
On Site Datetime 2022-09-28 14:23:00
Federal No
Location Type Private Property
Incident Area Type Underground
Incident Area Subtype Exposed Due To Excavation
Depth Of Cover 28.0
Other Underground Facilities Yes
Crossing No
Pipe Facility Type Privately Owned
System Part Involved Service
Installation Year 1992.0
Customer Type Single Family Residential
Was Efv Installed Before Ind No
Curb Valve Inst Before Inc Ind No
Pipe Diameter 1.0
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Plastic
Plastic Type Polyethylene (Pe)
Wt Plastic Unknown Ind Unknown
Material Pe Pipe Code Unknown
Release Type Rupture
Rupture Orient Circumferential
Rupture Length 1
Rupture Width 1
Class Location Type Class 3 Location
Est Cost Oper Paid 400000.0
Est Cost Prop Damage 1381.0
Est Cost Emergency 2500.0
Est Cost Other 0.0
Gas Cost In Mcf 6.4311
Est Cost Unintentional Release 142.0
Est Cost Intentional Release 0.0
Prpty 404023.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 1.0
Num Persons Hosp Not Ovnght 0.0
Num Injured Treated By Emt 0.0
Num Resident Building Affctd 1.0
Num Business Building Affctd 0.0
Accident Psig 54.0
Normal Psig 54.0
Mop Psig 60.0
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 1992-11-04 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type Injection Pump
Gas Odorized Level 5.2
Scada In Place Ind No
Accident Identifier Notification From Third Party That Caused The Incident
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Outside Force Damage
Cause Details Nearby Industrial, Man-Made, Or Other Fire/explosion As Primary Cause Of Incident
Outside Force Type Nearby Industrial, Man-Made, Or Other Fire/explosion As Primary Cause Of Incident
Osf Other Underground Ind Yes
Io Follow Procedure Ind Yes
Preparer Name R**** P*****
Preparer Title Lead Operations Specialist - Gas Compliance
Preparer Email R***********@c****************.com
Preparer Telephone 317-997-3939
Local Contact Name R**** P*****
Local Contact Email Lead Operations Specialist - Gas Compliance
Local Contact Telephone 317-997-3939
Authorizer Name S***** B***
Authorizer Title Manager Pipeline Safety And Compliance
Authorizer Telephone 812-4914806
Authorizer Email S**********@c****************.com
Narrative A crew from johnson county remc was repairing a buried 3 phase electric service 4' from the home located at 5409 innisbrooke pl, greenwood in when the gas service caught on fire, catching the home on fire. The remc crew had been using a blow torch to heat shrink the repair. The 3-phase electric repair was approximately 7 inches below the gas service line. Remc crew stated they had spotted the gas service, which was correctly located, used a shovel to protect the plastic gas line before introducing flame near it. While using the flame to shrink wrap the repair, there was an ignition of the gas line.