GD incident on 2022-07-16 — NJ

Operator
Public Service Electric & Gas Co
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$225,000
Incident datetime
2022-07-16 04:00
Report number
Location
NJ, MORRIS
Narrative
On saturday july 16th pse&g received notification that a downed jcp&l electric wire that found its way to nearby metal guard rail and resulted in the ignition of a 6 inch 60 lb. Steel main located at 55 rt 24 in chester township. The location of the ignition involves a bridge. The main was throttled and temporary bypass was installed to continue to service customers. The location of the downed wire was 2 miles away from the ignition location. The cause for how the wire came into contact with the guard rail is unknown at this time. There are no indications at this time that any type of damage was involved. A permanent repair plan is being developed at this time.
Detailed record list
Occurred At
2022-07-16 04:00:00
Year
2022
Report Received Date
2022-09-02 00:00:00
Iyear
2022.0
Report Number
20220058.0
Supplemental Number
37803.0
Report Type
Supplemental Final
Operator Id
Name
Public Service Electric & Gas Co
Operator Street Address
80 Park Plaza M/c - T18
Operator City Name
Newark
Operator State Abbreviation
NJ
Operator Postal Code
07102-4194
Local Datetime
2022-07-16 04:00:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Street Address
55 Rt 24
Location City Name
Chester Township
Location County Name
Morris
Location State Abbreviation
NJ
Location Postal Code
07930
Location Latitude
Location Longitude
Flow Cont Meter Reg Ind
Yes
Nrc Rpt Datetime
2022-08-15 04:03:00
Nrc Rpt Num
Additional Nrc Report Numbers
1344584
Commodity Released Type
Natural Gas
Unintentional Release
514.0
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Ignite Datetime
2022-07-16 04:00:00
How Extinguished
Operator/contractor
Gas Consumed By Fire In Mcf
514
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2022-07-16 04:00:00
On Site Datetime
2022-07-16 04:15:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
36.0
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Municipally Owned
System Part Involved
Main
Installation Year
1983.0
Pipe Diameter
6.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Cast/wrought Iron
Release Type
Leak
Leak Type
Pinhole
Class Location Type
Class 4 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
225000.0
Est Cost Emergency
25000.0
Est Cost Other
0.0
Gas Cost In Mcf
5.31
Est Cost Unintentional Release
2729.0
Est Cost Intentional Release
0.0
Prpty
252729.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
0.0
Num Business Building Affctd
0.0
Accident Psig
60.0
Normal Psig
60.0
Mop Psig
60.0
Mop Cfr Section
192.619(A)(1)
Maop Established Date
1983-08-11 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Other Outside Force Damage
Outside Force Type
Other Outside Force Damage
Osf Other Details
A Jcp&l Power Line Came Down 2 Miles Away From The Pse&g Point Of Ignition. Ten Other Ignitions Of Various Types (No Other Gas) Occurred In The 2 Mile Affected Zone. The Cause For The Power Line Drop Has Never Been Determined.
Preparer Name
R**** G******
Preparer Title
Principal Regulatory Specialist
Preparer Email
R************@p***.com
Preparer Telephone
9739871589
Local Contact Name
R**** G******
Local Contact Email
R************@p***.com
Local Contact Telephone
9739871589
Authorizer Name
C**** L******
Authorizer Title
Manager Regulatory Policy And Procedure
Authorizer Telephone
973-896-7617
Authorizer Email
C******************@p***.com
Narrative
On saturday july 16th pse&g received notification that a downed jcp&l electric wire that found its way to nearby metal guard rail and resulted in the ignition of a 6 inch 60 lb. Steel main located at 55 rt 24 in chester township. The location of the ignition involves a bridge. The main was throttled and temporary bypass was installed to continue to service customers. The location of the downed wire was 2 miles away from the ignition location. The cause for how the wire came into contact with the guard rail is unknown at this time. There are no indications at this time that any type of damage was involved. A permanent repair plan is being developed at this time.
Occurred At 2022-07-16 04:00:00
Year 2022
Report Received Date 2022-09-02 00:00:00
Iyear 2022.0
Report Number 20220058.0
Supplemental Number 37803.0
Report Type Supplemental Final
Operator Id 15952 PHMSA Enforcement
Name Public Service Electric & Gas Co
Operator Street Address 80 Park Plaza M/c - T18
Operator City Name Newark
Operator State Abbreviation NJ
Operator Postal Code 07102-4194
Local Datetime 2022-07-16 04:00:00
Time Zone Eastern
Daylight Savings Ind Yes
Location Street Address 55 Rt 24
Location City Name Chester Township
Location County Name Morris
Location State Abbreviation NJ
Location Postal Code 07930
Location Latitude 40.77927 Google Maps OpenStreetMap
Location Longitude -74.72032 Google Maps OpenStreetMap
Flow Cont Meter Reg Ind Yes
Nrc Rpt Datetime 2022-08-15 04:03:00
Nrc Rpt Num 1344582 NRC Report How to search
Additional Nrc Report Numbers 1344584
Commodity Released Type Natural Gas
Unintentional Release 514.0
Intentional Release 0.0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind Yes
Ignite Datetime 2022-07-16 04:00:00
How Extinguished Operator/contractor
Gas Consumed By Fire In Mcf 514
Explode Ind No
Num Pub Evacuated 0.0
Incident Identified Datetime 2022-07-16 04:00:00
On Site Datetime 2022-07-16 04:15:00
Federal No
Location Type Public Property
Incident Area Type Underground
Incident Area Subtype Under Pavement
Depth Of Cover 36.0
Other Underground Facilities No
Crossing No
Pipe Facility Type Municipally Owned
System Part Involved Main
Installation Year 1983.0
Pipe Diameter 6.0
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Cast/wrought Iron
Release Type Leak
Leak Type Pinhole
Class Location Type Class 4 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 225000.0
Est Cost Emergency 25000.0
Est Cost Other 0.0
Gas Cost In Mcf 5.31
Est Cost Unintentional Release 2729.0
Est Cost Intentional Release 0.0
Prpty 252729.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 0.0
Num Persons Hosp Not Ovnght 0.0
Num Injured Treated By Emt 0.0
Num Resident Building Affctd 0.0
Num Business Building Affctd 0.0
Accident Psig 60.0
Normal Psig 60.0
Mop Psig 60.0
Mop Cfr Section 192.619(A)(1) View CFR 49 §192
Maop Established Date 1983-08-11 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type Injection Pump
Gas Odorized Lvl Not Msrd Ind Yes
Scada In Place Ind No
Accident Identifier Notification From Emergency Responder
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Outside Force Damage
Cause Details Other Outside Force Damage
Outside Force Type Other Outside Force Damage
Osf Other Details A Jcp&l Power Line Came Down 2 Miles Away From The Pse&g Point Of Ignition. Ten Other Ignitions Of Various Types (No Other Gas) Occurred In The 2 Mile Affected Zone. The Cause For The Power Line Drop Has Never Been Determined.
Preparer Name R**** G******
Preparer Title Principal Regulatory Specialist
Preparer Email R************@p***.com
Preparer Telephone 9739871589
Local Contact Name R**** G******
Local Contact Email R************@p***.com
Local Contact Telephone 9739871589
Authorizer Name C**** L******
Authorizer Title Manager Regulatory Policy And Procedure
Authorizer Telephone 973-896-7617
Authorizer Email C******************@p***.com
Narrative On saturday july 16th pse&g received notification that a downed jcp&l electric wire that found its way to nearby metal guard rail and resulted in the ignition of a 6 inch 60 lb. Steel main located at 55 rt 24 in chester township. The location of the ignition involves a bridge. The main was throttled and temporary bypass was installed to continue to service customers. The location of the downed wire was 2 miles away from the ignition location. The cause for how the wire came into contact with the guard rail is unknown at this time. There are no indications at this time that any type of damage was involved. A permanent repair plan is being developed at this time.

All rights reserved. Copyright © by ClearPHMSA