Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2021-10-22 — TX
Operator
Brenham Utility, City Of
Cause
Excavation Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$2,904
Incident datetime
2021-10-22 09:20
Report number
Location
TX, WASHINGTON
Narrative
The excavator was working on the access road for the entrance to the new shopping center. The project has been ongoing since february. They had not started on this section until the last couple of months. After removing an old driveway that existed along the road they had changed the grade of the area by removing a portion of the dirt that covered the 6" main. There had been a locate done for a fiber contractor that was basically along the same path of the road contractors worksite. The main was flagged and marked correctly along the path. All the markings were present when burts construction removed some more material with a dozer and then brought in a reclaimer to mix the dirt and road base for stabilization. When the mixer started to till the dirt it hit the line damaging it and causing an ignition. The equipment operator shut off the machine and jumped off but but did get his right arm burnt to the point he was taken to the hospital by helicopter. The reclaimer was engulfed in flames and completely destroyed. We closed a valve off on the west side of the damage and then dug up the 6" and squeezed it off to stop the flow of gas on the east side. The fire department put the fire out. I contacted the rrc by phone and also the nrc. The rrc sent investigators out to access the scene and investigate it. I checked on the employee who was injured and his supervisor said he was released from the hospital that same night with severe burns on his right arm. The damaged reclaimer was removed from the spot on the 25th of october 2021. On tuesday the 26th october 2021 we dug up, lowered and repaired the line was damaged with the rrc inspectors on site. On thursday the gas department exposed the gas main along the area in 4 different spots verifying its location and depth. All were already correctly marked but these areas had not had dirt removed from the top of them. The city of brenham gas depoartment will continue to mark our facilities in accordance with the texas aministrative code title 16 part 1 chapter 18 for underground pipeline damage prevention. We have put in place in our plan review for developement services under the gas department comments section verbiage stating that the builder, contractor, developer and/or excavators that take part in these work projects will maintain contact with the city of brenham and be aware of their responsibility of protection of existing city untilities on these sites during the duration of the project.
Detailed record list
Occurred At
2021-10-22 09:20:00
Year
2021
Report Received Date
2021-11-16 00:00:00
Iyear
2021.0
Report Number
20210095.0
Supplemental Number
36213.0
Report Type
Supplemental Final
Operator Id
1720
Name
Brenham Utility, City Of
Operator Street Address
200 W Vulcan St
Operator City Name
Brenham
Operator State Abbreviation
TX
Operator Postal Code
77834
Local Datetime
2021-10-22 09:20:00
Time Zone
Central
Daylight Savings Ind
No
Location Street Address
H*********@ ******************
Location City Name
Brenham
Location County Name
Washington
Location State Abbreviation
TX
Location Postal Code
77833
Location Latitude
30.142049
Location Longitude
-96.382068
Flow Cont Key Crit Ind
Yes
Flow Cont Squeeze Off Ind
Yes
Nrc Rpt Datetime
2021-10-22 11:35:00
Nrc Rpt Num
1320155
Additional Nrc Report Numbers
1320663
Commodity Released Type
Natural Gas
Unintentional Release
250.0
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Ignite Datetime
2021-10-22 09:20:00
How Extinguished
Local/state/federal Emergency Responder
Gas Consumed By Fire In Mcf
250
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2021-10-22 09:20:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2021-10-22 09:20:00
On Site Datetime
2021-10-22 09:27:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Exposed Due To Excavation
Depth Of Cover
18.0
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Municipally Owned
System Part Involved
Main
Installation Year
1994.0
Manufactured Year
1992.0
Pipe Diameter
6.0
Pipe Specification
Astm D2513
Pipe Manufacturer
Driscopipe
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Plastic Sdr
11.5
Material Pe Pipe Code
2406
Release Type
Mechanical Puncture
Puncture Axial
1.0
Puncture Circum
1.5
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
2904.0
Est Cost Emergency
583.0
Est Cost Other
2025.0
Est Cost Other Details
Cost Of Brenham Fd Along With 3 Other Fire Departments Mutual Aid
Gas Cost In Mcf
8.05
Est Cost Unintentional Release
2013.0
Est Cost Intentional Release
0.0
Prpty
7525.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Num Persons Hosp Not Ovnght
1.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
0.0
Num Business Building Affctd
0.0
Accident Psig
28.0
Normal Psig
28.0
Mop Psig
60.0
Mop Cfr Section
192.619(A)(4)
Maop Established Date
1980-01-01 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The pressure changes was from the damage due to the pipeline.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
Yes
One Call System Ind
Yes
State Law Exempt Ind
No
Notify Cga Dirt
Yes
Public Row Ind
Yes
Public Subtype
State Highway
Excavator Type
Contractor
Excavator Equipment
Unknown/other
Work Performed
Road Work
One Call Notified Ind
Yes
One Call Ticket Num
2178065546
One Call Center Name
Texas 811 Is The Only One-Call
Locator Type
Utility Owner
Visible Marks
Yes
Service Interruption
Unknown/other
Root Cause Category
Excavation Issue
Root Cause Type
Improper Excavation Practice Not Listed Above
Preparer Name
A*** B******
Preparer Title
Gas Superintindent
Preparer Email
A*******@c************.org
Preparer Telephone
19793377416
Preparer Fax
19793377419
Local Contact Name
A*** B******
Local Contact Email
A*******@c************.org
Local Contact Telephone
19794511772
Authorizer Name
A*** B******
Authorizer Title
Gas Superintindent
Authorizer Telephone
19794511772
Authorizer Email
A*******@c************.org
Narrative
The excavator was working on the access road for the entrance to the new shopping center. The project has been ongoing since february. They had not started on this section until the last couple of months. After removing an old driveway that existed along the road they had changed the grade of the area by removing a portion of the dirt that covered the 6" main. There had been a locate done for a fiber contractor that was basically along the same path of the road contractors worksite. The main was flagged and marked correctly along the path. All the markings were present when burts construction removed some more material with a dozer and then brought in a reclaimer to mix the dirt and road base for stabilization. When the mixer started to till the dirt it hit the line damaging it and causing an ignition. The equipment operator shut off the machine and jumped off but but did get his right arm burnt to the point he was taken to the hospital by helicopter. The reclaimer was engulfed in flames and completely destroyed. We closed a valve off on the west side of the damage and then dug up the 6" and squeezed it off to stop the flow of gas on the east side. The fire department put the fire out. I contacted the rrc by phone and also the nrc. The rrc sent investigators out to access the scene and investigate it. I checked on the employee who was injured and his supervisor said he was released from the hospital that same night with severe burns on his right arm. The damaged reclaimer was removed from the spot on the 25th of october 2021. On tuesday the 26th october 2021 we dug up, lowered and repaired the line was damaged with the rrc inspectors on site. On thursday the gas department exposed the gas main along the area in 4 different spots verifying its location and depth. All were already correctly marked but these areas had not had dirt removed from the top of them. The city of brenham gas depoartment will continue to mark our facilities in accordance with the texas aministrative code title 16 part 1 chapter 18 for underground pipeline damage prevention. We have put in place in our plan review for developement services under the gas department comments section verbiage stating that the builder, contractor, developer and/or excavators that take part in these work projects will maintain contact with the city of brenham and be aware of their responsibility of protection of existing city untilities on these sites during the duration of the project.
| Occurred At | 2021-10-22 09:20:00 |
|---|---|
| Year | 2021 |
| Report Received Date | 2021-11-16 00:00:00 |
| Iyear | 2021.0 |
| Report Number | 20210095.0 |
| Supplemental Number | 36213.0 |
| Report Type | Supplemental Final |
| Operator Id | 1720 PHMSA Enforcement |
| Name | Brenham Utility, City Of |
| Operator Street Address | 200 W Vulcan St |
| Operator City Name | Brenham |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77834 |
| Local Datetime | 2021-10-22 09:20:00 |
| Time Zone | Central |
| Daylight Savings Ind | No |
| Location Street Address | H*********@ ****************** |
| Location City Name | Brenham |
| Location County Name | Washington |
| Location State Abbreviation | TX |
| Location Postal Code | 77833 |
| Location Latitude | 30.142049 Google Maps OpenStreetMap |
| Location Longitude | -96.382068 Google Maps OpenStreetMap |
| Flow Cont Key Crit Ind | Yes |
| Flow Cont Squeeze Off Ind | Yes |
| Nrc Rpt Datetime | 2021-10-22 11:35:00 |
| Nrc Rpt Num | 1320155 NRC Report How to search |
| Additional Nrc Report Numbers | 1320663 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 250.0 |
| Intentional Release | 0.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | Yes |
| Ignite Datetime | 2021-10-22 09:20:00 |
| How Extinguished | Local/state/federal Emergency Responder |
| Gas Consumed By Fire In Mcf | 250 |
| Explode Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2021-10-22 09:20:00 |
| Communication State Fed Ind | Yes |
| Party Initiated Communication | Operator |
| Initial Responder Com Datetime | 2021-10-22 09:20:00 |
| On Site Datetime | 2021-10-22 09:27:00 |
| Federal | No |
| Location Type | Public Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Exposed Due To Excavation |
| Depth Of Cover | 18.0 |
| Other Underground Facilities | No |
| Crossing | No |
| Pipe Facility Type | Municipally Owned |
| System Part Involved | Main |
| Installation Year | 1994.0 |
| Manufactured Year | 1992.0 |
| Pipe Diameter | 6.0 |
| Pipe Specification | Astm D2513 |
| Pipe Manufacturer | Driscopipe |
| Material Involved | Plastic |
| Plastic Type | Polyethylene (Pe) |
| Plastic Sdr | 11.5 |
| Material Pe Pipe Code | 2406 |
| Release Type | Mechanical Puncture |
| Puncture Axial | 1.0 |
| Puncture Circum | 1.5 |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 2904.0 |
| Est Cost Emergency | 583.0 |
| Est Cost Other | 2025.0 |
| Est Cost Other Details | Cost Of Brenham Fd Along With 3 Other Fire Departments Mutual Aid |
| Gas Cost In Mcf | 8.05 |
| Est Cost Unintentional Release | 2013.0 |
| Est Cost Intentional Release | 0.0 |
| Prpty | 7525.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 0.0 |
| Num Persons Hosp Not Ovnght | 1.0 |
| Num Injured Treated By Emt | 0.0 |
| Num Resident Building Affctd | 0.0 |
| Num Business Building Affctd | 0.0 |
| Accident Psig | 28.0 |
| Normal Psig | 28.0 |
| Mop Psig | 60.0 |
| Mop Cfr Section | 192.619(A)(4) View CFR 49 §192 |
| Maop Established Date | 1980-01-01 00:00:00 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Gas Odorized System Type | Injection Pump |
| Gas Odorized Lvl Not Msrd Ind | Yes |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | No |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | The pressure changes was from the damage due to the pipeline. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Excavation Damage |
| Cause Details | Excavation Damage By Third Party |
| Ex Party Type | Excavation Damage By Third Party |
| Prior Notification Ind | Yes |
| One Call System Ind | Yes |
| State Law Exempt Ind | No |
| Notify Cga Dirt | Yes |
| Public Row Ind | Yes |
| Public Subtype | State Highway |
| Excavator Type | Contractor |
| Excavator Equipment | Unknown/other |
| Work Performed | Road Work |
| One Call Notified Ind | Yes |
| One Call Ticket Num | 2178065546 |
| One Call Center Name | Texas 811 Is The Only One-Call |
| Locator Type | Utility Owner |
| Visible Marks | Yes |
| Service Interruption | Unknown/other |
| Root Cause Category | Excavation Issue |
| Root Cause Type | Improper Excavation Practice Not Listed Above |
| Preparer Name | A*** B****** |
| Preparer Title | Gas Superintindent |
| Preparer Email | A*******@c************.org |
| Preparer Telephone | 19793377416 |
| Preparer Fax | 19793377419 |
| Local Contact Name | A*** B****** |
| Local Contact Email | A*******@c************.org |
| Local Contact Telephone | 19794511772 |
| Authorizer Name | A*** B****** |
| Authorizer Title | Gas Superintindent |
| Authorizer Telephone | 19794511772 |
| Authorizer Email | A*******@c************.org |
| Narrative | The excavator was working on the access road for the entrance to the new shopping center. The project has been ongoing since february. They had not started on this section until the last couple of months. After removing an old driveway that existed along the road they had changed the grade of the area by removing a portion of the dirt that covered the 6" main. There had been a locate done for a fiber contractor that was basically along the same path of the road contractors worksite. The main was flagged and marked correctly along the path. All the markings were present when burts construction removed some more material with a dozer and then brought in a reclaimer to mix the dirt and road base for stabilization. When the mixer started to till the dirt it hit the line damaging it and causing an ignition. The equipment operator shut off the machine and jumped off but but did get his right arm burnt to the point he was taken to the hospital by helicopter. The reclaimer was engulfed in flames and completely destroyed. We closed a valve off on the west side of the damage and then dug up the 6" and squeezed it off to stop the flow of gas on the east side. The fire department put the fire out. I contacted the rrc by phone and also the nrc. The rrc sent investigators out to access the scene and investigate it. I checked on the employee who was injured and his supervisor said he was released from the hospital that same night with severe burns on his right arm. The damaged reclaimer was removed from the spot on the 25th of october 2021. On tuesday the 26th october 2021 we dug up, lowered and repaired the line was damaged with the rrc inspectors on site. On thursday the gas department exposed the gas main along the area in 4 different spots verifying its location and depth. All were already correctly marked but these areas had not had dirt removed from the top of them. The city of brenham gas depoartment will continue to mark our facilities in accordance with the texas aministrative code title 16 part 1 chapter 18 for underground pipeline damage prevention. We have put in place in our plan review for developement services under the gas department comments section verbiage stating that the builder, contractor, developer and/or excavators that take part in these work projects will maintain contact with the city of brenham and be aware of their responsibility of protection of existing city untilities on these sites during the duration of the project. |
External Resources
PHMSA pipeline safety insights.
Product
Features