GD incident on 2021-02-28 — KY

Operator
Columbia Gas Of Kentucky Inc
Cause
Excavation Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 2 injuries
Property damage (nominal)
$43
Incident datetime
2021-02-28 13:00
Report number
Location
KY, KNOT
Narrative
Columbia gas of kentucky (cky) received notice on february 28th, 2021 at 12:43 pm of a gas fire at 6560 state route 899. A cky service tech was dispatched and arrived on scene at 12:50 pm. Upon arrival the cky service tech was advised by the fire chief of pippa passes volunteer fire department (ppvfd) that they had responded to a house fire at 6560 sr 899 at approximately 5:00 am on february 27, 2021. Two people were hospitalized as a result of the fire. Ppvfd put the fire out, did not observe any gas service and left the scene. Ppvfd was dispatched to the same location on february 28, 2021 at approximately 12:00 pm due to a call received by a neighbor regarding a small fire at the house site. When the ppvfd arrived on site, they observed a small "pilot" like flame coming from the ground. When they approached the flame went out. Ppvfd stated that they relit the area and had a 12 inch flash of fire and it went back out. At that point, the ppvfd contacted cky. The cky service tech immediately secured the area and sent out notifications of the emergency. He then began a perimeter check of the area and noticed fresh excavation in the area of a cky two inch plastic main with high concentrations of gas escaping through a pvc pipe protruding from the ground located in this area. The cky service tech advised the ppvfd to shut down ky state route 899. The ky psc arrived on site and advised cky to secure the area and await the arrival of the state fire marshall prior to any excavation activity. The decision was made to shut off the gas main feeding this area, and the fire marshal advised they would be on site at 10:00 am on march 1, 2021. The fire marshal completed their initial assessment on march 1, 2021 and notified cky to proceed with repairs. A vacuum truck was utilized to expose cky's assets and discovered the service line for 6529 state route 899, which was a one inch plastic natural gas service line, had been struck and an unauthorized attempt to repair the one inch service line had been performed. It was observed that an unapproved eighteen inch section of one inch plastic piping and two unapproved brass water couplings were utilized in an attempt to repair the damaged service line. Upon further investigation, it was observed that one end of the piping had pulled apart from the coupling. Cky cut out the section of piping and repaired as per our standard. Service was restored at 09:15 pm on march 1, 2021.
Detailed record list
Occurred At
2021-02-28 13:00:00
Year
2021
Report Received Date
2021-03-26 00:00:00
Iyear
2021.0
Report Number
20210035.0
Supplemental Number
35742.0
Report Type
Supplemental Final
Operator Id
Name
Columbia Gas Of Kentucky Inc
Operator Street Address
2001 Mercer Road
Operator City Name
Lexington
Operator State Abbreviation
KY
Operator Postal Code
40511
Local Datetime
2021-02-27 05:00:00
Time Zone
Eastern
Daylight Savings Ind
No
Location Street Address
6520 State Road 899
Location City Name
Pippa Passes
Location County Name
Knot
Location State Abbreviation
KY
Location Postal Code
41844
Location Latitude
Location Longitude
Flow Cont Key Crit Ind
Yes
Nrc Rpt Datetime
2021-02-28 13:53:00
Nrc Rpt Num
Additional Nrc Report Numbers
1299365
Commodity Released Type
Natural Gas
Unintentional Release
75.3
Intentional Release
22.0
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
0
Num Er Injuries
0
Num Worker Injuries
0
Num Gp Injuries
2
Injure
2
Ignite Ind
Yes
Ignite Datetime
2021-02-27 05:00:00
How Extinguished
Local/state/federal Emergency Responder
Gas Consumed By Fire In Mcf
1
Explode Ind
Yes
Num Pub Evacuated
2.0
Incident Identified Datetime
2021-02-28 13:00:00
On Site Datetime
2021-02-28 13:05:00
Federal
No
Location Type
Private Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
22.0
Other Underground Facilities
Yes
Crossing
No
Pipe Facility Type
Privately Owned
System Part Involved
Service
Installation Year
2001.0
Manufactured Year
1995.0
Customer Type
Single Family Residential
Was Efv Installed Before Ind
No
Curb Valve Inst Before Inc Ind
Yes
Pipe Diameter
1.0
Pipe Specification
Astm D2513
Pipe Manufacturer
Unknown
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Wt Plastic
0.099
Material Pe Pipe Code
2406
Release Type
Leak
Leak Type
Connection Failure
Class Location Type
Class 3 Location
Est Cost Oper Paid
65000.0
Est Cost Prop Damage
43.0
Est Cost Emergency
10450.0
Est Cost Other
0.0
Gas Cost In Mcf
2.57
Est Cost Unintentional Release
194.0
Est Cost Intentional Release
57.0
Prpty
75744.0
Commercial Affected
1.0
Industrial Affected
0.0
Residences Affected
6.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
6.0
Num Business Building Affctd
1.0
Accident Psig
8.0
Normal Psig
8.0
Mop Psig
13.0
Mop Cfr Section
Maop Established Date
1993-08-20 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Other
Gas Odorized Sys Other Detail
Natural
Gas Odorized Level
5
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Columbia gas of kentucky reviewed the pressure trend from scada at the upstream regulator station r1429, from january 01, 2020 through march 15, 2021. There was no indication of the outlet pressure going beyond the set points of the control and monitor regulators.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Previous Damage Due To Excavation Activity
Ex Party Type
Previous Damage Due To Excavation Activity
Ex Hydrotest Leak Survey Date
2020-08-28 00:00:00
Ex Hydrotest Conducted Ind
No
Notify Cga Dirt
Yes
Public Row Ind
Yes
Public Subtype
State Highway
Pipeline Easement Row Ind
Yes
Excavator Type
Municipality
Excavator Equipment
Unknown/other
Work Performed
Sewer (Sanitary/storm)
One Call Notified Ind
Yes
One Call Ticket Num
2101041372
Locator Type
Utility Owner
Visible Marks
Yes
Service Interruption
Yes
Service Interruption Hours
26.0
Root Cause Category
Excavation Issue
Root Cause Type
Improper Excavation Practice Not Listed Above
Excvtn Dmg Previous Damage Ind
Yes
Preparer Name
R*** T****
Preparer Title
Manager Operations Compliance
Preparer Email
R******@n*******.com
Preparer Telephone
8595334022
Local Contact Name
R*** T****
Local Contact Email
R******@n*******.com
Local Contact Telephone
8595334022
Authorizer Name
R*** T****
Authorizer Title
Manager Operations Compliance
Authorizer Telephone
8595334022
Authorizer Email
R******@n*******.com
Narrative
Columbia gas of kentucky (cky) received notice on february 28th, 2021 at 12:43 pm of a gas fire at 6560 state route 899. A cky service tech was dispatched and arrived on scene at 12:50 pm. Upon arrival the cky service tech was advised by the fire chief of pippa passes volunteer fire department (ppvfd) that they had responded to a house fire at 6560 sr 899 at approximately 5:00 am on february 27, 2021. Two people were hospitalized as a result of the fire. Ppvfd put the fire out, did not observe any gas service and left the scene. Ppvfd was dispatched to the same location on february 28, 2021 at approximately 12:00 pm due to a call received by a neighbor regarding a small fire at the house site. When the ppvfd arrived on site, they observed a small "pilot" like flame coming from the ground. When they approached the flame went out. Ppvfd stated that they relit the area and had a 12 inch flash of fire and it went back out. At that point, the ppvfd contacted cky. The cky service tech immediately secured the area and sent out notifications of the emergency. He then began a perimeter check of the area and noticed fresh excavation in the area of a cky two inch plastic main with high concentrations of gas escaping through a pvc pipe protruding from the ground located in this area. The cky service tech advised the ppvfd to shut down ky state route 899. The ky psc arrived on site and advised cky to secure the area and await the arrival of the state fire marshall prior to any excavation activity. The decision was made to shut off the gas main feeding this area, and the fire marshal advised they would be on site at 10:00 am on march 1, 2021. The fire marshal completed their initial assessment on march 1, 2021 and notified cky to proceed with repairs. A vacuum truck was utilized to expose cky's assets and discovered the service line for 6529 state route 899, which was a one inch plastic natural gas service line, had been struck and an unauthorized attempt to repair the one inch service line had been performed. It was observed that an unapproved eighteen inch section of one inch plastic piping and two unapproved brass water couplings were utilized in an attempt to repair the damaged service line. Upon further investigation, it was observed that one end of the piping had pulled apart from the coupling. Cky cut out the section of piping and repaired as per our standard. Service was restored at 09:15 pm on march 1, 2021.
Occurred At 2021-02-28 13:00:00
Year 2021
Report Received Date 2021-03-26 00:00:00
Iyear 2021.0
Report Number 20210035.0
Supplemental Number 35742.0
Report Type Supplemental Final
Operator Id 2585 PHMSA Enforcement
Name Columbia Gas Of Kentucky Inc
Operator Street Address 2001 Mercer Road
Operator City Name Lexington
Operator State Abbreviation KY
Operator Postal Code 40511
Local Datetime 2021-02-27 05:00:00
Time Zone Eastern
Daylight Savings Ind No
Location Street Address 6520 State Road 899
Location City Name Pippa Passes
Location County Name Knot
Location State Abbreviation KY
Location Postal Code 41844
Location Latitude 37.3454759 Google Maps OpenStreetMap
Location Longitude -82.8681908 Google Maps OpenStreetMap
Flow Cont Key Crit Ind Yes
Nrc Rpt Datetime 2021-02-28 13:53:00
Nrc Rpt Num 1299227 NRC Report How to search
Additional Nrc Report Numbers 1299365
Commodity Released Type Natural Gas
Unintentional Release 75.3
Intentional Release 22.0
Fatality Ind No
Fatal 0
Injury Ind Yes
Num Emp Injuries 0
Num Contr Injuries 0
Num Er Injuries 0
Num Worker Injuries 0
Num Gp Injuries 2
Injure 2
Ignite Ind Yes
Ignite Datetime 2021-02-27 05:00:00
How Extinguished Local/state/federal Emergency Responder
Gas Consumed By Fire In Mcf 1
Explode Ind Yes
Num Pub Evacuated 2.0
Incident Identified Datetime 2021-02-28 13:00:00
On Site Datetime 2021-02-28 13:05:00
Federal No
Location Type Private Property
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 22.0
Other Underground Facilities Yes
Crossing No
Pipe Facility Type Privately Owned
System Part Involved Service
Installation Year 2001.0
Manufactured Year 1995.0
Customer Type Single Family Residential
Was Efv Installed Before Ind No
Curb Valve Inst Before Inc Ind Yes
Pipe Diameter 1.0
Pipe Specification Astm D2513
Pipe Manufacturer Unknown
Material Involved Plastic
Plastic Type Polyethylene (Pe)
Wt Plastic 0.099
Material Pe Pipe Code 2406
Release Type Leak
Leak Type Connection Failure
Class Location Type Class 3 Location
Est Cost Oper Paid 65000.0
Est Cost Prop Damage 43.0
Est Cost Emergency 10450.0
Est Cost Other 0.0
Gas Cost In Mcf 2.57
Est Cost Unintentional Release 194.0
Est Cost Intentional Release 57.0
Prpty 75744.0
Commercial Affected 1.0
Industrial Affected 0.0
Residences Affected 6.0
Num Persons Hosp Not Ovnght 0.0
Num Injured Treated By Emt 0.0
Num Resident Building Affctd 6.0
Num Business Building Affctd 1.0
Accident Psig 8.0
Normal Psig 8.0
Mop Psig 13.0
Mop Cfr Section 192.621 M View CFR 49 §192
Maop Established Date 1993-08-20 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type Other
Gas Odorized Sys Other Detail Natural
Gas Odorized Level 5
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Notification From Emergency Responder
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Columbia gas of kentucky reviewed the pressure trend from scada at the upstream regulator station r1429, from january 01, 2020 through march 15, 2021. There was no indication of the outlet pressure going beyond the set points of the control and monitor regulators.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Excavation Damage
Cause Details Previous Damage Due To Excavation Activity
Ex Party Type Previous Damage Due To Excavation Activity
Ex Hydrotest Leak Survey Date 2020-08-28 00:00:00
Ex Hydrotest Conducted Ind No
Notify Cga Dirt Yes
Public Row Ind Yes
Public Subtype State Highway
Pipeline Easement Row Ind Yes
Excavator Type Municipality
Excavator Equipment Unknown/other
Work Performed Sewer (Sanitary/storm)
One Call Notified Ind Yes
One Call Ticket Num 2101041372
Locator Type Utility Owner
Visible Marks Yes
Service Interruption Yes
Service Interruption Hours 26.0
Root Cause Category Excavation Issue
Root Cause Type Improper Excavation Practice Not Listed Above
Excvtn Dmg Previous Damage Ind Yes
Preparer Name R*** T****
Preparer Title Manager Operations Compliance
Preparer Email R******@n*******.com
Preparer Telephone 8595334022
Local Contact Name R*** T****
Local Contact Email R******@n*******.com
Local Contact Telephone 8595334022
Authorizer Name R*** T****
Authorizer Title Manager Operations Compliance
Authorizer Telephone 8595334022
Authorizer Email R******@n*******.com
Narrative Columbia gas of kentucky (cky) received notice on february 28th, 2021 at 12:43 pm of a gas fire at 6560 state route 899. A cky service tech was dispatched and arrived on scene at 12:50 pm. Upon arrival the cky service tech was advised by the fire chief of pippa passes volunteer fire department (ppvfd) that they had responded to a house fire at 6560 sr 899 at approximately 5:00 am on february 27, 2021. Two people were hospitalized as a result of the fire. Ppvfd put the fire out, did not observe any gas service and left the scene. Ppvfd was dispatched to the same location on february 28, 2021 at approximately 12:00 pm due to a call received by a neighbor regarding a small fire at the house site. When the ppvfd arrived on site, they observed a small "pilot" like flame coming from the ground. When they approached the flame went out. Ppvfd stated that they relit the area and had a 12 inch flash of fire and it went back out. At that point, the ppvfd contacted cky. The cky service tech immediately secured the area and sent out notifications of the emergency. He then began a perimeter check of the area and noticed fresh excavation in the area of a cky two inch plastic main with high concentrations of gas escaping through a pvc pipe protruding from the ground located in this area. The cky service tech advised the ppvfd to shut down ky state route 899. The ky psc arrived on site and advised cky to secure the area and await the arrival of the state fire marshall prior to any excavation activity. The decision was made to shut off the gas main feeding this area, and the fire marshal advised they would be on site at 10:00 am on march 1, 2021. The fire marshal completed their initial assessment on march 1, 2021 and notified cky to proceed with repairs. A vacuum truck was utilized to expose cky's assets and discovered the service line for 6529 state route 899, which was a one inch plastic natural gas service line, had been struck and an unauthorized attempt to repair the one inch service line had been performed. It was observed that an unapproved eighteen inch section of one inch plastic piping and two unapproved brass water couplings were utilized in an attempt to repair the damaged service line. Upon further investigation, it was observed that one end of the piping had pulled apart from the coupling. Cky cut out the section of piping and repaired as per our standard. Service was restored at 09:15 pm on march 1, 2021.