GTG incident on 2022-01-27 — TX
Operator
Atmos Pipeline - Texas
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$298,701
Incident datetime
2022-01-27 02:34
Report number
Location
TX
Narrative
On january 27, 2022, at approximately 1:06 am, a passerby made an emergency report that a vehicle had damaged natural gas facilities near 8514 east parmer lane. The natural gas facilities at this location are primarily owned and operated by texas gas service (tgs), and tgs representatives were on the scene. Atmos service technician arrived at 2:34 am, verified that the gas was shut off, and requested that a measurement, instrument, and controls (mic)technician be dispatched to the scene as well. The mic technician was immediately dispatched. Tgs handled the removal of the vehicle and temporary fencing. Atmos energy was onsite, standing by. Preliminarily, it appeared that the property damage was nearly entirely damage to the facilities of tgs rather than the facilities of atmos energy. However, during the course of the emergency response, at approximately 9:30 am cst, atmos energy determined there may be sufficient damage to atmos energy's property to exceed the cost threshold established in 49 cfr 191.3. Therefore, atmos energy reported the event to nrc at 10:07 am cst. A clamp-on ultrasonic meter was installed and temporary repairs were made to be able to place station back in service. Service from atmos energy to tgs was restored on february 3, 2022, at 5:45 pm.
Detailed record list
Report Received Date
2022-02-25 00:00:00
Iyear
2022
Report Number
20220020
Supplemental Number
37101
Report Type
Supplemental Final
Operator Id
31978
Name
Atmos Pipeline - Texas
Operator Street Address
5420 Lbj Freeway, Suite 1500
Operator City Name
Dallas
Operator State Abbreviation
TX
Operator Postal Code
75240
Local Datetime
2022-01-27 00:25:00
Time Zone
Central
Daylight Savings Ind
No
Location Latitude
30.35107558
Location Longitude
-97.58859103
Nrc Rpt Num
1327416
Nrc Rpt Datetime
2022-01-27 10:07:00
Additional Nrc Report Numbers
1327538
Commodity Released Type
Natural Gas
Unintentional Release
35.03
Intentional Release
0
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Normal Operation, Includes Pauses During Maintenance
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2022-01-27 02:34:00
Restart Datetime
2022-02-03 17:45:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-01-27 02:34:00
Ignite Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2022-01-27 02:34:00
On Site Datetime
2022-01-27 02:34:00
On Off Shore
Onshore
Onshore State Abbreviation
Tx
Onshore Postal Code
78653
Onshore City Name
Manor
Onshore County Name
Travis
Designated Location
Survey Station No.
Designated Name
36+53
Pipe Fac Name
P-20
Segment Name
P-20
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
System Part Involved
Onshore Regulator/metering Station Equipment And Piping
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
8.625
Puddle Weld Ind
No
Pipe Wall Thickness
0.322
Pipe Smys
52000
Pipe Specification
Api 5l
Pipe Seam Type
Longitudinal Erw - High Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Paint
Coating Applied Ind
Yes
Installation Year
2015
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
3rd Party Vehicle Damage On Above-Ground Piping
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
166
Heat Damage Ind
No
Non Heat Damage Ind
No
Hca Fatalities Ind
No
Did Occur In Mca Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
276
Est Cost Intentional Release
0
Est Cost Prop Damage
298701
Est Cost Emergency
828
Est Cost Other
0
Gas Cost In Mcf
7.874
Prpty
299805
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
699
Gas Flow In Pipe In Mcf
1120.8
Mop Psig
778
Mop Cfr Section
192.619(A)(2)
Maop Established Date
2015-09-28 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
Yes
Gas Odorized Ind
Yes
Pipeline Function
Transmission System
Scada In Place Ind
No
Accident Identifier
Notification From Public
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Outside Force Type
Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Vehicle Subtype
Third Party
Driver Issued Citation Ind
Unknown
Driver In Control Ind
Yes
Estimated Speed Unknown Ind
Yes
Vehicle Type
Small Truck
Vehicle Travel From
Roadway
Vehicle Travel Distance Ft
50
Protections Installed Ind
Yes
Protection Barricades Ind
Yes
Preparer Name
D*** G*******
Preparer Title
Supervisor Compliance
Preparer Email
D************@a**********.com
Preparer Telephone
512-310-3841
Local Contact Name
D*** G*******
Local Contact Email
D************@a**********.com
Local Contact Telephone
512-310-3841
Authorizer Name
M**** S*****
Authorizer Title
Vp Technical Services
Authorizer Telephone
214-206-2033
Authorizer Email
M***********@a**********.com
Narrative
On january 27, 2022, at approximately 1:06 am, a passerby made an emergency report that a vehicle had damaged natural gas facilities near 8514 east parmer lane. The natural gas facilities at this location are primarily owned and operated by texas gas service (tgs), and tgs representatives were on the scene. Atmos service technician arrived at 2:34 am, verified that the gas was shut off, and requested that a measurement, instrument, and controls (mic)technician be dispatched to the scene as well. The mic technician was immediately dispatched. Tgs handled the removal of the vehicle and temporary fencing. Atmos energy was onsite, standing by. Preliminarily, it appeared that the property damage was nearly entirely damage to the facilities of tgs rather than the facilities of atmos energy. However, during the course of the emergency response, at approximately 9:30 am cst, atmos energy determined there may be sufficient damage to atmos energy's property to exceed the cost threshold established in 49 cfr 191.3. Therefore, atmos energy reported the event to nrc at 10:07 am cst. A clamp-on ultrasonic meter was installed and temporary repairs were made to be able to place station back in service. Service from atmos energy to tgs was restored on february 3, 2022, at 5:45 pm.
| Report Received Date | 2022-02-25 00:00:00 |
|---|---|
| Iyear | 2022 |
| Report Number | 20220020 |
| Supplemental Number | 37101 |
| Report Type | Supplemental Final |
| Operator Id | 31978 PHMSA Enforcement |
| Name | Atmos Pipeline - Texas |
| Operator Street Address | 5420 Lbj Freeway, Suite 1500 |
| Operator City Name | Dallas |
| Operator State Abbreviation | TX |
| Operator Postal Code | 75240 |
| Local Datetime | 2022-01-27 00:25:00 |
| Time Zone | Central |
| Daylight Savings Ind | No |
| Location Latitude | 30.35107558 Google Maps OpenStreetMap |
| Location Longitude | -97.58859103 Google Maps OpenStreetMap |
| Nrc Rpt Num | 1327416 NRC Report How to search |
| Nrc Rpt Datetime | 2022-01-27 10:07:00 |
| Additional Nrc Report Numbers | 1327538 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 35.03 |
| Intentional Release | 0 |
| Accompanying Liquid | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Status When Identified | Normal Operation, Includes Pauses During Maintenance |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2022-01-27 02:34:00 |
| Restart Datetime | 2022-02-03 17:45:00 |
| Communication State Fed Ind | Yes |
| Party Initiated Communication | Operator |
| Initial Responder Com Datetime | 2022-01-27 02:34:00 |
| Ignite Ind | No |
| Num Pub Evacuated | 0 |
| Incident Identified Datetime | 2022-01-27 02:34:00 |
| On Site Datetime | 2022-01-27 02:34:00 |
| On Off Shore | Onshore |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 78653 |
| Onshore City Name | Manor |
| Onshore County Name | Travis |
| Designated Location | Survey Station No. |
| Designated Name | 36+53 |
| Pipe Fac Name | P-20 |
| Segment Name | P-20 |
| Federal | No |
| Location Type | Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| System Part Involved | Onshore Regulator/metering Station Equipment And Piping |
| Item Involved | Pipe |
| Pipe Type | Pipe Body |
| Pipe Diameter | 8.625 |
| Puddle Weld Ind | No |
| Pipe Wall Thickness | 0.322 |
| Pipe Smys | 52000 |
| Pipe Specification | Api 5l |
| Pipe Seam Type | Longitudinal Erw - High Frequency |
| Pipe Manufacturer | Unknown |
| Pipe Coating Type | Paint |
| Coating Applied Ind | Yes |
| Installation Year | 2015 |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Other |
| Release Type Details | 3rd Party Vehicle Damage On Above-Ground Piping |
| Class Location Type | Class 1 Location |
| Could Be Hca | No |
| Pir Radius | 166 |
| Heat Damage Ind | No |
| Non Heat Damage Ind | No |
| Hca Fatalities Ind | No |
| Did Occur In Mca Ind | No |
| Est Cost Oper Paid | 0 |
| Est Cost Unintentional Release | 276 |
| Est Cost Intentional Release | 0 |
| Est Cost Prop Damage | 298701 |
| Est Cost Emergency | 828 |
| Est Cost Other | 0 |
| Gas Cost In Mcf | 7.874 |
| Prpty | 299805 |
| Num Persons Hosp Not Ovnght | 0 |
| Num Injured Treated By Emt | 0 |
| Num Resident Building Affctd | 0 |
| Num Business Building Affctd | 0 |
| Wildlife Impact Ind | No |
| Accident Psig | 699 |
| Gas Flow In Pipe In Mcf | 1120.8 |
| Mop Psig | 778 |
| Mop Cfr Section | 192.619(A)(2) View CFR 49 §192 |
| Maop Established Date | 2015-09-28 00:00:00 |
| Maop Reversal Flow Ind | No |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Pressure Restriction Ind | No |
| Gas Required Odorized Ind | Yes |
| Gas Odorized Ind | Yes |
| Pipeline Function | Transmission System |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Public |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Other Outside Force Damage |
| Cause Details | Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation |
| Outside Force Type | Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation |
| Vehicle Subtype | Third Party |
| Driver Issued Citation Ind | Unknown |
| Driver In Control Ind | Yes |
| Estimated Speed Unknown Ind | Yes |
| Vehicle Type | Small Truck |
| Vehicle Travel From | Roadway |
| Vehicle Travel Distance Ft | 50 |
| Protections Installed Ind | Yes |
| Protection Barricades Ind | Yes |
| Preparer Name | D*** G******* |
| Preparer Title | Supervisor Compliance |
| Preparer Email | D************@a**********.com |
| Preparer Telephone | 512-310-3841 |
| Local Contact Name | D*** G******* |
| Local Contact Email | D************@a**********.com |
| Local Contact Telephone | 512-310-3841 |
| Authorizer Name | M**** S***** |
| Authorizer Title | Vp Technical Services |
| Authorizer Telephone | 214-206-2033 |
| Authorizer Email | M***********@a**********.com |
| Narrative | On january 27, 2022, at approximately 1:06 am, a passerby made an emergency report that a vehicle had damaged natural gas facilities near 8514 east parmer lane. The natural gas facilities at this location are primarily owned and operated by texas gas service (tgs), and tgs representatives were on the scene. Atmos service technician arrived at 2:34 am, verified that the gas was shut off, and requested that a measurement, instrument, and controls (mic)technician be dispatched to the scene as well. The mic technician was immediately dispatched. Tgs handled the removal of the vehicle and temporary fencing. Atmos energy was onsite, standing by. Preliminarily, it appeared that the property damage was nearly entirely damage to the facilities of tgs rather than the facilities of atmos energy. However, during the course of the emergency response, at approximately 9:30 am cst, atmos energy determined there may be sufficient damage to atmos energy's property to exceed the cost threshold established in 49 cfr 191.3. Therefore, atmos energy reported the event to nrc at 10:07 am cst. A clamp-on ultrasonic meter was installed and temporary repairs were made to be able to place station back in service. Service from atmos energy to tgs was restored on february 3, 2022, at 5:45 pm. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA