HL incident on 2021-10-15 — LA

Operator
Imtt-Bayonne
Cause
Corrosion Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$95,000
Incident datetime
2021-10-15 12:30
Report number
Location
LA
Narrative
Initial report-10/19/2021 imtt-bayonne was performing an excavation for continual integrity assessment of buried facility piping. During said excavation, a leak was discovered from the asset to be assessed. At this time corrosion is the factor, this report will be updated as the investigation progresses. At the time of discovery the leak was contained into a plastic drip pan which was evacuated by a vacuum truck. The vacuum truck was on standby to assist the excavation crew to control any ground water. Approximately 15 gallons leaked into the pan before operations was able to evacuate and isolate the line, which was recovered by the vacuum truck. The leak did not pose any threat to a public roadway, navigable waterway or active railroad as it was inside the facility. As of 10/19/2021- the line segment is currently out of service with isolation skillets in place and empty. Imtt will perform integrity assessments on the rest of the segment before any repairs will commence. Once assessments are complete, imtt will determine if the segment will be repaired, replaced or abandoned. The line was static at time of discovery. 11/30/2021 update- damaged pipe was removed and replaced.
Detailed record list
Report Received Date
2021-10-19 00:00:00
Iyear
2021
Report Number
20210300
Supplemental Number
36051
Report Type
Supplemental Final
Operator Id
Name
Imtt-Bayonne
Operator Street Address
400 Poydras Street Suite 3000
Operator City Name
New Orleans
Operator State Abbreviation
LA
Operator Postal Code
70130
Local Datetime
2021-10-15 13:30:00
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls
0.35
Recovered Bbls
0.3
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Other
Accident Details
Discovered During Excavation
Incident Identified Datetime
2021-10-15 12:30:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
The Segment Of Line Was Taken Out Of Service.
On Site Datetime
2021-10-15 12:30:00
Nrc Rpt Datetime
2021-10-15 13:30:00
Nrc Rpt Num
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Imtt Bayonne
Segment Name
12" To Packards
Onshore State Abbreviation
Nj
Onshore Postal Code
07002
Onshore City Name
Bayonne
Onshore County Name
Hudson
Designated Location
Milepost/valve Station
Designated Name
12 Inch Line
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Underground
Incident Area Subtype
Exposed Due To Excavation
Depth Of Cover
40
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
12
Pipe Wall Thickness
0.312
Pipe Smys
Unknown
Pipe Specification
Carbon Steel
Pipe Seam Type
Erw � Unknown Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Coal Tar
Installation Year
Unknown
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
Yes
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Other Pop Ind
Yes
Other Pop Yes No
No
Est Cost Oper Paid
0
Est Cost Gas Released
35
Est Cost Prop Damage
95000
Est Cost Emergency
2500
Est Cost Environmental
25
Est Cost Other
25
Est Cost Other Details
Total Costs Will Be Included In Supplemental Or Final Report. 11/30/2021 Update
Prpty
97585
Accident Psig
10
Mop Psig
175
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the accident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
Localized Pitting
Galvanic Corrosion Ind
Yes
Field Exam Basis Ind
Yes
Underground Location
Yes
Under Cathodic Protection Ind
Yes
Cathodic Pro Start Year
2019
Shielding Evident
No
Cathodic Survey Type
Yes
Cp Annual Survey Ind
Yes
Cp Annual Survey Year
2021
Prior Damage
Yes
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
Yes
Hydrtst Most Rcnt Year
2017
Hydrtst Most Rcnt Pressure
220
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
R***** M**********
Preparer Email
R****************@i***.com
Preparer Telephone
2018235334
Prepared Date
2021-11-30 00:00:00
Authorizer Name
R***** M**********
Authorizer Telephone
2018235334
Authorizer Email
R****************@i***.com
Narrative
Initial report-10/19/2021 imtt-bayonne was performing an excavation for continual integrity assessment of buried facility piping. During said excavation, a leak was discovered from the asset to be assessed. At this time corrosion is the factor, this report will be updated as the investigation progresses. At the time of discovery the leak was contained into a plastic drip pan which was evacuated by a vacuum truck. The vacuum truck was on standby to assist the excavation crew to control any ground water. Approximately 15 gallons leaked into the pan before operations was able to evacuate and isolate the line, which was recovered by the vacuum truck. The leak did not pose any threat to a public roadway, navigable waterway or active railroad as it was inside the facility. As of 10/19/2021- the line segment is currently out of service with isolation skillets in place and empty. Imtt will perform integrity assessments on the rest of the segment before any repairs will commence. Once assessments are complete, imtt will determine if the segment will be repaired, replaced or abandoned. The line was static at time of discovery. 11/30/2021 update- damaged pipe was removed and replaced.
Report Received Date 2021-10-19 00:00:00
Iyear 2021
Report Number 20210300
Supplemental Number 36051
Report Type Supplemental Final
Operator Id 39149 PHMSA Enforcement
Name Imtt-Bayonne
Operator Street Address 400 Poydras Street Suite 3000
Operator City Name New Orleans
Operator State Abbreviation LA
Operator Postal Code 70130
Local Datetime 2021-10-15 13:30:00
Location Latitude 40.655789 Google Maps OpenStreetMap
Location Longitude -74.111125 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Diesel, Fuel Oil, Kerosene, Jet Fuel
Unintentional Release Bbls 0.35
Recovered Bbls 0.3
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Other
Accident Details Discovered During Excavation
Incident Identified Datetime 2021-10-15 12:30:00
System Part Involved Onshore Terminal/tank Farm Equipment And Piping
On Off Shore Onshore
Shutdown Due Accident Ind No
Shutdown Explain The Segment Of Line Was Taken Out Of Service.
On Site Datetime 2021-10-15 12:30:00
Nrc Rpt Datetime 2021-10-15 13:30:00
Nrc Rpt Num 1319572 NRC Report How to search
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0
Pipe Fac Name Imtt Bayonne
Segment Name 12" To Packards
Onshore State Abbreviation Nj
Onshore Postal Code 07002
Onshore City Name Bayonne
Onshore County Name Hudson
Designated Location Milepost/valve Station
Designated Name 12 Inch Line
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Underground
Incident Area Subtype Exposed Due To Excavation
Depth Of Cover 40
Crossing No
Pipe Facility Type Intrastate
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 12
Pipe Wall Thickness 0.312
Pipe Smys Unknown
Pipe Specification Carbon Steel
Pipe Seam Type Erw � Unknown Frequency
Pipe Manufacturer Unknown
Pipe Coating Type Coal Tar
Installation Year Unknown
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment Yes
Remediation Ind Yes
Soil Remed Ind Yes
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
Other Pop Ind Yes
Other Pop Yes No No
Est Cost Oper Paid 0
Est Cost Gas Released 35
Est Cost Prop Damage 95000
Est Cost Emergency 2500
Est Cost Environmental 25
Est Cost Other 25
Est Cost Other Details Total Costs Will Be Included In Supplemental Or Final Report. 11/30/2021 Update
Prpty 97585
Accident Psig 10
Mop Psig 175
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function < 20% Smys Regulated Transmission
Scada In Place Ind No
Cpm In Place Ind No
Investigation Status No, the facility was not monitored by a controller(s) at the time of the accident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details External Corrosion
Internal External External Corrosion
Visual Exam Results Localized Pitting
Galvanic Corrosion Ind Yes
Field Exam Basis Ind Yes
Underground Location Yes
Under Cathodic Protection Ind Yes
Cathodic Pro Start Year 2019
Shielding Evident No
Cathodic Survey Type Yes
Cp Annual Survey Ind Yes
Cp Annual Survey Year 2021
Prior Damage Yes
Collected Data Ind No
Has Hydrtst Conduc Before Ind Yes
Hydrtst Most Rcnt Year 2017
Hydrtst Most Rcnt Pressure 220
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Preparer Name R***** M**********
Preparer Email R****************@i***.com
Preparer Telephone 2018235334
Prepared Date 2021-11-30 00:00:00
Authorizer Name R***** M**********
Authorizer Telephone 2018235334
Authorizer Email R****************@i***.com
Narrative Initial report-10/19/2021 imtt-bayonne was performing an excavation for continual integrity assessment of buried facility piping. During said excavation, a leak was discovered from the asset to be assessed. At this time corrosion is the factor, this report will be updated as the investigation progresses. At the time of discovery the leak was contained into a plastic drip pan which was evacuated by a vacuum truck. The vacuum truck was on standby to assist the excavation crew to control any ground water. Approximately 15 gallons leaked into the pan before operations was able to evacuate and isolate the line, which was recovered by the vacuum truck. The leak did not pose any threat to a public roadway, navigable waterway or active railroad as it was inside the facility. As of 10/19/2021- the line segment is currently out of service with isolation skillets in place and empty. Imtt will perform integrity assessments on the rest of the segment before any repairs will commence. Once assessments are complete, imtt will determine if the segment will be repaired, replaced or abandoned. The line was static at time of discovery. 11/30/2021 update- damaged pipe was removed and replaced.

All rights reserved. Copyright © by ClearPHMSA