HL incident on 2021-11-04 — TX

Operator
Plains Pipeline, L.p.
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$10,009
Incident datetime
2021-11-04 17:04
Report number
Location
TX
Narrative
Approximately 165 barrels of crude oil were released from the pump 9 discharge station piping at china grove station. The date and time of the release (part a q4) is indicative of the earliest possible time the release could have started, as it was the date/time that the pump had started. The cause of the release was attributed to external corrosion as a result of stay current inference. To prevent future incidents, an interrupted close interval cathodic protection survey will be performed to determine the cause of the stray current and ensure that other facility piping does not have stray current interference. Supplemental narrative: updated the nominal diameter of the failed section of pipe to 10" (part c q3.A). Supplemental narrative (2): the cause of the release was attributed to external corrosion, likely from stay current inference as indicated by the pit morphology. The type of stray current interference is not known (part g1 q2a). To prevent future incidents, a cis survey was conducted and results indicated that the incident location met criteria. Additionally, in 2022, non-destructive testing inspections will be conducted for select pipeline segments within the facility.
Detailed record list
Report Received Date
2021-12-03 00:00:00
Iyear
2021
Report Number
20210340
Supplemental Number
36602
Report Type
Supplemental Final
Operator Id
Name
Plains Pipeline, L.p.
Operator Street Address
333 Clay Street, Suite 1900
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2021-11-04 16:30:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
-100.8419713
Commodity Released Type
Crude Oil
Unintentional Release Bbls
165
Recovered Bbls
165
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Notification From Public
Incident Identified Datetime
2021-11-04 17:04:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Status When Identified
Idle
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2021-11-04 18:21:00
On Site Datetime
2021-11-04 17:30:00
Confirmed Discovery Datetime
2021-11-04 17:30:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Notify Qualified Indiv Ind
Yes
Qualified Indiv Notif Datetime
2021-11-04 17:30:00
Oil Spill Removal Org Ind
No
Num Pub Evacuated
0
Pipe Fac Name
China Grove
Segment Name
China Grove Station Piping - Pump 9 Discharge
Onshore State Abbreviation
Tx
Onshore Postal Code
79526
Onshore City Name
Hermleigh
Onshore County Name
Scurry
Designated Location
Milepost
Designated Name
0+00
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
48
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Pipe
Pipe Type
Pipe Body
Puddle Weld Ind
No
Pipe Diameter
10
Pipe Wall Thickness
0.188
Pipe Smys
42000
Pipe Specification
Api 5l
Pipe Seam Type
Erw � Unknown Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Other
Pipe Coating Details
Mastic
Coating Applied Ind
Unknown
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
400
Est Cost Prop Damage
10009
Est Cost Emergency
10563
Est Cost Environmental
16017
Est Cost Other
0
Prpty
36989
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Accident Psig
38
Mop Psig
285
Mop Cfr Section
Component Design Pressure �195.406(A)(2)
Maop Established Date
1993-01-01 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind
Yes
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
Localized Pitting
Stray Current Corrosion Ind
Yes
Stray Current Type
Alternating Current
Stray Current Details
Unknown
Field Exam Basis Ind
Yes
Metallurgical Basis Ind
Yes
Underground Location
Yes
Under Cathodic Protection Ind
Yes
Cathodic Pro Start Year
Unknown
Shielding Evident
No
Cathodic Survey Type
Yes
Cp Annual Survey Ind
Yes
Cp Annual Survey Year
2021
Prior Damage
No
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
N****** G*******
Preparer Title
Hse Compliance Specialist
Preparer Email
N*********@p****.com
Preparer Telephone
7136464376
Prepared Date
2022-04-22 00:00:00
Local Contact Name
N****** G*******
Local Contact Email
N*********@p****.com
Local Contact Telephone
7136464376
Authorizer Name
N***** G*****
Authorizer Telephone
7136464336
Authorizer Title
Hse Mgr Director
Authorizer Email
N******@p****.com
Narrative
Approximately 165 barrels of crude oil were released from the pump 9 discharge station piping at china grove station. The date and time of the release (part a q4) is indicative of the earliest possible time the release could have started, as it was the date/time that the pump had started. The cause of the release was attributed to external corrosion as a result of stay current inference. To prevent future incidents, an interrupted close interval cathodic protection survey will be performed to determine the cause of the stray current and ensure that other facility piping does not have stray current interference. Supplemental narrative: updated the nominal diameter of the failed section of pipe to 10" (part c q3.A). Supplemental narrative (2): the cause of the release was attributed to external corrosion, likely from stay current inference as indicated by the pit morphology. The type of stray current interference is not known (part g1 q2a). To prevent future incidents, a cis survey was conducted and results indicated that the incident location met criteria. Additionally, in 2022, non-destructive testing inspections will be conducted for select pipeline segments within the facility.
Report Received Date 2021-12-03 00:00:00
Iyear 2021
Report Number 20210340
Supplemental Number 36602
Report Type Supplemental Final
Operator Id 300 PHMSA Enforcement
Name Plains Pipeline, L.p.
Operator Street Address 333 Clay Street, Suite 1900
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77002
Local Datetime 2021-11-04 16:30:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 32.5320273 Google Maps OpenStreetMap
Location Longitude -100.8419713 Google Maps OpenStreetMap
Commodity Released Type Crude Oil
Unintentional Release Bbls 165
Recovered Bbls 165
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Notification From Public
Incident Identified Datetime 2021-11-04 17:04:00
System Part Involved Onshore Terminal/tank Farm Equipment And Piping
On Off Shore Onshore
Status When Identified Idle
Communication State Fed Ind Yes
Party Initiated Communication Operator
Initial Responder Com Datetime 2021-11-04 18:21:00
On Site Datetime 2021-11-04 17:30:00
Confirmed Discovery Datetime 2021-11-04 17:30:00
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Notify Qualified Indiv Ind Yes
Qualified Indiv Notif Datetime 2021-11-04 17:30:00
Oil Spill Removal Org Ind No
Num Pub Evacuated 0
Pipe Fac Name China Grove
Segment Name China Grove Station Piping - Pump 9 Discharge
Onshore State Abbreviation Tx
Onshore Postal Code 79526
Onshore City Name Hermleigh
Onshore County Name Scurry
Designated Location Milepost
Designated Name 0+00
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 48
Crossing No
Pipe Facility Type Intrastate
Item Involved Pipe
Pipe Type Pipe Body
Puddle Weld Ind No
Pipe Diameter 10
Pipe Wall Thickness 0.188
Pipe Smys 42000
Pipe Specification Api 5l
Pipe Seam Type Erw � Unknown Frequency
Pipe Manufacturer Unknown
Pipe Coating Type Other
Pipe Coating Details Mastic
Coating Applied Ind Unknown
Installation Year Unknown
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 400
Est Cost Prop Damage 10009
Est Cost Emergency 10563
Est Cost Environmental 16017
Est Cost Other 0
Prpty 36989
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Accident Psig 38
Mop Psig 285
Mop Cfr Section Component Design Pressure �195.406(A)(2) View CFR 49 §192
Maop Established Date 1993-01-01 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest Schedule Ind Yes
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details External Corrosion
Internal External External Corrosion
Visual Exam Results Localized Pitting
Stray Current Corrosion Ind Yes
Stray Current Type Alternating Current
Stray Current Details Unknown
Field Exam Basis Ind Yes
Metallurgical Basis Ind Yes
Underground Location Yes
Under Cathodic Protection Ind Yes
Cathodic Pro Start Year Unknown
Shielding Evident No
Cathodic Survey Type Yes
Cp Annual Survey Ind Yes
Cp Annual Survey Year 2021
Prior Damage No
Collected Data Ind No
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name N****** G*******
Preparer Title Hse Compliance Specialist
Preparer Email N*********@p****.com
Preparer Telephone 7136464376
Prepared Date 2022-04-22 00:00:00
Local Contact Name N****** G*******
Local Contact Email N*********@p****.com
Local Contact Telephone 7136464376
Authorizer Name N***** G*****
Authorizer Telephone 7136464336
Authorizer Title Hse Mgr Director
Authorizer Email N******@p****.com
Narrative Approximately 165 barrels of crude oil were released from the pump 9 discharge station piping at china grove station. The date and time of the release (part a q4) is indicative of the earliest possible time the release could have started, as it was the date/time that the pump had started. The cause of the release was attributed to external corrosion as a result of stay current inference. To prevent future incidents, an interrupted close interval cathodic protection survey will be performed to determine the cause of the stray current and ensure that other facility piping does not have stray current interference. Supplemental narrative: updated the nominal diameter of the failed section of pipe to 10" (part c q3.A). Supplemental narrative (2): the cause of the release was attributed to external corrosion, likely from stay current inference as indicated by the pit morphology. The type of stray current interference is not known (part g1 q2a). To prevent future incidents, a cis survey was conducted and results indicated that the incident location met criteria. Additionally, in 2022, non-destructive testing inspections will be conducted for select pipeline segments within the facility.