GD incident on 2021-11-29 — SD

Operator
Montana - Dakota Utilities Co
Cause
Notification Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$8,000
Incident datetime
2021-11-29 10:27
Report number
Location
SD, PENNINGTON
Narrative
On november 29, 2021 at 9:22 a.M. Mst, an excavator notified montana-dakota utilities co. (mdu) that they damaged a 1" main near 920 11th street, rapid city, south dakota. An mdu first responder arrived at 10:27 a.M. Mst and after checking in with local fire department personnel on scene, began investigating. While the mdu emergency responders were working to secure the damage, the leaking natural gas caused by the excavation damage migrated and subsequently ignited causing an explosion and a fire at 920 11th street. An mdu crew excavated and squeezed the 2" steel main upstream of the damaged 1" main. The investigation determined the third-party excavator locate ticket expired prior to commencing work on the date of the incident.
Detailed record list
Occurred At
2021-11-29 10:27:00
Year
2021
Report Received Date
2021-12-22 00:00:00
Iyear
2021.0
Report Number
20210104.0
Supplemental Number
36172.0
Report Type
Original Final
Operator Id
Name
Montana - Dakota Utilities Co
Operator Street Address
400 North Fourth Street
Operator City Name
Bismarck
Operator State Abbreviation
ND
Operator Postal Code
58501
Local Datetime
2021-11-29 11:00:00
Time Zone
Mountain
Daylight Savings Ind
No
Location Street Address
920 11th Street
Location City Name
Rapid City
Location County Name
Pennington
Location State Abbreviation
SD
Location Postal Code
57701
Location Latitude
Location Longitude
Flow Cont Squeeze Off Ind
Yes
Nrc Rpt Datetime
2021-11-29 11:28:00
Nrc Rpt Num
Additional Nrc Report Numbers
1323315
Commodity Released Type
Natural Gas
Unintentional Release
46.28
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Ignite Datetime
2021-11-29 11:00:00
How Extinguished
Allowed To Burn Out
Gas Consumed By Fire In Mcf
10.85
Explode Ind
Yes
Num Pub Evacuated
4.0
Incident Identified Datetime
2021-11-29 10:27:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2021-11-29 10:27:00
On Site Datetime
2021-11-29 10:27:00
Federal
No
Location Type
Private Property
Incident Area Type
Underground
Incident Area Subtype
Other
Incident Area Details
Inside Residential Structure.
Depth Of Cover
30.0
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
1967.0
Pipe Diameter
1.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Longitudinal Erw - Unknown Frequency
Release Type
Other
Release Type Details
Third Party Damage Pulled Distribution Main Apart At An Elbow Fitting Connection.
Class Location Type
Class 3 Location
Est Cost Oper Paid
210000.0
Est Cost Prop Damage
8000.0
Est Cost Emergency
6500.0
Est Cost Other
0.0
Gas Cost In Mcf
6.22
Est Cost Unintentional Release
288.0
Est Cost Intentional Release
0.0
Prpty
224788.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
5.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
5.0
Num Business Building Affctd
0.0
Accident Psig
30.0
Normal Psig
30.0
Mop Psig
34.0
Mop Cfr Section
192.619(A)(1)
Maop Established Date
1993-09-17 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Odorized By Others
Gas Odorized Level
12.5
Scada In Place Ind
No
Accident Identifier
Notification From Third Party That Caused The Incident
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
Yes
One Call System Ind
Yes
State Law Exempt Ind
No
Notify Cga Dirt
No
Public Row Ind
Yes
Public Subtype
City Street
Excavator Type
Contractor
Excavator Equipment
Backhoe/trackhoe
Work Performed
Water
One Call Notified Ind
Yes
One Call Ticket Num
2129918149
Locator Type
Contract Locator
Visible Marks
No
Service Interruption
Yes
Service Interruption Hours
3.0
Root Cause Category
Notification Issue
Root Cause Type
No Notification Made To The One-Call Center/811
Preparer Name
G*** W******
Preparer Title
Manager Policy And Procedure
Preparer Email
G***********@m**.com
Preparer Telephone
2083776032
Local Contact Name
G*** W******
Local Contact Email
G***********@m**.com
Local Contact Telephone
2083776032
Authorizer Name
G*** W******
Authorizer Title
Manager Policy And Procedure
Authorizer Telephone
2083776032
Authorizer Email
G***********@m**.com
Narrative
On november 29, 2021 at 9:22 a.M. Mst, an excavator notified montana-dakota utilities co. (mdu) that they damaged a 1" main near 920 11th street, rapid city, south dakota. An mdu first responder arrived at 10:27 a.M. Mst and after checking in with local fire department personnel on scene, began investigating. While the mdu emergency responders were working to secure the damage, the leaking natural gas caused by the excavation damage migrated and subsequently ignited causing an explosion and a fire at 920 11th street. An mdu crew excavated and squeezed the 2" steel main upstream of the damaged 1" main. The investigation determined the third-party excavator locate ticket expired prior to commencing work on the date of the incident.
Occurred At 2021-11-29 10:27:00
Year 2021
Report Received Date 2021-12-22 00:00:00
Iyear 2021.0
Report Number 20210104.0
Supplemental Number 36172.0
Report Type Original Final
Operator Id 12684 PHMSA Enforcement
Name Montana - Dakota Utilities Co
Operator Street Address 400 North Fourth Street
Operator City Name Bismarck
Operator State Abbreviation ND
Operator Postal Code 58501
Local Datetime 2021-11-29 11:00:00
Time Zone Mountain
Daylight Savings Ind No
Location Street Address 920 11th Street
Location City Name Rapid City
Location County Name Pennington
Location State Abbreviation SD
Location Postal Code 57701
Location Latitude 44.07769794 Google Maps OpenStreetMap
Location Longitude -103.237473 Google Maps OpenStreetMap
Flow Cont Squeeze Off Ind Yes
Nrc Rpt Datetime 2021-11-29 11:28:00
Nrc Rpt Num 1323119 NRC Report How to search
Additional Nrc Report Numbers 1323315
Commodity Released Type Natural Gas
Unintentional Release 46.28
Intentional Release 0.0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind Yes
Ignite Datetime 2021-11-29 11:00:00
How Extinguished Allowed To Burn Out
Gas Consumed By Fire In Mcf 10.85
Explode Ind Yes
Num Pub Evacuated 4.0
Incident Identified Datetime 2021-11-29 10:27:00
Communication State Fed Ind Yes
Party Initiated Communication Operator
Initial Responder Com Datetime 2021-11-29 10:27:00
On Site Datetime 2021-11-29 10:27:00
Federal No
Location Type Private Property
Incident Area Type Underground
Incident Area Subtype Other
Incident Area Details Inside Residential Structure.
Depth Of Cover 30.0
Other Underground Facilities No
Crossing No
Pipe Facility Type Investor Owned
System Part Involved Main
Installation Year 1967.0
Pipe Diameter 1.0
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Steel
Steel Seam Type Longitudinal Erw - Unknown Frequency
Release Type Other
Release Type Details Third Party Damage Pulled Distribution Main Apart At An Elbow Fitting Connection.
Class Location Type Class 3 Location
Est Cost Oper Paid 210000.0
Est Cost Prop Damage 8000.0
Est Cost Emergency 6500.0
Est Cost Other 0.0
Gas Cost In Mcf 6.22
Est Cost Unintentional Release 288.0
Est Cost Intentional Release 0.0
Prpty 224788.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 5.0
Num Persons Hosp Not Ovnght 0.0
Num Injured Treated By Emt 0.0
Num Resident Building Affctd 5.0
Num Business Building Affctd 0.0
Accident Psig 30.0
Normal Psig 30.0
Mop Psig 34.0
Mop Cfr Section 192.619(A)(1) View CFR 49 §192
Maop Established Date 1993-09-17 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type Odorized By Others
Gas Odorized Level 12.5
Scada In Place Ind No
Accident Identifier Notification From Third Party That Caused The Incident
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Excavation Damage
Cause Details Excavation Damage By Third Party
Ex Party Type Excavation Damage By Third Party
Prior Notification Ind Yes
One Call System Ind Yes
State Law Exempt Ind No
Notify Cga Dirt No
Public Row Ind Yes
Public Subtype City Street
Excavator Type Contractor
Excavator Equipment Backhoe/trackhoe
Work Performed Water
One Call Notified Ind Yes
One Call Ticket Num 2129918149
Locator Type Contract Locator
Visible Marks No
Service Interruption Yes
Service Interruption Hours 3.0
Root Cause Category Notification Issue
Root Cause Type No Notification Made To The One-Call Center/811
Preparer Name G*** W******
Preparer Title Manager Policy And Procedure
Preparer Email G***********@m**.com
Preparer Telephone 2083776032
Local Contact Name G*** W******
Local Contact Email G***********@m**.com
Local Contact Telephone 2083776032
Authorizer Name G*** W******
Authorizer Title Manager Policy And Procedure
Authorizer Telephone 2083776032
Authorizer Email G***********@m**.com
Narrative On november 29, 2021 at 9:22 a.M. Mst, an excavator notified montana-dakota utilities co. (mdu) that they damaged a 1" main near 920 11th street, rapid city, south dakota. An mdu first responder arrived at 10:27 a.M. Mst and after checking in with local fire department personnel on scene, began investigating. While the mdu emergency responders were working to secure the damage, the leaking natural gas caused by the excavation damage migrated and subsequently ignited causing an explosion and a fire at 920 11th street. An mdu crew excavated and squeezed the 2" steel main upstream of the damaged 1" main. The investigation determined the third-party excavator locate ticket expired prior to commencing work on the date of the incident.

All rights reserved. Copyright © by ClearPHMSA