Operator, cause, commodity and consequences with raw source fields.
GD incident on 2022-01-27 — TX
Operator
Texas Gas Service Company, A Division Of One Gas, Inc.
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$250,000
Incident datetime
2022-01-27 01:30
Report number
Location
TX, TRAVIS
Narrative
Third-party vehicle ran off the roadway traveling westbound on east parmer lane at a high speed and crashed through fencing, concrete-filled steel bollard posts with welded steel crossbars, and the texas gas service (tgs) regulator station at subject location before damaging and coming to rest against atmos energy's metering station, which feeds tgs's station and distribution system. The vehicle's impact caused the piping to separate, leading to an unintentional release of gas from the inlet and outlet sides of tgs's regulator station. After damaging the atmos energy metering station, the vehicle came to rest on top of the atmos energy piping. Atmos energy's measurement instrumentation was damaged and could not provide a volume of gas that flowed through the station during and after the incident. Tgs has no knowledge of the damage estimates for atmos facilities or the vehicle at fault for the incident.
Detailed record list
Occurred At
2022-01-27 01:30:00
Year
2022
Report Received Date
2022-02-25 00:00:00
Iyear
2022.0
Report Number
20220017.0
Supplemental Number
36393.0
Report Type
Original Final
Operator Id
18532
Name
Texas Gas Service Company, A Division Of One Gas, Inc.
Operator Street Address
1301 Mopac Expressway Suite 400
Operator City Name
Austin
Operator State Abbreviation
TX
Operator Postal Code
78746
Local Datetime
2022-01-27 08:10:00
Time Zone
Central
Daylight Savings Ind
No
Location Street Address
8500 E Parmer Lane
Location City Name
Manor
Location County Name
Travis
Location State Abbreviation
TX
Location Postal Code
78653
Location Latitude
30.35105
Location Longitude
-97.58847
Flow Cont Key Crit Ind
Yes
Nrc Rpt Datetime
2022-01-27 08:32:00
Nrc Rpt Num
1327404
Additional Nrc Report Numbers
1327531
Commodity Released Type
Natural Gas
Unintentional Release
25858.0
Intentional Release
0.71
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2022-01-27 01:30:00
Communication State Fed Ind
Yes
Party Initiated Communication
Local/state/federal Emergency Responder
Initial Responder Com Datetime
2022-01-27 00:42:00
On Site Datetime
2022-01-27 01:30:00
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set)
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
District Regulator/metering Station
Installation Year
2016.0
Manufactured Year
2015.0
Material Involved
Steel
Steel Seam Type
Longitudinal Erw - High Frequency
Wt Steel
0.237
Release Type
Other
Release Type Details
Third Party Vehicle Struck Above Ground Station Piping And Sheered Fabrication At 2 Circumferential Welds Between Pipe And Reducers.
Class Location Type
Class 1 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
250000.0
Est Cost Emergency
1115.0
Est Cost Other
0.0
Gas Cost In Mcf
5.78
Est Cost Unintentional Release
149459.0
Est Cost Intentional Release
4.0
Prpty
400578.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Num Persons Hosp Not Ovnght
1.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
0.0
Num Business Building Affctd
0.0
Accident Psig
707.0
Normal Psig
707.0
Mop Psig
778.0
Mop Cfr Section
192.621 M
Maop Established Date
2016-01-11 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Odorized By Others
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Damage to the regulator station by third-party vehicle initiated scada alarms in control room. Controller followed procedures to investigate alarms.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Outside Force Type
Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Vehicle Subtype
Third Party
Driver Issued Citation Ind
Unknown
Driver In Control Ind
Unknown
Estimated Speed
Unknown
Vehicle Type
Small Truck
Vehicle Travel From
Roadway
Vehicle Travel Distance Ft
60
Protections Installed Ind
Yes
Protection Barricades Ind
Yes
Osf Vehicle Ind
Yes
Preparer Name
A** M***
Preparer Title
Regulatory Compliance Specialist
Preparer Email
A*******@o*****.com
Preparer Telephone
512-407-1571
Local Contact Name
B**** W****
Local Contact Email
B**********@o*****.com
Local Contact Telephone
512-407-1529
Authorizer Name
B**** W****
Authorizer Title
Director Of Engineering
Authorizer Telephone
512-407-1529
Authorizer Email
B**********@o*****.com
Narrative
Third-party vehicle ran off the roadway traveling westbound on east parmer lane at a high speed and crashed through fencing, concrete-filled steel bollard posts with welded steel crossbars, and the texas gas service (tgs) regulator station at subject location before damaging and coming to rest against atmos energy's metering station, which feeds tgs's station and distribution system. The vehicle's impact caused the piping to separate, leading to an unintentional release of gas from the inlet and outlet sides of tgs's regulator station. After damaging the atmos energy metering station, the vehicle came to rest on top of the atmos energy piping. Atmos energy's measurement instrumentation was damaged and could not provide a volume of gas that flowed through the station during and after the incident. Tgs has no knowledge of the damage estimates for atmos facilities or the vehicle at fault for the incident.
| Occurred At | 2022-01-27 01:30:00 |
|---|---|
| Year | 2022 |
| Report Received Date | 2022-02-25 00:00:00 |
| Iyear | 2022.0 |
| Report Number | 20220017.0 |
| Supplemental Number | 36393.0 |
| Report Type | Original Final |
| Operator Id | 18532 PHMSA Enforcement |
| Name | Texas Gas Service Company, A Division Of One Gas, Inc. |
| Operator Street Address | 1301 Mopac Expressway Suite 400 |
| Operator City Name | Austin |
| Operator State Abbreviation | TX |
| Operator Postal Code | 78746 |
| Local Datetime | 2022-01-27 08:10:00 |
| Time Zone | Central |
| Daylight Savings Ind | No |
| Location Street Address | 8500 E Parmer Lane |
| Location City Name | Manor |
| Location County Name | Travis |
| Location State Abbreviation | TX |
| Location Postal Code | 78653 |
| Location Latitude | 30.35105 Google Maps OpenStreetMap |
| Location Longitude | -97.58847 Google Maps OpenStreetMap |
| Flow Cont Key Crit Ind | Yes |
| Nrc Rpt Datetime | 2022-01-27 08:32:00 |
| Nrc Rpt Num | 1327404 NRC Report How to search |
| Additional Nrc Report Numbers | 1327531 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 25858.0 |
| Intentional Release | 0.71 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2022-01-27 01:30:00 |
| Communication State Fed Ind | Yes |
| Party Initiated Communication | Local/state/federal Emergency Responder |
| Initial Responder Com Datetime | 2022-01-27 00:42:00 |
| On Site Datetime | 2022-01-27 01:30:00 |
| Federal | No |
| Location Type | Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set) |
| Crossing | No |
| Pipe Facility Type | Investor Owned |
| System Part Involved | District Regulator/metering Station |
| Installation Year | 2016.0 |
| Manufactured Year | 2015.0 |
| Material Involved | Steel |
| Steel Seam Type | Longitudinal Erw - High Frequency |
| Wt Steel | 0.237 |
| Release Type | Other |
| Release Type Details | Third Party Vehicle Struck Above Ground Station Piping And Sheered Fabrication At 2 Circumferential Welds Between Pipe And Reducers. |
| Class Location Type | Class 1 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 250000.0 |
| Est Cost Emergency | 1115.0 |
| Est Cost Other | 0.0 |
| Gas Cost In Mcf | 5.78 |
| Est Cost Unintentional Release | 149459.0 |
| Est Cost Intentional Release | 4.0 |
| Prpty | 400578.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 0.0 |
| Num Persons Hosp Not Ovnght | 1.0 |
| Num Injured Treated By Emt | 0.0 |
| Num Resident Building Affctd | 0.0 |
| Num Business Building Affctd | 0.0 |
| Accident Psig | 707.0 |
| Normal Psig | 707.0 |
| Mop Psig | 778.0 |
| Mop Cfr Section | 192.621 M View CFR 49 §192 |
| Maop Established Date | 2016-01-11 00:00:00 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Gas Odorized System Type | Odorized By Others |
| Gas Odorized Lvl Not Msrd Ind | Yes |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Accident Identifier | Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations) |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Damage to the regulator station by third-party vehicle initiated scada alarms in control room. Controller followed procedures to investigate alarms. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Other Outside Force Damage |
| Cause Details | Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation |
| Outside Force Type | Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation |
| Vehicle Subtype | Third Party |
| Driver Issued Citation Ind | Unknown |
| Driver In Control Ind | Unknown |
| Estimated Speed | Unknown |
| Vehicle Type | Small Truck |
| Vehicle Travel From | Roadway |
| Vehicle Travel Distance Ft | 60 |
| Protections Installed Ind | Yes |
| Protection Barricades Ind | Yes |
| Osf Vehicle Ind | Yes |
| Preparer Name | A** M*** |
| Preparer Title | Regulatory Compliance Specialist |
| Preparer Email | A*******@o*****.com |
| Preparer Telephone | 512-407-1571 |
| Local Contact Name | B**** W**** |
| Local Contact Email | B**********@o*****.com |
| Local Contact Telephone | 512-407-1529 |
| Authorizer Name | B**** W**** |
| Authorizer Title | Director Of Engineering |
| Authorizer Telephone | 512-407-1529 |
| Authorizer Email | B**********@o*****.com |
| Narrative | Third-party vehicle ran off the roadway traveling westbound on east parmer lane at a high speed and crashed through fencing, concrete-filled steel bollard posts with welded steel crossbars, and the texas gas service (tgs) regulator station at subject location before damaging and coming to rest against atmos energy's metering station, which feeds tgs's station and distribution system. The vehicle's impact caused the piping to separate, leading to an unintentional release of gas from the inlet and outlet sides of tgs's regulator station. After damaging the atmos energy metering station, the vehicle came to rest on top of the atmos energy piping. Atmos energy's measurement instrumentation was damaged and could not provide a volume of gas that flowed through the station during and after the incident. Tgs has no knowledge of the damage estimates for atmos facilities or the vehicle at fault for the incident. |