GD incident on 2021-07-18 — WV

Operator
Mountaineer Gas Co
Cause
Excavation Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 1 injury
Property damage (nominal)
$111
Incident datetime
2021-07-18 16:51
Report number
Location
WV, RALEIGH
Narrative
At 16:20 july 18, 2021, operator's dispatch center received an odor of gas call from 123 beaver plaza, a united states post office serving the community of beaver, raleigh county, w.Va. A first responder was dispatched. At 16:51, raleigh county emergency services notified operator's dispatch center of a reported explosion at 103 beaver plaza. An operations manager also was dispatched. Operator's employees noted that a structure at 103 beaver plaza was visibly damaged. Emergency responders informed operator's employees that one person was injured and had been airlifted to cabell-huntington hospital. An odor of gas was detected at a nearby sewer manhole. Operator's employees also checked nearby businesses for gas with consistently negative results. There are two buildings located at 103 beaver plaza. The damaged building is located on the southern side of the property and houses a gambling establishment. A second building is located on the northern side of the property and houses only two restrooms, but at the time of the incident was boarded up. Operator has a 4-inch medium-pressure plastic gas distribution main in an easement immediately north of the second building. Operator's employees checked nearby sewer manholes and determined that gas was present in the area of the second building. Employees began excavating the main to determine the source of the leak. When the main was exposed, a sewer connection for the second building was found directly over the main. Concrete had been poured over the sewer connection. Operator's employees discovered a gouge in the main. A clamp was found covering the gouge. Fastenings on the clamp were corroded. The damaged section of main and the clamp were recovered and are being preserved. Prior to the completion of work at the site, operator's employees performed an odorization read, showing a .30 average threshold, .51 readily detectable. The answers to the following questions have been provided provisionally using guidance received on august 16, 2021 from mary friend, director of gas pipeline safety at the public service commission of west virginia due to recognized programming errors in the PHMSA portal used to submit this report: a7, a8, a21c, a22, d2a, d2b, d2c, d2d, d2e, d2f, d2g, d2h, d2i, e6.
Detailed record list
Occurred At
2021-07-18 16:51:00
Year
2021
Report Received Date
2021-08-17 00:00:00
Iyear
2021.0
Report Number
20210072.0
Supplemental Number
36946.0
Report Type
Supplemental Final
Operator Id
Name
Mountaineer Gas Co
Operator Street Address
501 56th St. Se
Operator City Name
Charleston
Operator State Abbreviation
WV
Operator Postal Code
25304
Local Datetime
2021-07-18 16:51:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Street Address
103 Beaver Plaza
Location City Name
Beaver
Location County Name
Raleigh
Location State Abbreviation
WV
Location Postal Code
25813
Location Latitude
Location Longitude
Flow Cont Main Valve Ind
Yes
Nrc Rpt Datetime
2021-07-18 17:59:00
Nrc Rpt Num
Additional Nrc Report Numbers
1311291
Commodity Released Type
Natural Gas
Unintentional Release
2.0
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
0
Num Er Injuries
0
Num Worker Injuries
0
Num Gp Injuries
1
Injure
1
Ignite Ind
Yes
Ignite Datetime
2021-07-18 16:51:00
How Extinguished
Local/state/federal Emergency Responder
Gas Consumed By Fire In Mcf
1
Explode Ind
Yes
Num Pub Evacuated
0.0
Incident Identified Datetime
2021-07-18 16:51:00
Communication State Fed Ind
Yes
Party Initiated Communication
Local/state/federal Emergency Responder
Initial Responder Com Datetime
2021-07-18 16:51:00
On Site Datetime
2021-07-18 16:51:00
Federal
No
Location Type
Private Property
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
38.0
Other Underground Facilities
Yes
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Main
Installation Year
1983.0
Manufactured Year
1978.0
Pipe Diameter
4.0
Pipe Specification
Astm D2513
Pipe Manufacturer
Plexco
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Plastic Sdr
11.5
Material Pe Pipe Code
2306
Release Type
Mechanical Puncture
Puncture Axial
3.0
Puncture Circum
1.5
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
111.0
Est Cost Emergency
626.0
Est Cost Other
0.0
Est Cost Other Details
0
Gas Cost In Mcf
6.739
Est Cost Unintentional Release
13.0
Est Cost Intentional Release
0.0
Prpty
750.0
Commercial Affected
15.0
Industrial Affected
0.0
Residences Affected
0.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
1.0
Num Resident Building Affctd
0.0
Num Business Building Affctd
15.0
Accident Psig
35.0
Normal Psig
35.0
Mop Psig
44.0
Mop Cfr Section
192.619(A)(4)
Maop Established Date
1998-06-23 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
None
Gas Odorized Level
0
Scada In Place Ind
No
Accident Identifier
Notification From Public
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Previous Damage Due To Excavation Activity
Ex Party Type
Previous Damage Due To Excavation Activity
Ex Hydrotest Leak Survey Date
2021-05-03 00:00:00
Ex Hydrotest Conducted Ind
No
Notify Cga Dirt
No
Public Util Easement Row Ind
Yes
Excavator Type
Unknown/other
Excavator Equipment
Unknown/other
Work Performed
Drainage
One Call Notified Ind
No
Service Interruption
Unknown/other
Root Cause Category
Excavation Issue
Root Cause Type
Improper Excavation Practice Not Listed Above
Osf Other Underground Ind
Yes
Preparer Name
P***** K******
Preparer Title
Manager Engineering
Preparer Email
P************@m****.com
Preparer Telephone
8884204427
Preparer Fax
3049259605
Local Contact Name
P*** T******
Local Contact Email
P**********@m****.com
Local Contact Telephone
8884204427
Authorizer Name
T***** W*******
Authorizer Title
Vice President Gas Supply And Technical Services
Authorizer Telephone
8884204427
Authorizer Email
T*************@m****.com
Narrative
At 16:20 july 18, 2021, operator's dispatch center received an odor of gas call from 123 beaver plaza, a united states post office serving the community of beaver, raleigh county, w.Va. A first responder was dispatched. At 16:51, raleigh county emergency services notified operator's dispatch center of a reported explosion at 103 beaver plaza. An operations manager also was dispatched. Operator's employees noted that a structure at 103 beaver plaza was visibly damaged. Emergency responders informed operator's employees that one person was injured and had been airlifted to cabell-huntington hospital. An odor of gas was detected at a nearby sewer manhole. Operator's employees also checked nearby businesses for gas with consistently negative results. There are two buildings located at 103 beaver plaza. The damaged building is located on the southern side of the property and houses a gambling establishment. A second building is located on the northern side of the property and houses only two restrooms, but at the time of the incident was boarded up. Operator has a 4-inch medium-pressure plastic gas distribution main in an easement immediately north of the second building. Operator's employees checked nearby sewer manholes and determined that gas was present in the area of the second building. Employees began excavating the main to determine the source of the leak. When the main was exposed, a sewer connection for the second building was found directly over the main. Concrete had been poured over the sewer connection. Operator's employees discovered a gouge in the main. A clamp was found covering the gouge. Fastenings on the clamp were corroded. The damaged section of main and the clamp were recovered and are being preserved. Prior to the completion of work at the site, operator's employees performed an odorization read, showing a .30 average threshold, .51 readily detectable. The answers to the following questions have been provided provisionally using guidance received on august 16, 2021 from mary friend, director of gas pipeline safety at the public service commission of west virginia due to recognized programming errors in the PHMSA portal used to submit this report: a7, a8, a21c, a22, d2a, d2b, d2c, d2d, d2e, d2f, d2g, d2h, d2i, e6.
Occurred At 2021-07-18 16:51:00
Year 2021
Report Received Date 2021-08-17 00:00:00
Iyear 2021.0
Report Number 20210072.0
Supplemental Number 36946.0
Report Type Supplemental Final
Operator Id 12878 PHMSA Enforcement
Name Mountaineer Gas Co
Operator Street Address 501 56th St. Se
Operator City Name Charleston
Operator State Abbreviation WV
Operator Postal Code 25304
Local Datetime 2021-07-18 16:51:00
Time Zone Eastern
Daylight Savings Ind Yes
Location Street Address 103 Beaver Plaza
Location City Name Beaver
Location County Name Raleigh
Location State Abbreviation WV
Location Postal Code 25813
Location Latitude 37.750002 Google Maps OpenStreetMap
Location Longitude -81.137488 Google Maps OpenStreetMap
Flow Cont Main Valve Ind Yes
Nrc Rpt Datetime 2021-07-18 17:59:00
Nrc Rpt Num 1311101 NRC Report How to search
Additional Nrc Report Numbers 1311291
Commodity Released Type Natural Gas
Unintentional Release 2.0
Intentional Release 0.0
Fatality Ind No
Fatal 0
Injury Ind Yes
Num Emp Injuries 0
Num Contr Injuries 0
Num Er Injuries 0
Num Worker Injuries 0
Num Gp Injuries 1
Injure 1
Ignite Ind Yes
Ignite Datetime 2021-07-18 16:51:00
How Extinguished Local/state/federal Emergency Responder
Gas Consumed By Fire In Mcf 1
Explode Ind Yes
Num Pub Evacuated 0.0
Incident Identified Datetime 2021-07-18 16:51:00
Communication State Fed Ind Yes
Party Initiated Communication Local/state/federal Emergency Responder
Initial Responder Com Datetime 2021-07-18 16:51:00
On Site Datetime 2021-07-18 16:51:00
Federal No
Location Type Private Property
Incident Area Type Underground
Incident Area Subtype Under Pavement
Depth Of Cover 38.0
Other Underground Facilities Yes
Crossing No
Pipe Facility Type Privately Owned
System Part Involved Main
Installation Year 1983.0
Manufactured Year 1978.0
Pipe Diameter 4.0
Pipe Specification Astm D2513
Pipe Manufacturer Plexco
Material Involved Plastic
Plastic Type Polyethylene (Pe)
Plastic Sdr 11.5
Material Pe Pipe Code 2306
Release Type Mechanical Puncture
Puncture Axial 3.0
Puncture Circum 1.5
Class Location Type Class 3 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 111.0
Est Cost Emergency 626.0
Est Cost Other 0.0
Est Cost Other Details 0
Gas Cost In Mcf 6.739
Est Cost Unintentional Release 13.0
Est Cost Intentional Release 0.0
Prpty 750.0
Commercial Affected 15.0
Industrial Affected 0.0
Residences Affected 0.0
Num Persons Hosp Not Ovnght 0.0
Num Injured Treated By Emt 1.0
Num Resident Building Affctd 0.0
Num Business Building Affctd 15.0
Accident Psig 35.0
Normal Psig 35.0
Mop Psig 44.0
Mop Cfr Section 192.619(A)(4) View CFR 49 §192
Maop Established Date 1998-06-23 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type None
Gas Odorized Level 0
Scada In Place Ind No
Accident Identifier Notification From Public
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Excavation Damage
Cause Details Previous Damage Due To Excavation Activity
Ex Party Type Previous Damage Due To Excavation Activity
Ex Hydrotest Leak Survey Date 2021-05-03 00:00:00
Ex Hydrotest Conducted Ind No
Notify Cga Dirt No
Public Util Easement Row Ind Yes
Excavator Type Unknown/other
Excavator Equipment Unknown/other
Work Performed Drainage
One Call Notified Ind No
Service Interruption Unknown/other
Root Cause Category Excavation Issue
Root Cause Type Improper Excavation Practice Not Listed Above
Osf Other Underground Ind Yes
Preparer Name P***** K******
Preparer Title Manager Engineering
Preparer Email P************@m****.com
Preparer Telephone 8884204427
Preparer Fax 3049259605
Local Contact Name P*** T******
Local Contact Email P**********@m****.com
Local Contact Telephone 8884204427
Authorizer Name T***** W*******
Authorizer Title Vice President Gas Supply And Technical Services
Authorizer Telephone 8884204427
Authorizer Email T*************@m****.com
Narrative At 16:20 july 18, 2021, operator's dispatch center received an odor of gas call from 123 beaver plaza, a united states post office serving the community of beaver, raleigh county, w.Va. A first responder was dispatched. At 16:51, raleigh county emergency services notified operator's dispatch center of a reported explosion at 103 beaver plaza. An operations manager also was dispatched. Operator's employees noted that a structure at 103 beaver plaza was visibly damaged. Emergency responders informed operator's employees that one person was injured and had been airlifted to cabell-huntington hospital. An odor of gas was detected at a nearby sewer manhole. Operator's employees also checked nearby businesses for gas with consistently negative results. There are two buildings located at 103 beaver plaza. The damaged building is located on the southern side of the property and houses a gambling establishment. A second building is located on the northern side of the property and houses only two restrooms, but at the time of the incident was boarded up. Operator has a 4-inch medium-pressure plastic gas distribution main in an easement immediately north of the second building. Operator's employees checked nearby sewer manholes and determined that gas was present in the area of the second building. Employees began excavating the main to determine the source of the leak. When the main was exposed, a sewer connection for the second building was found directly over the main. Concrete had been poured over the sewer connection. Operator's employees discovered a gouge in the main. A clamp was found covering the gouge. Fastenings on the clamp were corroded. The damaged section of main and the clamp were recovered and are being preserved. Prior to the completion of work at the site, operator's employees performed an odorization read, showing a .30 average threshold, .51 readily detectable. The answers to the following questions have been provided provisionally using guidance received on august 16, 2021 from mary friend, director of gas pipeline safety at the public service commission of west virginia due to recognized programming errors in the PHMSA portal used to submit this report: a7, a8, a21c, a22, d2a, d2b, d2c, d2d, d2e, d2f, d2g, d2h, d2i, e6.