Narrative
During a site visit to inspect newly installed station restoration, a gas odor was detected near the valve setting. Water was present around the base of the valve due to previous weather and bubbles were noticed at ground level. Leak was deemed not fixable by normal means (greasing) so valve was replaced. Due to the nature of the leak, the volume of gas loss was small but could not be determined.
Detailed record list
Report Received Date
2022-04-01 00:00:00
Iyear
2022
Report Number
20220041
Supplemental Number
36534
Report Type
Original Final
Operator Id
Name
Piedmont Natural Gas Co Inc
Operator Street Address
525 South Tryon Street
Operator City Name
Charlotte
Operator State Abbreviation
NC
Operator Postal Code
28202
Local Datetime
2022-03-09 13:30:00
Time Zone
Eastern
Daylight Savings Ind
No
Location Latitude
Location Longitude
Nrc Rpt Num
Nrc Rpt Datetime
2022-03-10 14:38:00
Additional Nrc Report Numbers
1330814
Commodity Released Type
Natural Gas
Unintentional Release
0.1
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Idle
Communication State Fed Ind
No
Ignite Ind
No
Upstream Action Taken
Operational Control
Upstream Oprtnl Cntrl Detail
No Initial Action Taken Place.
Downstream Action Taken
Operational Control
Downstream Oprtnl Cntrl Detail
No Initial Action Taken Place.
Num Pub Evacuated
0
Incident Identified Datetime
2022-03-09 13:15:00
On Site Datetime
2022-03-09 14:30:00
On Off Shore
Onshore
Onshore State Abbreviation
Nc
Onshore Postal Code
27910
Onshore City Name
Ahoskie
Onshore County Name
Hertford
Designated Location
Not Applicable
Pipe Fac Name
Line 208
Segment Name
208_mlv_1
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
65
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Intrastate
System Part Involved
Onshore Pipeline, Including Valve Sites
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
12
Puddle Weld Ind
No
Pipe Wall Thickness
0.312
Pipe Smys
42000
Pipe Specification
Unknown
Pipe Seam Type
Longitudinal Erw - High Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Coal Tar
Coating Applied Ind
Yes
Installation Year
2002
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Seal Or Packing
Class Location Type
Class 2 Location
Could Be Hca
No
Pir Radius
254
Heat Damage Ind
No
Non Heat Damage Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
0
Est Cost Intentional Release
0
Est Cost Prop Damage
770000
Est Cost Emergency
30000
Est Cost Other
0
Gas Cost In Mcf
0.1
Prpty
800000
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
775
Gas Flow In Pipe In Mcf
5
Mop Psig
800
Mop Cfr Section
192.619(A)(2)
Maop Established Date
2021-09-30 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Length Segment Isolated
44536
Internal Inspection Ind
Yes
Operation Complications Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Control Valve Ind
Yes
Additional Vibration Ind
Yes
Additional Defect Ind
Yes
Additional Installation Ind
Yes
Eq Additional Misalign Ind
Yes
Eq Additional Other Ind
Yes
Eq Additional Other Details
Gasket Failure
Preparer Name
C********** R******
Preparer Title
Gas Regulatory Compliance Analyst
Preparer Email
C******************@d**********.com
Preparer Telephone
704-731-4680
Authorizer Name
F***** B****
Authorizer Title
Pipeline Safety Manager
Authorizer Telephone
704-731-4618
Authorizer Email
F***********@d**********.com
Narrative
During a site visit to inspect newly installed station restoration, a gas odor was detected near the valve setting. Water was present around the base of the valve due to previous weather and bubbles were noticed at ground level. Leak was deemed not fixable by normal means (greasing) so valve was replaced. Due to the nature of the leak, the volume of gas loss was small but could not be determined.
Report Received Date 2022-04-01 00:00:00
Iyear 2022
Report Number 20220041
Supplemental Number 36534
Report Type Original Final
Operator Id 15518 PHMSA Enforcement
Name Piedmont Natural Gas Co Inc
Operator Street Address 525 South Tryon Street
Operator City Name Charlotte
Operator State Abbreviation NC
Operator Postal Code 28202
Local Datetime 2022-03-09 13:30:00
Time Zone Eastern
Daylight Savings Ind No
Location Latitude 36.344927 Google Maps OpenStreetMap
Location Longitude -76.934875 Google Maps OpenStreetMap
Nrc Rpt Num 1330740 NRC Report How to search
Nrc Rpt Datetime 2022-03-10 14:38:00
Additional Nrc Report Numbers 1330814
Commodity Released Type Natural Gas
Unintentional Release 0.1
Intentional Release 0
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Idle
Communication State Fed Ind No
Ignite Ind No
Upstream Action Taken Operational Control
Upstream Oprtnl Cntrl Detail No Initial Action Taken Place.
Downstream Action Taken Operational Control
Downstream Oprtnl Cntrl Detail No Initial Action Taken Place.
Num Pub Evacuated 0
Incident Identified Datetime 2022-03-09 13:15:00
On Site Datetime 2022-03-09 14:30:00
On Off Shore Onshore
Onshore State Abbreviation Nc
Onshore Postal Code 27910
Onshore City Name Ahoskie
Onshore County Name Hertford
Designated Location Not Applicable
Pipe Fac Name Line 208
Segment Name 208_mlv_1
Federal No
Location Type Operator-Controlled Property
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 65
Other Underground Facilities No
Crossing No
Pipe Facility Type Intrastate
System Part Involved Onshore Pipeline, Including Valve Sites
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 12
Puddle Weld Ind No
Pipe Wall Thickness 0.312
Pipe Smys 42000
Pipe Specification Unknown
Pipe Seam Type Longitudinal Erw - High Frequency
Pipe Manufacturer Unknown
Pipe Coating Type Coal Tar
Coating Applied Ind Yes
Installation Year 2002
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Seal Or Packing
Class Location Type Class 2 Location
Could Be Hca No
Pir Radius 254
Heat Damage Ind No
Non Heat Damage Ind No
Did Occur In Mca Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 0
Est Cost Intentional Release 0
Est Cost Prop Damage 770000
Est Cost Emergency 30000
Est Cost Other 0
Gas Cost In Mcf 0.1
Prpty 800000
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 775
Gas Flow In Pipe In Mcf 5
Mop Psig 800
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 2021-09-30 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Length Segment Isolated 44536
Internal Inspection Ind Yes
Operation Complications Ind No
Pipeline Function Transmission System
Scada In Place Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Malfunction Of Control/relief Equipment
Eq Failure Type Malfunction Of Control/relief Equipment
Control Valve Ind Yes
Additional Vibration Ind Yes
Additional Defect Ind Yes
Additional Installation Ind Yes
Eq Additional Misalign Ind Yes
Eq Additional Other Ind Yes
Eq Additional Other Details Gasket Failure
Preparer Name C********** R******
Preparer Title Gas Regulatory Compliance Analyst
Preparer Email C******************@d**********.com
Preparer Telephone 704-731-4680
Authorizer Name F***** B****
Authorizer Title Pipeline Safety Manager
Authorizer Telephone 704-731-4618
Authorizer Email F***********@d**********.com
Narrative During a site visit to inspect newly installed station restoration, a gas odor was detected near the valve setting. Water was present around the base of the valve due to previous weather and bubbles were noticed at ground level. Leak was deemed not fixable by normal means (greasing) so valve was replaced. Due to the nature of the leak, the volume of gas loss was small but could not be determined.

All rights reserved. Copyright © by ClearPHMSA