GTG incident on 2022-04-04 — TX

Operator
Gulf South Pipeline Company, Llc
Cause
Equipment Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$651
Incident datetime
2022-04-04 01:33
Report number
Location
TX
Narrative
On april 4, 2022 at approximately 1:33 am, gulf south pipelines experienced a station esd at its harrisville compressor station. Gas control dispatched local operations personnel who confirmed there was no fire at the time of arrival. Investigation revealed that a blown o-ring on an engine oil filter housing of unit #3 allowed oil to spray on the exhaust manifold which caused a brief fire. This flash fire was recognized by fire detection which initiated the esd. The damage was isolated to the oil filter housing and exhaust manifold insulation blanket. Unit #3 was locked out/tagged out, parts were replaced, the area was cleaned up and the unit was returned to service the same day. The answer provided for e1 is 1,424 psig which is the discharge pressure. The suction pressure at the station was 994 psig.
Detailed record list
Report Received Date
2022-04-27 00:00:00
Iyear
2022
Report Number
20220049
Supplemental Number
36615
Report Type
Original Final
Operator Id
Name
Gulf South Pipeline Company, Llc
Operator Street Address
9 Greenway Plaza Suite 2800
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77046
Local Datetime
2022-04-04 01:33:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
Nrc Rpt Num
Nrc Rpt Datetime
2022-04-04 02:39:00
Additional Nrc Report Numbers
1332763
Commodity Released Type
Natural Gas
Unintentional Release
3394
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-04-04 01:33:00
Restart Datetime
2022-04-04 10:21:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-04-04 01:42:00
Ignite Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2022-04-04 01:33:00
On Site Datetime
2022-04-04 02:21:00
On Off Shore
Onshore
Onshore State Abbreviation
Ms
Onshore Postal Code
39073
Onshore City Name
Not Within A Municipality
Onshore County Name
Simpson
Designated Location
Not Applicable
Pipe Fac Name
Harrisville Compressor Station
Segment Name
Index 817 / 817-L / 818
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Interstate
System Part Involved
Onshore Compressor Station Equipment And Piping
Item Involved
Esd System, But Excluding Product Drain Lines And Tubing
Installation Year
2007
Manufactured Year
2007
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Compressor Station Esd
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
272
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
18124
Est Cost Intentional Release
0
Est Cost Prop Damage
651
Est Cost Emergency
630
Est Cost Other
0
Gas Cost In Mcf
5.34
Prpty
19405
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
1424
Gas Flow In Pipe In Mcf
2300
Mop Psig
1480
Mop Cfr Section
192.619(A)(1)
Maop Established Date
2008-05-20 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Other Equipment Failure
Eq Failure Type
Other Equipment Failure
Eq Failure Details
O-Ring Failure On Engine Oil Filter Housing
Eq Additional Other Ind
Yes
Eq Additional Other Details
O-Ring Failure On Engine Oil Filter Housing
Preparer Name
S****** M********
Preparer Title
Pa Oq And Event Program Leader
Preparer Email
S****************@b**********.com
Preparer Telephone
2709035764
Authorizer Name
T*** B****
Authorizer Title
Manager Compliance Services
Authorizer Telephone
2703146547
Authorizer Email
T*********@b**********.com
Narrative
On april 4, 2022 at approximately 1:33 am, gulf south pipelines experienced a station esd at its harrisville compressor station. Gas control dispatched local operations personnel who confirmed there was no fire at the time of arrival. Investigation revealed that a blown o-ring on an engine oil filter housing of unit #3 allowed oil to spray on the exhaust manifold which caused a brief fire. This flash fire was recognized by fire detection which initiated the esd. The damage was isolated to the oil filter housing and exhaust manifold insulation blanket. Unit #3 was locked out/tagged out, parts were replaced, the area was cleaned up and the unit was returned to service the same day. The answer provided for e1 is 1,424 psig which is the discharge pressure. The suction pressure at the station was 994 psig.
Report Received Date 2022-04-27 00:00:00
Iyear 2022
Report Number 20220049
Supplemental Number 36615
Report Type Original Final
Operator Id 31728 PHMSA Enforcement
Name Gulf South Pipeline Company, Llc
Operator Street Address 9 Greenway Plaza Suite 2800
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77046
Local Datetime 2022-04-04 01:33:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 32.02848 Google Maps OpenStreetMap
Location Longitude -90.142318 Google Maps OpenStreetMap
Nrc Rpt Num 1332640 NRC Report How to search
Nrc Rpt Datetime 2022-04-04 02:39:00
Additional Nrc Report Numbers 1332763
Commodity Released Type Natural Gas
Unintentional Release 3394
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind Yes
Shutdown Datetime 2022-04-04 01:33:00
Restart Datetime 2022-04-04 10:21:00
Communication State Fed Ind Yes
Party Initiated Communication Operator
Initial Responder Com Datetime 2022-04-04 01:42:00
Ignite Ind No
Num Pub Evacuated 0
Incident Identified Datetime 2022-04-04 01:33:00
On Site Datetime 2022-04-04 02:21:00
On Off Shore Onshore
Onshore State Abbreviation Ms
Onshore Postal Code 39073
Onshore City Name Not Within A Municipality
Onshore County Name Simpson
Designated Location Not Applicable
Pipe Fac Name Harrisville Compressor Station
Segment Name Index 817 / 817-L / 818
Federal No
Location Type Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Inside A Building
Crossing No
Pipe Facility Type Interstate
System Part Involved Onshore Compressor Station Equipment And Piping
Item Involved Esd System, But Excluding Product Drain Lines And Tubing
Installation Year 2007
Manufactured Year 2007
Material Involved Carbon Steel
Release Type Other
Release Type Details Compressor Station Esd
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 272
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 18124
Est Cost Intentional Release 0
Est Cost Prop Damage 651
Est Cost Emergency 630
Est Cost Other 0
Gas Cost In Mcf 5.34
Prpty 19405
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 1424
Gas Flow In Pipe In Mcf 2300
Mop Psig 1480
Mop Cfr Section 192.619(A)(1) View CFR 49 §192
Maop Established Date 2008-05-20 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Other Equipment Failure
Eq Failure Type Other Equipment Failure
Eq Failure Details O-Ring Failure On Engine Oil Filter Housing
Eq Additional Other Ind Yes
Eq Additional Other Details O-Ring Failure On Engine Oil Filter Housing
Preparer Name S****** M********
Preparer Title Pa Oq And Event Program Leader
Preparer Email S****************@b**********.com
Preparer Telephone 2709035764
Authorizer Name T*** B****
Authorizer Title Manager Compliance Services
Authorizer Telephone 2703146547
Authorizer Email T*********@b**********.com
Narrative On april 4, 2022 at approximately 1:33 am, gulf south pipelines experienced a station esd at its harrisville compressor station. Gas control dispatched local operations personnel who confirmed there was no fire at the time of arrival. Investigation revealed that a blown o-ring on an engine oil filter housing of unit #3 allowed oil to spray on the exhaust manifold which caused a brief fire. This flash fire was recognized by fire detection which initiated the esd. The damage was isolated to the oil filter housing and exhaust manifold insulation blanket. Unit #3 was locked out/tagged out, parts were replaced, the area was cleaned up and the unit was returned to service the same day. The answer provided for e1 is 1,424 psig which is the discharge pressure. The suction pressure at the station was 994 psig.

All rights reserved. Copyright © by ClearPHMSA