GD incident on 2021-07-18 — WV
Operator
Mountaineer Gas Co
Cause
Excavation Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
1 injury
Property damage (nominal)
$111
Incident datetime
2021-07-18 16:51
Report number
Location
WV, RALEIGH
Narrative
At 16:20 july 18, 2021, operator's dispatch center received an odor of gas call from 123 beaver plaza, a united states post office serving the community of beaver, raleigh county, w.Va. A first responder was dispatched. At 16:51, raleigh county emergency services notified operator's dispatch center of a reported explosion at 103 beaver plaza. An operations manager also was dispatched. Operator's employees noted that a structure at 103 beaver plaza was visibly damaged. Emergency responders informed operator's employees that one person was injured and had been airlifted to cabell-huntington hospital. An odor of gas was detected at a nearby sewer manhole. Operator's employees also checked nearby businesses for gas with consistently negative results. There are two buildings located at 103 beaver plaza. The damaged building is located on the southern side of the property and houses a gambling establishment. A second building is located on the northern side of the property and houses only two restrooms, but at the time of the incident was boarded up. Operator has a 4-inch medium-pressure plastic gas distribution main in an easement immediately north of the second building. Operator's employees checked nearby sewer manholes and determined that gas was present in the area of the second building. Employees began excavating the main to determine the source of the leak. When the main was exposed, a sewer connection for the second building was found directly over the main. Concrete had been poured over the sewer connection. Operator's employees discovered a gouge in the main. A clamp was found covering the gouge. Fastenings on the clamp were corroded. The damaged section of main and the clamp were recovered and are being preserved. Prior to the completion of work at the site, operator's employees performed an odorization read, showing a .30 average threshold, .51 readily detectable. The answers to the following questions have been provided provisionally using guidance received on august 16, 2021 from mary friend, director of gas pipeline safety at the public service commission of west virginia due to recognized programming errors in the PHMSA portal used to submit this report: a7, a8, a21c, a22, d2a, d2b, d2c, d2d, d2e, d2f, d2g, d2h, d2i, e6.
Detailed record list
Occurred At
2021-07-18 16:51:00
Year
2021
Report Received Date
2021-08-17 00:00:00
Iyear
2021.0
Report Number
20210072.0
Supplemental Number
36946.0
Report Type
Supplemental Final
Operator Id
12878
Name
Mountaineer Gas Co
Operator Street Address
501 56th St. Se
Operator City Name
Charleston
Operator State Abbreviation
WV
Operator Postal Code
25304
Local Datetime
2021-07-18 16:51:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Street Address
103 Beaver Plaza
Location City Name
Beaver
Location County Name
Raleigh
Location State Abbreviation
WV
Location Postal Code
25813
Location Latitude
37.750002
Location Longitude
-81.137488
Flow Cont Main Valve Ind
Yes
Nrc Rpt Datetime
2021-07-18 17:59:00
Nrc Rpt Num
1311101
Additional Nrc Report Numbers
1311291
Commodity Released Type
Natural Gas
Unintentional Release
2.0
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
0
Num Er Injuries
0
Num Worker Injuries
0
Num Gp Injuries
1
Injure
1
Ignite Ind
Yes
Ignite Datetime
2021-07-18 16:51:00
How Extinguished
Local/state/federal Emergency Responder
Gas Consumed By Fire In Mcf
1
Explode Ind
Yes
Num Pub Evacuated
0.0
Incident Identified Datetime
2021-07-18 16:51:00
Communication State Fed Ind
Yes
Party Initiated Communication
Local/state/federal Emergency Responder
Initial Responder Com Datetime
2021-07-18 16:51:00
On Site Datetime
2021-07-18 16:51:00
Federal
No
Location Type
Private Property
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
38.0
Other Underground Facilities
Yes
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Main
Installation Year
1983.0
Manufactured Year
1978.0
Pipe Diameter
4.0
Pipe Specification
Astm D2513
Pipe Manufacturer
Plexco
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Plastic Sdr
11.5
Material Pe Pipe Code
2306
Release Type
Mechanical Puncture
Puncture Axial
3.0
Puncture Circum
1.5
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
111.0
Est Cost Emergency
626.0
Est Cost Other
0.0
Est Cost Other Details
0
Gas Cost In Mcf
6.739
Est Cost Unintentional Release
13.0
Est Cost Intentional Release
0.0
Prpty
750.0
Commercial Affected
15.0
Industrial Affected
0.0
Residences Affected
0.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
1.0
Num Resident Building Affctd
0.0
Num Business Building Affctd
15.0
Accident Psig
35.0
Normal Psig
35.0
Mop Psig
44.0
Mop Cfr Section
192.619(A)(4)
Maop Established Date
1998-06-23 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
None
Gas Odorized Level
0
Scada In Place Ind
No
Accident Identifier
Notification From Public
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Previous Damage Due To Excavation Activity
Ex Party Type
Previous Damage Due To Excavation Activity
Ex Hydrotest Leak Survey Date
2021-05-03 00:00:00
Ex Hydrotest Conducted Ind
No
Notify Cga Dirt
No
Public Util Easement Row Ind
Yes
Excavator Type
Unknown/other
Excavator Equipment
Unknown/other
Work Performed
Drainage
One Call Notified Ind
No
Service Interruption
Unknown/other
Root Cause Category
Excavation Issue
Root Cause Type
Improper Excavation Practice Not Listed Above
Osf Other Underground Ind
Yes
Preparer Name
P***** K******
Preparer Title
Manager Engineering
Preparer Email
P************@m****.com
Preparer Telephone
8884204427
Preparer Fax
3049259605
Local Contact Name
P*** T******
Local Contact Email
P**********@m****.com
Local Contact Telephone
8884204427
Authorizer Name
T***** W*******
Authorizer Title
Vice President Gas Supply And Technical Services
Authorizer Telephone
8884204427
Authorizer Email
T*************@m****.com
Narrative
At 16:20 july 18, 2021, operator's dispatch center received an odor of gas call from 123 beaver plaza, a united states post office serving the community of beaver, raleigh county, w.Va. A first responder was dispatched. At 16:51, raleigh county emergency services notified operator's dispatch center of a reported explosion at 103 beaver plaza. An operations manager also was dispatched. Operator's employees noted that a structure at 103 beaver plaza was visibly damaged. Emergency responders informed operator's employees that one person was injured and had been airlifted to cabell-huntington hospital. An odor of gas was detected at a nearby sewer manhole. Operator's employees also checked nearby businesses for gas with consistently negative results. There are two buildings located at 103 beaver plaza. The damaged building is located on the southern side of the property and houses a gambling establishment. A second building is located on the northern side of the property and houses only two restrooms, but at the time of the incident was boarded up. Operator has a 4-inch medium-pressure plastic gas distribution main in an easement immediately north of the second building. Operator's employees checked nearby sewer manholes and determined that gas was present in the area of the second building. Employees began excavating the main to determine the source of the leak. When the main was exposed, a sewer connection for the second building was found directly over the main. Concrete had been poured over the sewer connection. Operator's employees discovered a gouge in the main. A clamp was found covering the gouge. Fastenings on the clamp were corroded. The damaged section of main and the clamp were recovered and are being preserved. Prior to the completion of work at the site, operator's employees performed an odorization read, showing a .30 average threshold, .51 readily detectable. The answers to the following questions have been provided provisionally using guidance received on august 16, 2021 from mary friend, director of gas pipeline safety at the public service commission of west virginia due to recognized programming errors in the PHMSA portal used to submit this report: a7, a8, a21c, a22, d2a, d2b, d2c, d2d, d2e, d2f, d2g, d2h, d2i, e6.
| Occurred At | 2021-07-18 16:51:00 |
|---|---|
| Year | 2021 |
| Report Received Date | 2021-08-17 00:00:00 |
| Iyear | 2021.0 |
| Report Number | 20210072.0 |
| Supplemental Number | 36946.0 |
| Report Type | Supplemental Final |
| Operator Id | 12878 PHMSA Enforcement |
| Name | Mountaineer Gas Co |
| Operator Street Address | 501 56th St. Se |
| Operator City Name | Charleston |
| Operator State Abbreviation | WV |
| Operator Postal Code | 25304 |
| Local Datetime | 2021-07-18 16:51:00 |
| Time Zone | Eastern |
| Daylight Savings Ind | Yes |
| Location Street Address | 103 Beaver Plaza |
| Location City Name | Beaver |
| Location County Name | Raleigh |
| Location State Abbreviation | WV |
| Location Postal Code | 25813 |
| Location Latitude | 37.750002 Google Maps OpenStreetMap |
| Location Longitude | -81.137488 Google Maps OpenStreetMap |
| Flow Cont Main Valve Ind | Yes |
| Nrc Rpt Datetime | 2021-07-18 17:59:00 |
| Nrc Rpt Num | 1311101 NRC Report How to search |
| Additional Nrc Report Numbers | 1311291 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 2.0 |
| Intentional Release | 0.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | Yes |
| Num Emp Injuries | 0 |
| Num Contr Injuries | 0 |
| Num Er Injuries | 0 |
| Num Worker Injuries | 0 |
| Num Gp Injuries | 1 |
| Injure | 1 |
| Ignite Ind | Yes |
| Ignite Datetime | 2021-07-18 16:51:00 |
| How Extinguished | Local/state/federal Emergency Responder |
| Gas Consumed By Fire In Mcf | 1 |
| Explode Ind | Yes |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2021-07-18 16:51:00 |
| Communication State Fed Ind | Yes |
| Party Initiated Communication | Local/state/federal Emergency Responder |
| Initial Responder Com Datetime | 2021-07-18 16:51:00 |
| On Site Datetime | 2021-07-18 16:51:00 |
| Federal | No |
| Location Type | Private Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Pavement |
| Depth Of Cover | 38.0 |
| Other Underground Facilities | Yes |
| Crossing | No |
| Pipe Facility Type | Privately Owned |
| System Part Involved | Main |
| Installation Year | 1983.0 |
| Manufactured Year | 1978.0 |
| Pipe Diameter | 4.0 |
| Pipe Specification | Astm D2513 |
| Pipe Manufacturer | Plexco |
| Material Involved | Plastic |
| Plastic Type | Polyethylene (Pe) |
| Plastic Sdr | 11.5 |
| Material Pe Pipe Code | 2306 |
| Release Type | Mechanical Puncture |
| Puncture Axial | 3.0 |
| Puncture Circum | 1.5 |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 111.0 |
| Est Cost Emergency | 626.0 |
| Est Cost Other | 0.0 |
| Est Cost Other Details | 0 |
| Gas Cost In Mcf | 6.739 |
| Est Cost Unintentional Release | 13.0 |
| Est Cost Intentional Release | 0.0 |
| Prpty | 750.0 |
| Commercial Affected | 15.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 0.0 |
| Num Persons Hosp Not Ovnght | 0.0 |
| Num Injured Treated By Emt | 1.0 |
| Num Resident Building Affctd | 0.0 |
| Num Business Building Affctd | 15.0 |
| Accident Psig | 35.0 |
| Normal Psig | 35.0 |
| Mop Psig | 44.0 |
| Mop Cfr Section | 192.619(A)(4) View CFR 49 §192 |
| Maop Established Date | 1998-06-23 00:00:00 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Gas Odorized System Type | None |
| Gas Odorized Level | 0 |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Public |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Excavation Damage |
| Cause Details | Previous Damage Due To Excavation Activity |
| Ex Party Type | Previous Damage Due To Excavation Activity |
| Ex Hydrotest Leak Survey Date | 2021-05-03 00:00:00 |
| Ex Hydrotest Conducted Ind | No |
| Notify Cga Dirt | No |
| Public Util Easement Row Ind | Yes |
| Excavator Type | Unknown/other |
| Excavator Equipment | Unknown/other |
| Work Performed | Drainage |
| One Call Notified Ind | No |
| Service Interruption | Unknown/other |
| Root Cause Category | Excavation Issue |
| Root Cause Type | Improper Excavation Practice Not Listed Above |
| Osf Other Underground Ind | Yes |
| Preparer Name | P***** K****** |
| Preparer Title | Manager Engineering |
| Preparer Email | P************@m****.com |
| Preparer Telephone | 8884204427 |
| Preparer Fax | 3049259605 |
| Local Contact Name | P*** T****** |
| Local Contact Email | P**********@m****.com |
| Local Contact Telephone | 8884204427 |
| Authorizer Name | T***** W******* |
| Authorizer Title | Vice President Gas Supply And Technical Services |
| Authorizer Telephone | 8884204427 |
| Authorizer Email | T*************@m****.com |
| Narrative | At 16:20 july 18, 2021, operator's dispatch center received an odor of gas call from 123 beaver plaza, a united states post office serving the community of beaver, raleigh county, w.Va. A first responder was dispatched. At 16:51, raleigh county emergency services notified operator's dispatch center of a reported explosion at 103 beaver plaza. An operations manager also was dispatched. Operator's employees noted that a structure at 103 beaver plaza was visibly damaged. Emergency responders informed operator's employees that one person was injured and had been airlifted to cabell-huntington hospital. An odor of gas was detected at a nearby sewer manhole. Operator's employees also checked nearby businesses for gas with consistently negative results. There are two buildings located at 103 beaver plaza. The damaged building is located on the southern side of the property and houses a gambling establishment. A second building is located on the northern side of the property and houses only two restrooms, but at the time of the incident was boarded up. Operator has a 4-inch medium-pressure plastic gas distribution main in an easement immediately north of the second building. Operator's employees checked nearby sewer manholes and determined that gas was present in the area of the second building. Employees began excavating the main to determine the source of the leak. When the main was exposed, a sewer connection for the second building was found directly over the main. Concrete had been poured over the sewer connection. Operator's employees discovered a gouge in the main. A clamp was found covering the gouge. Fastenings on the clamp were corroded. The damaged section of main and the clamp were recovered and are being preserved. Prior to the completion of work at the site, operator's employees performed an odorization read, showing a .30 average threshold, .51 readily detectable. The answers to the following questions have been provided provisionally using guidance received on august 16, 2021 from mary friend, director of gas pipeline safety at the public service commission of west virginia due to recognized programming errors in the PHMSA portal used to submit this report: a7, a8, a21c, a22, d2a, d2b, d2c, d2d, d2e, d2f, d2g, d2h, d2i, e6. |