Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2021-08-11 — VA
Operator
Virginia Natural Gas
Cause
Locating Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$247,458
Incident datetime
2021-08-11 14:42
Report number
Location
VA, CHESAPEAKE
Narrative
Damaged line reported by 3rd party contractor (utility cable) for the intersection of cedar rd & waters rd in chesapeake va. Contractor was using hdd machine from the sw corner of intersection to the nw corner to install conduit from vault to vault. Contractor had valid ticket and locate contractor marked what they thought was the 8 inch steel main. Gis did not show an offset in roadway where the hdd machine struck the eight inch epoxy coated steel main in the street.
Detailed record list
Occurred At
2021-08-11 14:42:00
Year
2021
Report Received Date
2021-09-08 00:00:00
Iyear
2021.0
Report Number
20210077.0
Supplemental Number
36489.0
Report Type
Supplemental Final
Operator Id
21349
Name
Virginia Natural Gas
Operator Street Address
544 S. Independence Blvd
Operator City Name
Virginia Beach
Operator State Abbreviation
VA
Operator Postal Code
23452
Local Datetime
2021-08-12 10:20:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Street Address
Intersection Of Cedar Road And Waters Road
Location City Name
Chesapeake
Location County Name
Chesapeake
Location State Abbreviation
VA
Location Postal Code
23322
Location Latitude
36.711178
Location Longitude
-76.273372
Flow Cont Squeeze Off Ind
Yes
Nrc Rpt Datetime
2021-08-12 10:50:00
Nrc Rpt Num
1313471
Additional Nrc Report Numbers
1313577
Commodity Released Type
Natural Gas
Unintentional Release
10090.6
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Num Pub Evacuated
100.0
Incident Identified Datetime
2021-08-11 14:42:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2021-08-11 15:01:00
On Site Datetime
2021-08-11 15:01:00
Federal
No
Location Type
Utility Right-Of-Way / Easement
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
48.0
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Pipe Diameter
8.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Longitudinal Erw - Unknown Frequency
Wt Steel
0.219
Release Type
Mechanical Puncture
Puncture Axial
3.0
Puncture Circum
4.0
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
247458.0
Est Cost Emergency
102179.0
Est Cost Other
0.0
Gas Cost In Mcf
3.4182
Est Cost Unintentional Release
34492.0
Est Cost Intentional Release
0.0
Prpty
384129.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
1.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
1.0
Num Business Building Affctd
2.0
Accident Psig
53.0
Normal Psig
53.0
Mop Psig
60.0
Mop Cfr Section
192.619(A)(4)
Maop Established Date
1985-01-01 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Combination Of Odorization Types
Gas Odorized Level
100
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Notification From Third Party That Caused The Incident
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Failure was reported by a third party immediately following the damage. This leak did not cause a pressure reduction which would have been identified via a scada measurement.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
Yes
One Call System Ind
Yes
State Law Exempt Ind
No
Notify Cga Dirt
No
Public Row Ind
Yes
Public Subtype
City Street
Excavator Type
Contractor
Excavator Equipment
Directional Drilling
Work Performed
Telecommunications
One Call Notified Ind
Yes
One Call Ticket Num
A120701656
Locator Type
Contract Locator
Visible Marks
No
Service Interruption
Yes
Service Interruption Hours
24.0
Root Cause Category
Locating Issue
Root Cause Type
Facility Not Marked Due To Incorrect Facility Records/maps
Preparer Name
J******* H****
Preparer Title
Director - Compliance And System Integrity
Preparer Email
J******@s*********.com
Preparer Telephone
(757) 298-5729
Local Contact Name
J******* H****
Local Contact Email
J******@s*********.com
Local Contact Telephone
(757) 298-5729
Authorizer Name
J******* H****
Authorizer Title
Director - Compliance And System Integrity
Authorizer Telephone
7572985729
Authorizer Email
J******@s*********.com
Narrative
Damaged line reported by 3rd party contractor (utility cable) for the intersection of cedar rd & waters rd in chesapeake va. Contractor was using hdd machine from the sw corner of intersection to the nw corner to install conduit from vault to vault. Contractor had valid ticket and locate contractor marked what they thought was the 8 inch steel main. Gis did not show an offset in roadway where the hdd machine struck the eight inch epoxy coated steel main in the street.
| Occurred At | 2021-08-11 14:42:00 |
|---|---|
| Year | 2021 |
| Report Received Date | 2021-09-08 00:00:00 |
| Iyear | 2021.0 |
| Report Number | 20210077.0 |
| Supplemental Number | 36489.0 |
| Report Type | Supplemental Final |
| Operator Id | 21349 PHMSA Enforcement |
| Name | Virginia Natural Gas |
| Operator Street Address | 544 S. Independence Blvd |
| Operator City Name | Virginia Beach |
| Operator State Abbreviation | VA |
| Operator Postal Code | 23452 |
| Local Datetime | 2021-08-12 10:20:00 |
| Time Zone | Eastern |
| Daylight Savings Ind | Yes |
| Location Street Address | Intersection Of Cedar Road And Waters Road |
| Location City Name | Chesapeake |
| Location County Name | Chesapeake |
| Location State Abbreviation | VA |
| Location Postal Code | 23322 |
| Location Latitude | 36.711178 Google Maps OpenStreetMap |
| Location Longitude | -76.273372 Google Maps OpenStreetMap |
| Flow Cont Squeeze Off Ind | Yes |
| Nrc Rpt Datetime | 2021-08-12 10:50:00 |
| Nrc Rpt Num | 1313471 NRC Report How to search |
| Additional Nrc Report Numbers | 1313577 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 10090.6 |
| Intentional Release | 0.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | No |
| Num Pub Evacuated | 100.0 |
| Incident Identified Datetime | 2021-08-11 14:42:00 |
| Communication State Fed Ind | Yes |
| Party Initiated Communication | Operator |
| Initial Responder Com Datetime | 2021-08-11 15:01:00 |
| On Site Datetime | 2021-08-11 15:01:00 |
| Federal | No |
| Location Type | Utility Right-Of-Way / Easement |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Pavement |
| Depth Of Cover | 48.0 |
| Other Underground Facilities | No |
| Crossing | No |
| Pipe Facility Type | Investor Owned |
| System Part Involved | Main |
| Pipe Diameter | 8.0 |
| Pipe Specification | Unknown |
| Pipe Manufacturer | Unknown |
| Material Involved | Steel |
| Steel Seam Type | Longitudinal Erw - Unknown Frequency |
| Wt Steel | 0.219 |
| Release Type | Mechanical Puncture |
| Puncture Axial | 3.0 |
| Puncture Circum | 4.0 |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 247458.0 |
| Est Cost Emergency | 102179.0 |
| Est Cost Other | 0.0 |
| Gas Cost In Mcf | 3.4182 |
| Est Cost Unintentional Release | 34492.0 |
| Est Cost Intentional Release | 0.0 |
| Prpty | 384129.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 1.0 |
| Num Persons Hosp Not Ovnght | 0.0 |
| Num Injured Treated By Emt | 0.0 |
| Num Resident Building Affctd | 1.0 |
| Num Business Building Affctd | 2.0 |
| Accident Psig | 53.0 |
| Normal Psig | 53.0 |
| Mop Psig | 60.0 |
| Mop Cfr Section | 192.619(A)(4) View CFR 49 §192 |
| Maop Established Date | 1985-01-01 00:00:00 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Gas Odorized System Type | Combination Of Odorization Types |
| Gas Odorized Level | 100 |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Accident Identifier | Notification From Third Party That Caused The Incident |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Failure was reported by a third party immediately following the damage. This leak did not cause a pressure reduction which would have been identified via a scada measurement. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Excavation Damage |
| Cause Details | Excavation Damage By Third Party |
| Ex Party Type | Excavation Damage By Third Party |
| Prior Notification Ind | Yes |
| One Call System Ind | Yes |
| State Law Exempt Ind | No |
| Notify Cga Dirt | No |
| Public Row Ind | Yes |
| Public Subtype | City Street |
| Excavator Type | Contractor |
| Excavator Equipment | Directional Drilling |
| Work Performed | Telecommunications |
| One Call Notified Ind | Yes |
| One Call Ticket Num | A120701656 |
| Locator Type | Contract Locator |
| Visible Marks | No |
| Service Interruption | Yes |
| Service Interruption Hours | 24.0 |
| Root Cause Category | Locating Issue |
| Root Cause Type | Facility Not Marked Due To Incorrect Facility Records/maps |
| Preparer Name | J******* H**** |
| Preparer Title | Director - Compliance And System Integrity |
| Preparer Email | J******@s*********.com |
| Preparer Telephone | (757) 298-5729 |
| Local Contact Name | J******* H**** |
| Local Contact Email | J******@s*********.com |
| Local Contact Telephone | (757) 298-5729 |
| Authorizer Name | J******* H**** |
| Authorizer Title | Director - Compliance And System Integrity |
| Authorizer Telephone | 7572985729 |
| Authorizer Email | J******@s*********.com |
| Narrative | Damaged line reported by 3rd party contractor (utility cable) for the intersection of cedar rd & waters rd in chesapeake va. Contractor was using hdd machine from the sw corner of intersection to the nw corner to install conduit from vault to vault. Contractor had valid ticket and locate contractor marked what they thought was the 8 inch steel main. Gis did not show an offset in roadway where the hdd machine struck the eight inch epoxy coated steel main in the street. |