GD incident on 2022-01-24 — HI
Operator
Hawaii Gas
Cause
Locating Issue
Commodity
Synthetic Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$25,000
Incident datetime
2022-01-24 09:02
Report number
Location
HI, HONOLULU
Narrative
Incident summary on monday, january 24, 2022, frank coluccio construction ("fcc") was performing a sewer installation on a portion of waiakamilo road in honolulu, hawaii, with an auger. At approximately 9:02 a.M., on the portion of waiakamilo road between hart street and kalani street, the auger struck a hawai'I gas ("hg") underground 8-inch pipeline ("subject segment"). The auger caused an approximately 3-inch long fracture along the top of the pipeline. The subject segment began to leak gas. Hg's first responder arrived on site at approximately 9:15 a.M. And confirmed the damage to the subject segment. Due to the magnitude of the leak, hg called the honolulu fire department ("hfd") at approximately 10:19 a.M. To assist in securing the roadway and to help monitor the hot zone. Hg's maintenance crew arrived on site at approximately 10:30 a.M. And began assessing repairs. At approximately 11:15 a.M., hfd began evacuating nearby commercial buildings. Hg was able to stop the flow of gas to the subject segment at approximately 5:35 p.M., january 24, 2022. Final repairs were completed at approximately 11:00 p.M., january 24, 2022. Hawai'I gas involvement prior to incident hg installed the subject segment in 1940. The subject segment is an 8-inch bare steel pipe. Hg maps and records contain no indication that the subject segment was repaired, altered or excavated since its installation. On monday, january 3, 2022, fcc submitted one call ticket number 22000022 to the hawaii one call center indicating that fcc would be excavating "on waiakamilo road between dillingham boulevard and hart street (ewa side of road)" ("excavation area"). In response to ticket no. 22000022, hg reviewed gis maps of the excavation area and determined that an underground main line was located within that area. On january 10, 2022, hg personnel attempted to perform toning on the underground main line in the excavation area but noted that the location of the underground main line had already been marked by another party in yellow paint. Please contact hg for additional narrative detail. Also, please note that this investigation is still ongoing. Update 6/10/2022 upon completion of the investigation by hg, it was determined that toning of the subject segment was performed inadequately by hg. As indicated in the "incident summary" section above, the underground main line had already been marked by another party in yellow paint and hg failed to confirm the markings were correct when responding to ticket no. 22000022. As a result of the investigation, hg has incorporated the following mitigative actions into its toning operations as of may 2022: 1. Revise "hg one call pipe location guidelines" document. A. All painted utility markings by hg will have a unique hg identifier. B. All existing utility markings (whether by hg or 3rd party) shall be reverified in response to an 811 ticket. 2. Update training requirements for all hg employees who conduct utility locations. A. Initial training requirements (oq & "hg one call pipe location guidelines" document review). B. Refresher training requirements (pipe location refresher training to be provided in 2022 and every 3 years after or when probable cause is determined by hg management). C. Documentation retention requirements. Hg is confident the mitigative actions listed above will help to further reduce toning related incidents going forward. Please contact hg for additional narrative detail.
Detailed record list
Occurred At
2022-01-24 09:02:00
Year
2022
Report Received Date
2022-02-23 00:00:00
Iyear
2022.0
Report Number
20220015.0
Supplemental Number
36773.0
Report Type
Supplemental Final
Operator Id
6243
Name
Hawaii Gas
Operator Street Address
515 Kamakee Street (P.o. Box 3000)
Operator City Name
Honolulu
Operator State Abbreviation
HI
Operator Postal Code
96802-3000
Local Datetime
2022-01-24 11:15:00
Time Zone
Hawaii-Aleutian
Daylight Savings Ind
No
Location Street Address
Waiakamilo Road (Between Hart St & Kalani St)
Location City Name
Honolulu
Location County Name
Honolulu
Location State Abbreviation
HI
Location Postal Code
96817
Location Latitude
21.32236
Location Longitude
-157.878238
Flow Cont Key Crit Ind
Yes
Nrc Rpt Datetime
2022-01-24 12:30:00
Nrc Rpt Num
1327229
Additional Nrc Report Numbers
1327369 And 1327376
Commodity Released Type
Synthetic Gas
Unintentional Release
550.0
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Num Pub Evacuated
100.0
Incident Identified Datetime
2022-01-24 09:02:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2022-01-24 10:19:00
On Site Datetime
2022-01-24 09:15:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
48.0
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Main
Installation Year
1940.0
Pipe Diameter
8.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Wt Steel
0.625
Release Type
Mechanical Puncture
Puncture Axial
3.0
Puncture Circum
1.0
Class Location Type
Class 4 Location
Est Cost Oper Paid
100000.0
Est Cost Prop Damage
25000.0
Est Cost Emergency
20000.0
Est Cost Other
0.0
Gas Cost In Mcf
46.67
Est Cost Unintentional Release
25669.0
Est Cost Intentional Release
0.0
Prpty
170669.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
0.0
Num Business Building Affctd
5.0
Accident Psig
31.0
Normal Psig
33.0
Mop Psig
50.0
Mop Cfr Section
192.619(C)
Maop Established Date
1999-03-31 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
No
Accident Identifier
Notification From Third Party That Caused The Incident
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind
Yes
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
Yes
One Call System Ind
Yes
State Law Exempt Ind
No
Notify Cga Dirt
Yes
Public Row Ind
Yes
Public Subtype
City Street
Excavator Type
Contractor
Excavator Equipment
Auger
Work Performed
Sewer (Sanitary/storm)
One Call Notified Ind
Yes
One Call Ticket Num
22000022
Locator Type
Unknown/other
Visible Marks
Yes
Service Interruption
No
Root Cause Category
Locating Issue
Root Cause Type
Facility Not Marked Due To Incomplete Marks At Damage Location
Io Inadequate Procedure Ind
Yes
Preparer Name
C********** H***
Preparer Title
Imp Engineer
Preparer Email
C****@h********.com
Preparer Telephone
808-594-5553
Local Contact Name
C**** H***
Local Contact Email
C****@h********.com
Local Contact Telephone
808-594-5553
Authorizer Name
K**** N********
Authorizer Title
Vice President Operations
Authorizer Telephone
808-594-5573
Authorizer Email
K*******@h********.com
Narrative
Incident summary on monday, january 24, 2022, frank coluccio construction ("fcc") was performing a sewer installation on a portion of waiakamilo road in honolulu, hawaii, with an auger. At approximately 9:02 a.M., on the portion of waiakamilo road between hart street and kalani street, the auger struck a hawai'I gas ("hg") underground 8-inch pipeline ("subject segment"). The auger caused an approximately 3-inch long fracture along the top of the pipeline. The subject segment began to leak gas. Hg's first responder arrived on site at approximately 9:15 a.M. And confirmed the damage to the subject segment. Due to the magnitude of the leak, hg called the honolulu fire department ("hfd") at approximately 10:19 a.M. To assist in securing the roadway and to help monitor the hot zone. Hg's maintenance crew arrived on site at approximately 10:30 a.M. And began assessing repairs. At approximately 11:15 a.M., hfd began evacuating nearby commercial buildings. Hg was able to stop the flow of gas to the subject segment at approximately 5:35 p.M., january 24, 2022. Final repairs were completed at approximately 11:00 p.M., january 24, 2022. Hawai'I gas involvement prior to incident hg installed the subject segment in 1940. The subject segment is an 8-inch bare steel pipe. Hg maps and records contain no indication that the subject segment was repaired, altered or excavated since its installation. On monday, january 3, 2022, fcc submitted one call ticket number 22000022 to the hawaii one call center indicating that fcc would be excavating "on waiakamilo road between dillingham boulevard and hart street (ewa side of road)" ("excavation area"). In response to ticket no. 22000022, hg reviewed gis maps of the excavation area and determined that an underground main line was located within that area. On january 10, 2022, hg personnel attempted to perform toning on the underground main line in the excavation area but noted that the location of the underground main line had already been marked by another party in yellow paint. Please contact hg for additional narrative detail. Also, please note that this investigation is still ongoing. Update 6/10/2022 upon completion of the investigation by hg, it was determined that toning of the subject segment was performed inadequately by hg. As indicated in the "incident summary" section above, the underground main line had already been marked by another party in yellow paint and hg failed to confirm the markings were correct when responding to ticket no. 22000022. As a result of the investigation, hg has incorporated the following mitigative actions into its toning operations as of may 2022: 1. Revise "hg one call pipe location guidelines" document. A. All painted utility markings by hg will have a unique hg identifier. B. All existing utility markings (whether by hg or 3rd party) shall be reverified in response to an 811 ticket. 2. Update training requirements for all hg employees who conduct utility locations. A. Initial training requirements (oq & "hg one call pipe location guidelines" document review). B. Refresher training requirements (pipe location refresher training to be provided in 2022 and every 3 years after or when probable cause is determined by hg management). C. Documentation retention requirements. Hg is confident the mitigative actions listed above will help to further reduce toning related incidents going forward. Please contact hg for additional narrative detail.
| Occurred At | 2022-01-24 09:02:00 |
|---|---|
| Year | 2022 |
| Report Received Date | 2022-02-23 00:00:00 |
| Iyear | 2022.0 |
| Report Number | 20220015.0 |
| Supplemental Number | 36773.0 |
| Report Type | Supplemental Final |
| Operator Id | 6243 PHMSA Enforcement |
| Name | Hawaii Gas |
| Operator Street Address | 515 Kamakee Street (P.o. Box 3000) |
| Operator City Name | Honolulu |
| Operator State Abbreviation | HI |
| Operator Postal Code | 96802-3000 |
| Local Datetime | 2022-01-24 11:15:00 |
| Time Zone | Hawaii-Aleutian |
| Daylight Savings Ind | No |
| Location Street Address | Waiakamilo Road (Between Hart St & Kalani St) |
| Location City Name | Honolulu |
| Location County Name | Honolulu |
| Location State Abbreviation | HI |
| Location Postal Code | 96817 |
| Location Latitude | 21.32236 Google Maps OpenStreetMap |
| Location Longitude | -157.878238 Google Maps OpenStreetMap |
| Flow Cont Key Crit Ind | Yes |
| Nrc Rpt Datetime | 2022-01-24 12:30:00 |
| Nrc Rpt Num | 1327229 NRC Report How to search |
| Additional Nrc Report Numbers | 1327369 And 1327376 |
| Commodity Released Type | Synthetic Gas |
| Unintentional Release | 550.0 |
| Intentional Release | 0.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | No |
| Num Pub Evacuated | 100.0 |
| Incident Identified Datetime | 2022-01-24 09:02:00 |
| Communication State Fed Ind | Yes |
| Party Initiated Communication | Operator |
| Initial Responder Com Datetime | 2022-01-24 10:19:00 |
| On Site Datetime | 2022-01-24 09:15:00 |
| Federal | No |
| Location Type | Public Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Pavement |
| Depth Of Cover | 48.0 |
| Other Underground Facilities | No |
| Crossing | No |
| Pipe Facility Type | Privately Owned |
| System Part Involved | Main |
| Installation Year | 1940.0 |
| Pipe Diameter | 8.0 |
| Pipe Specification | Unknown |
| Pipe Manufacturer | Unknown |
| Material Involved | Steel |
| Steel Seam Type | Other |
| Steel Seam Type Details | Unknown |
| Wt Steel | 0.625 |
| Release Type | Mechanical Puncture |
| Puncture Axial | 3.0 |
| Puncture Circum | 1.0 |
| Class Location Type | Class 4 Location |
| Est Cost Oper Paid | 100000.0 |
| Est Cost Prop Damage | 25000.0 |
| Est Cost Emergency | 20000.0 |
| Est Cost Other | 0.0 |
| Gas Cost In Mcf | 46.67 |
| Est Cost Unintentional Release | 25669.0 |
| Est Cost Intentional Release | 0.0 |
| Prpty | 170669.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 0.0 |
| Num Persons Hosp Not Ovnght | 0.0 |
| Num Injured Treated By Emt | 0.0 |
| Num Resident Building Affctd | 0.0 |
| Num Business Building Affctd | 5.0 |
| Accident Psig | 31.0 |
| Normal Psig | 33.0 |
| Mop Psig | 50.0 |
| Mop Cfr Section | 192.619(C) View CFR 49 §192 |
| Maop Established Date | 1999-03-31 00:00:00 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Gas Odorized System Type | Injection Pump |
| Gas Odorized Lvl Not Msrd Ind | Yes |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Third Party That Caused The Incident |
| Investigation Status | Yes, specify investigation result(s): (select all that apply) |
| Invest Schedule Ind | Yes |
| Invest No Control Room Ind | Yes |
| Invest No Controller Ind | Yes |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Excavation Damage |
| Cause Details | Excavation Damage By Third Party |
| Ex Party Type | Excavation Damage By Third Party |
| Prior Notification Ind | Yes |
| One Call System Ind | Yes |
| State Law Exempt Ind | No |
| Notify Cga Dirt | Yes |
| Public Row Ind | Yes |
| Public Subtype | City Street |
| Excavator Type | Contractor |
| Excavator Equipment | Auger |
| Work Performed | Sewer (Sanitary/storm) |
| One Call Notified Ind | Yes |
| One Call Ticket Num | 22000022 |
| Locator Type | Unknown/other |
| Visible Marks | Yes |
| Service Interruption | No |
| Root Cause Category | Locating Issue |
| Root Cause Type | Facility Not Marked Due To Incomplete Marks At Damage Location |
| Io Inadequate Procedure Ind | Yes |
| Preparer Name | C********** H*** |
| Preparer Title | Imp Engineer |
| Preparer Email | C****@h********.com |
| Preparer Telephone | 808-594-5553 |
| Local Contact Name | C**** H*** |
| Local Contact Email | C****@h********.com |
| Local Contact Telephone | 808-594-5553 |
| Authorizer Name | K**** N******** |
| Authorizer Title | Vice President Operations |
| Authorizer Telephone | 808-594-5573 |
| Authorizer Email | K*******@h********.com |
| Narrative | Incident summary on monday, january 24, 2022, frank coluccio construction ("fcc") was performing a sewer installation on a portion of waiakamilo road in honolulu, hawaii, with an auger. At approximately 9:02 a.M., on the portion of waiakamilo road between hart street and kalani street, the auger struck a hawai'I gas ("hg") underground 8-inch pipeline ("subject segment"). The auger caused an approximately 3-inch long fracture along the top of the pipeline. The subject segment began to leak gas. Hg's first responder arrived on site at approximately 9:15 a.M. And confirmed the damage to the subject segment. Due to the magnitude of the leak, hg called the honolulu fire department ("hfd") at approximately 10:19 a.M. To assist in securing the roadway and to help monitor the hot zone. Hg's maintenance crew arrived on site at approximately 10:30 a.M. And began assessing repairs. At approximately 11:15 a.M., hfd began evacuating nearby commercial buildings. Hg was able to stop the flow of gas to the subject segment at approximately 5:35 p.M., january 24, 2022. Final repairs were completed at approximately 11:00 p.M., january 24, 2022. Hawai'I gas involvement prior to incident hg installed the subject segment in 1940. The subject segment is an 8-inch bare steel pipe. Hg maps and records contain no indication that the subject segment was repaired, altered or excavated since its installation. On monday, january 3, 2022, fcc submitted one call ticket number 22000022 to the hawaii one call center indicating that fcc would be excavating "on waiakamilo road between dillingham boulevard and hart street (ewa side of road)" ("excavation area"). In response to ticket no. 22000022, hg reviewed gis maps of the excavation area and determined that an underground main line was located within that area. On january 10, 2022, hg personnel attempted to perform toning on the underground main line in the excavation area but noted that the location of the underground main line had already been marked by another party in yellow paint. Please contact hg for additional narrative detail. Also, please note that this investigation is still ongoing. Update 6/10/2022 upon completion of the investigation by hg, it was determined that toning of the subject segment was performed inadequately by hg. As indicated in the "incident summary" section above, the underground main line had already been marked by another party in yellow paint and hg failed to confirm the markings were correct when responding to ticket no. 22000022. As a result of the investigation, hg has incorporated the following mitigative actions into its toning operations as of may 2022: 1. Revise "hg one call pipe location guidelines" document. A. All painted utility markings by hg will have a unique hg identifier. B. All existing utility markings (whether by hg or 3rd party) shall be reverified in response to an 811 ticket. 2. Update training requirements for all hg employees who conduct utility locations. A. Initial training requirements (oq & "hg one call pipe location guidelines" document review). B. Refresher training requirements (pipe location refresher training to be provided in 2022 and every 3 years after or when probable cause is determined by hg management). C. Documentation retention requirements. Hg is confident the mitigative actions listed above will help to further reduce toning related incidents going forward. Please contact hg for additional narrative detail. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA