GD incident on 2022-01-27 — TX

Operator
Texas Gas Service Company, A Division Of One Gas, Inc.
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$250,000
Incident datetime
2022-01-27 01:30
Report number
Location
TX, TRAVIS
Narrative
Third-party vehicle ran off the roadway traveling westbound on east parmer lane at a high speed and crashed through fencing, concrete-filled steel bollard posts with welded steel crossbars, and the texas gas service (tgs) regulator station at subject location before damaging and coming to rest against atmos energy's metering station, which feeds tgs's station and distribution system. The vehicle's impact caused the piping to separate, leading to an unintentional release of gas from the inlet and outlet sides of tgs's regulator station. After damaging the atmos energy metering station, the vehicle came to rest on top of the atmos energy piping. Atmos energy's measurement instrumentation was damaged and could not provide a volume of gas that flowed through the station during and after the incident. Tgs has no knowledge of the damage estimates for atmos facilities or the vehicle at fault for the incident.
Detailed record list
Occurred At
2022-01-27 01:30:00
Year
2022
Report Received Date
2022-02-25 00:00:00
Iyear
2022.0
Report Number
20220017.0
Supplemental Number
36393.0
Report Type
Original Final
Operator Id
Name
Texas Gas Service Company, A Division Of One Gas, Inc.
Operator Street Address
1301 Mopac Expressway Suite 400
Operator City Name
Austin
Operator State Abbreviation
TX
Operator Postal Code
78746
Local Datetime
2022-01-27 08:10:00
Time Zone
Central
Daylight Savings Ind
No
Location Street Address
8500 E Parmer Lane
Location City Name
Manor
Location County Name
Travis
Location State Abbreviation
TX
Location Postal Code
78653
Location Latitude
Location Longitude
Flow Cont Key Crit Ind
Yes
Nrc Rpt Datetime
2022-01-27 08:32:00
Nrc Rpt Num
Additional Nrc Report Numbers
1327531
Commodity Released Type
Natural Gas
Unintentional Release
25858.0
Intentional Release
0.71
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2022-01-27 01:30:00
Communication State Fed Ind
Yes
Party Initiated Communication
Local/state/federal Emergency Responder
Initial Responder Com Datetime
2022-01-27 00:42:00
On Site Datetime
2022-01-27 01:30:00
Federal
No
Location Type
Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set)
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
District Regulator/metering Station
Installation Year
2016.0
Manufactured Year
2015.0
Material Involved
Steel
Steel Seam Type
Longitudinal Erw - High Frequency
Wt Steel
0.237
Release Type
Other
Release Type Details
Third Party Vehicle Struck Above Ground Station Piping And Sheered Fabrication At 2 Circumferential Welds Between Pipe And Reducers.
Class Location Type
Class 1 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
250000.0
Est Cost Emergency
1115.0
Est Cost Other
0.0
Gas Cost In Mcf
5.78
Est Cost Unintentional Release
149459.0
Est Cost Intentional Release
4.0
Prpty
400578.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Num Persons Hosp Not Ovnght
1.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
0.0
Num Business Building Affctd
0.0
Accident Psig
707.0
Normal Psig
707.0
Mop Psig
778.0
Mop Cfr Section
Maop Established Date
2016-01-11 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Odorized By Others
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Damage to the regulator station by third-party vehicle initiated scada alarms in control room. Controller followed procedures to investigate alarms.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Outside Force Type
Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Vehicle Subtype
Third Party
Driver Issued Citation Ind
Unknown
Driver In Control Ind
Unknown
Estimated Speed
Unknown
Vehicle Type
Small Truck
Vehicle Travel From
Roadway
Vehicle Travel Distance Ft
60
Protections Installed Ind
Yes
Protection Barricades Ind
Yes
Osf Vehicle Ind
Yes
Preparer Name
A** M***
Preparer Title
Regulatory Compliance Specialist
Preparer Email
A*******@o*****.com
Preparer Telephone
512-407-1571
Local Contact Name
B**** W****
Local Contact Email
B**********@o*****.com
Local Contact Telephone
512-407-1529
Authorizer Name
B**** W****
Authorizer Title
Director Of Engineering
Authorizer Telephone
512-407-1529
Authorizer Email
B**********@o*****.com
Narrative
Third-party vehicle ran off the roadway traveling westbound on east parmer lane at a high speed and crashed through fencing, concrete-filled steel bollard posts with welded steel crossbars, and the texas gas service (tgs) regulator station at subject location before damaging and coming to rest against atmos energy's metering station, which feeds tgs's station and distribution system. The vehicle's impact caused the piping to separate, leading to an unintentional release of gas from the inlet and outlet sides of tgs's regulator station. After damaging the atmos energy metering station, the vehicle came to rest on top of the atmos energy piping. Atmos energy's measurement instrumentation was damaged and could not provide a volume of gas that flowed through the station during and after the incident. Tgs has no knowledge of the damage estimates for atmos facilities or the vehicle at fault for the incident.
Occurred At 2022-01-27 01:30:00
Year 2022
Report Received Date 2022-02-25 00:00:00
Iyear 2022.0
Report Number 20220017.0
Supplemental Number 36393.0
Report Type Original Final
Operator Id 18532 PHMSA Enforcement
Name Texas Gas Service Company, A Division Of One Gas, Inc.
Operator Street Address 1301 Mopac Expressway Suite 400
Operator City Name Austin
Operator State Abbreviation TX
Operator Postal Code 78746
Local Datetime 2022-01-27 08:10:00
Time Zone Central
Daylight Savings Ind No
Location Street Address 8500 E Parmer Lane
Location City Name Manor
Location County Name Travis
Location State Abbreviation TX
Location Postal Code 78653
Location Latitude 30.35105 Google Maps OpenStreetMap
Location Longitude -97.58847 Google Maps OpenStreetMap
Flow Cont Key Crit Ind Yes
Nrc Rpt Datetime 2022-01-27 08:32:00
Nrc Rpt Num 1327404 NRC Report How to search
Additional Nrc Report Numbers 1327531
Commodity Released Type Natural Gas
Unintentional Release 25858.0
Intentional Release 0.71
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind No
Num Pub Evacuated 0.0
Incident Identified Datetime 2022-01-27 01:30:00
Communication State Fed Ind Yes
Party Initiated Communication Local/state/federal Emergency Responder
Initial Responder Com Datetime 2022-01-27 00:42:00
On Site Datetime 2022-01-27 01:30:00
Federal No
Location Type Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set)
Crossing No
Pipe Facility Type Investor Owned
System Part Involved District Regulator/metering Station
Installation Year 2016.0
Manufactured Year 2015.0
Material Involved Steel
Steel Seam Type Longitudinal Erw - High Frequency
Wt Steel 0.237
Release Type Other
Release Type Details Third Party Vehicle Struck Above Ground Station Piping And Sheered Fabrication At 2 Circumferential Welds Between Pipe And Reducers.
Class Location Type Class 1 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 250000.0
Est Cost Emergency 1115.0
Est Cost Other 0.0
Gas Cost In Mcf 5.78
Est Cost Unintentional Release 149459.0
Est Cost Intentional Release 4.0
Prpty 400578.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 0.0
Num Persons Hosp Not Ovnght 1.0
Num Injured Treated By Emt 0.0
Num Resident Building Affctd 0.0
Num Business Building Affctd 0.0
Accident Psig 707.0
Normal Psig 707.0
Mop Psig 778.0
Mop Cfr Section 192.621 M View CFR 49 §192
Maop Established Date 2016-01-11 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type Odorized By Others
Gas Odorized Lvl Not Msrd Ind Yes
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Accident Identifier Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Or Pack Calculations)
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Damage to the regulator station by third-party vehicle initiated scada alarms in control room. Controller followed procedures to investigate alarms.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Outside Force Damage
Cause Details Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Outside Force Type Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Vehicle Subtype Third Party
Driver Issued Citation Ind Unknown
Driver In Control Ind Unknown
Estimated Speed Unknown
Vehicle Type Small Truck
Vehicle Travel From Roadway
Vehicle Travel Distance Ft 60
Protections Installed Ind Yes
Protection Barricades Ind Yes
Osf Vehicle Ind Yes
Preparer Name A** M***
Preparer Title Regulatory Compliance Specialist
Preparer Email A*******@o*****.com
Preparer Telephone 512-407-1571
Local Contact Name B**** W****
Local Contact Email B**********@o*****.com
Local Contact Telephone 512-407-1529
Authorizer Name B**** W****
Authorizer Title Director Of Engineering
Authorizer Telephone 512-407-1529
Authorizer Email B**********@o*****.com
Narrative Third-party vehicle ran off the roadway traveling westbound on east parmer lane at a high speed and crashed through fencing, concrete-filled steel bollard posts with welded steel crossbars, and the texas gas service (tgs) regulator station at subject location before damaging and coming to rest against atmos energy's metering station, which feeds tgs's station and distribution system. The vehicle's impact caused the piping to separate, leading to an unintentional release of gas from the inlet and outlet sides of tgs's regulator station. After damaging the atmos energy metering station, the vehicle came to rest on top of the atmos energy piping. Atmos energy's measurement instrumentation was damaged and could not provide a volume of gas that flowed through the station during and after the incident. Tgs has no knowledge of the damage estimates for atmos facilities or the vehicle at fault for the incident.