Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2021-01-17 — NY
Operator
Niagara Mohawk Power Corp
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$12,100
Incident datetime
2021-01-17 03:45
Report number
Location
NY, NEW YORK
Narrative
On january 17, national grid received notification of a gas related fire with main blowing gas. The cause of the fire was a primary electrical wire making contact above the 6" steel main resulting in the fire occurring. Approx. 17 houses were evacuated (18 residents), a 2" bypass was run to avoid customer interruptions, and temporary repairs were made. Temporary repairs were completed with a made safe time of 16:25. Additionally, the south park street bridge was closed as a result of this incident. For part e, question 5, odorant is injected at either biddlecum gate station or crogham gate station. The damaged pipeline segment was replaced with a 5'6" segment of 6" apix62 smaw 6010/7010 pipe with cold applied tape coating early february, 2021. The segment was air tested at 90 psi for 1 hour.
Detailed record list
Occurred At
2021-01-17 03:45:00
Year
2021
Report Received Date
2021-02-16 00:00:00
Iyear
2021.0
Report Number
20210019.0
Supplemental Number
34936.0
Report Type
Supplemental Final
Operator Id
13480
Name
Niagara Mohawk Power Corp
Operator Street Address
300 Erie Boulevard West
Operator City Name
Syracuse
Operator State Abbreviation
NY
Operator Postal Code
13202
Local Datetime
2021-01-17 04:14:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Street Address
South Park St Bridge Bet Spring St And Grange Avenue
Location City Name
Adams
Location County Name
New York
Location State Abbreviation
NY
Location Postal Code
13605
Location Latitude
43.80773
Location Longitude
-76.0193
Flow Cont Stopple Fitng Ind
Yes
Nrc Rpt Datetime
2021-01-17 12:30:00
Nrc Rpt Num
1296212
Additional Nrc Report Numbers
1296291
Commodity Released Type
Natural Gas
Unintentional Release
22.4
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Ignite Datetime
2021-01-17 03:45:00
How Extinguished
Allowed To Burn Out
Gas Consumed By Fire In Mcf
22.4
Explode Ind
No
Num Pub Evacuated
18.0
Incident Identified Datetime
2021-01-17 03:45:00
On Site Datetime
2021-01-17 04:25:00
Federal
No
Location Type
Public Property
Incident Area Type
Aboveground
Incident Area Subtype
Overhead Crossing
Crossing
Yes
Bridge Crossing Ind
Yes
Bridge Type
Uncased
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
1955.0
Pipe Diameter
6.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Seamless
Wt Steel
0.28
Release Type
Leak
Leak Type
Pinhole
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
12100.0
Est Cost Emergency
39070.0
Est Cost Other
0.0
Gas Cost In Mcf
2.3
Est Cost Unintentional Release
52.0
Est Cost Intentional Release
0.0
Prpty
51222.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
17.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
18.0
Num Business Building Affctd
0.0
Accident Psig
20.0
Normal Psig
21.0
Mop Psig
24.0
Mop Cfr Section
192.619(C)
Maop Established Date
1955-01-01 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The incident was due to inclement weather with winds blowing down a power line and not involving the control room operator.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Electrical Arcing From Other Equipment Or Facility
Outside Force Type
Electrical Arcing From Other Equipment Or Facility
Preparer Name
C****** B*****
Preparer Title
Prin Program Manager Regulatory Moc
Preparer Email
C*************@n***********.com
Preparer Telephone
5169030596
Local Contact Name
C****** B*****
Local Contact Email
C*************@n***********.com
Local Contact Telephone
5169030596
Authorizer Name
C****** B*****
Authorizer Title
Prin. Program Mgr Regulatory Management Of Change
Authorizer Telephone
5164924469
Authorizer Email
C*************@n***********.com
Narrative
On january 17, national grid received notification of a gas related fire with main blowing gas. The cause of the fire was a primary electrical wire making contact above the 6" steel main resulting in the fire occurring. Approx. 17 houses were evacuated (18 residents), a 2" bypass was run to avoid customer interruptions, and temporary repairs were made. Temporary repairs were completed with a made safe time of 16:25. Additionally, the south park street bridge was closed as a result of this incident. For part e, question 5, odorant is injected at either biddlecum gate station or crogham gate station. The damaged pipeline segment was replaced with a 5'6" segment of 6" apix62 smaw 6010/7010 pipe with cold applied tape coating early february, 2021. The segment was air tested at 90 psi for 1 hour.
| Occurred At | 2021-01-17 03:45:00 |
|---|---|
| Year | 2021 |
| Report Received Date | 2021-02-16 00:00:00 |
| Iyear | 2021.0 |
| Report Number | 20210019.0 |
| Supplemental Number | 34936.0 |
| Report Type | Supplemental Final |
| Operator Id | 13480 PHMSA Enforcement |
| Name | Niagara Mohawk Power Corp |
| Operator Street Address | 300 Erie Boulevard West |
| Operator City Name | Syracuse |
| Operator State Abbreviation | NY |
| Operator Postal Code | 13202 |
| Local Datetime | 2021-01-17 04:14:00 |
| Time Zone | Eastern |
| Daylight Savings Ind | Yes |
| Location Street Address | South Park St Bridge Bet Spring St And Grange Avenue |
| Location City Name | Adams |
| Location County Name | New York |
| Location State Abbreviation | NY |
| Location Postal Code | 13605 |
| Location Latitude | 43.80773 Google Maps OpenStreetMap |
| Location Longitude | -76.0193 Google Maps OpenStreetMap |
| Flow Cont Stopple Fitng Ind | Yes |
| Nrc Rpt Datetime | 2021-01-17 12:30:00 |
| Nrc Rpt Num | 1296212 NRC Report How to search |
| Additional Nrc Report Numbers | 1296291 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 22.4 |
| Intentional Release | 0.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | Yes |
| Ignite Datetime | 2021-01-17 03:45:00 |
| How Extinguished | Allowed To Burn Out |
| Gas Consumed By Fire In Mcf | 22.4 |
| Explode Ind | No |
| Num Pub Evacuated | 18.0 |
| Incident Identified Datetime | 2021-01-17 03:45:00 |
| On Site Datetime | 2021-01-17 04:25:00 |
| Federal | No |
| Location Type | Public Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Overhead Crossing |
| Crossing | Yes |
| Bridge Crossing Ind | Yes |
| Bridge Type | Uncased |
| Pipe Facility Type | Investor Owned |
| System Part Involved | Main |
| Installation Year | 1955.0 |
| Pipe Diameter | 6.0 |
| Pipe Specification | Unknown |
| Pipe Manufacturer | Unknown |
| Material Involved | Steel |
| Steel Seam Type | Seamless |
| Wt Steel | 0.28 |
| Release Type | Leak |
| Leak Type | Pinhole |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 12100.0 |
| Est Cost Emergency | 39070.0 |
| Est Cost Other | 0.0 |
| Gas Cost In Mcf | 2.3 |
| Est Cost Unintentional Release | 52.0 |
| Est Cost Intentional Release | 0.0 |
| Prpty | 51222.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 17.0 |
| Num Persons Hosp Not Ovnght | 0.0 |
| Num Injured Treated By Emt | 0.0 |
| Num Resident Building Affctd | 18.0 |
| Num Business Building Affctd | 0.0 |
| Accident Psig | 20.0 |
| Normal Psig | 21.0 |
| Mop Psig | 24.0 |
| Mop Cfr Section | 192.619(C) View CFR 49 §192 |
| Maop Established Date | 1955-01-01 00:00:00 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Gas Odorized System Type | Injection Pump |
| Gas Odorized Lvl Not Msrd Ind | Yes |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Accident Identifier | Notification From Emergency Responder |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | The incident was due to inclement weather with winds blowing down a power line and not involving the control room operator. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Other Outside Force Damage |
| Cause Details | Electrical Arcing From Other Equipment Or Facility |
| Outside Force Type | Electrical Arcing From Other Equipment Or Facility |
| Preparer Name | C****** B***** |
| Preparer Title | Prin Program Manager Regulatory Moc |
| Preparer Email | C*************@n***********.com |
| Preparer Telephone | 5169030596 |
| Local Contact Name | C****** B***** |
| Local Contact Email | C*************@n***********.com |
| Local Contact Telephone | 5169030596 |
| Authorizer Name | C****** B***** |
| Authorizer Title | Prin. Program Mgr Regulatory Management Of Change |
| Authorizer Telephone | 5164924469 |
| Authorizer Email | C*************@n***********.com |
| Narrative | On january 17, national grid received notification of a gas related fire with main blowing gas. The cause of the fire was a primary electrical wire making contact above the 6" steel main resulting in the fire occurring. Approx. 17 houses were evacuated (18 residents), a 2" bypass was run to avoid customer interruptions, and temporary repairs were made. Temporary repairs were completed with a made safe time of 16:25. Additionally, the south park street bridge was closed as a result of this incident. For part e, question 5, odorant is injected at either biddlecum gate station or crogham gate station. The damaged pipeline segment was replaced with a 5'6" segment of 6" apix62 smaw 6010/7010 pipe with cold applied tape coating early february, 2021. The segment was air tested at 90 psi for 1 hour. |
External Resources