GD incident on 2021-01-17 — NY

Operator
Niagara Mohawk Power Corp
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$12,100
Incident datetime
2021-01-17 03:45
Report number
Location
NY, NEW YORK
Narrative
On january 17, national grid received notification of a gas related fire with main blowing gas. The cause of the fire was a primary electrical wire making contact above the 6" steel main resulting in the fire occurring. Approx. 17 houses were evacuated (18 residents), a 2" bypass was run to avoid customer interruptions, and temporary repairs were made. Temporary repairs were completed with a made safe time of 16:25. Additionally, the south park street bridge was closed as a result of this incident. For part e, question 5, odorant is injected at either biddlecum gate station or crogham gate station. The damaged pipeline segment was replaced with a 5'6" segment of 6" apix62 smaw 6010/7010 pipe with cold applied tape coating early february, 2021. The segment was air tested at 90 psi for 1 hour.
Detailed record list
Occurred At
2021-01-17 03:45:00
Year
2021
Report Received Date
2021-02-16 00:00:00
Iyear
2021.0
Report Number
20210019.0
Supplemental Number
34936.0
Report Type
Supplemental Final
Operator Id
Name
Niagara Mohawk Power Corp
Operator Street Address
300 Erie Boulevard West
Operator City Name
Syracuse
Operator State Abbreviation
NY
Operator Postal Code
13202
Local Datetime
2021-01-17 04:14:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Street Address
South Park St Bridge Bet Spring St And Grange Avenue
Location City Name
Adams
Location County Name
New York
Location State Abbreviation
NY
Location Postal Code
13605
Location Latitude
Location Longitude
Flow Cont Stopple Fitng Ind
Yes
Nrc Rpt Datetime
2021-01-17 12:30:00
Nrc Rpt Num
Additional Nrc Report Numbers
1296291
Commodity Released Type
Natural Gas
Unintentional Release
22.4
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
Yes
Ignite Datetime
2021-01-17 03:45:00
How Extinguished
Allowed To Burn Out
Gas Consumed By Fire In Mcf
22.4
Explode Ind
No
Num Pub Evacuated
18.0
Incident Identified Datetime
2021-01-17 03:45:00
On Site Datetime
2021-01-17 04:25:00
Federal
No
Location Type
Public Property
Incident Area Type
Aboveground
Incident Area Subtype
Overhead Crossing
Crossing
Yes
Bridge Crossing Ind
Yes
Bridge Type
Uncased
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
1955.0
Pipe Diameter
6.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Seamless
Wt Steel
0.28
Release Type
Leak
Leak Type
Pinhole
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
12100.0
Est Cost Emergency
39070.0
Est Cost Other
0.0
Gas Cost In Mcf
2.3
Est Cost Unintentional Release
52.0
Est Cost Intentional Release
0.0
Prpty
51222.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
17.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
18.0
Num Business Building Affctd
0.0
Accident Psig
20.0
Normal Psig
21.0
Mop Psig
24.0
Mop Cfr Section
Maop Established Date
1955-01-01 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The incident was due to inclement weather with winds blowing down a power line and not involving the control room operator.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Electrical Arcing From Other Equipment Or Facility
Outside Force Type
Electrical Arcing From Other Equipment Or Facility
Preparer Name
C****** B*****
Preparer Title
Prin Program Manager Regulatory Moc
Preparer Email
C*************@n***********.com
Preparer Telephone
5169030596
Local Contact Name
C****** B*****
Local Contact Email
C*************@n***********.com
Local Contact Telephone
5169030596
Authorizer Name
C****** B*****
Authorizer Title
Prin. Program Mgr Regulatory Management Of Change
Authorizer Telephone
5164924469
Authorizer Email
C*************@n***********.com
Narrative
On january 17, national grid received notification of a gas related fire with main blowing gas. The cause of the fire was a primary electrical wire making contact above the 6" steel main resulting in the fire occurring. Approx. 17 houses were evacuated (18 residents), a 2" bypass was run to avoid customer interruptions, and temporary repairs were made. Temporary repairs were completed with a made safe time of 16:25. Additionally, the south park street bridge was closed as a result of this incident. For part e, question 5, odorant is injected at either biddlecum gate station or crogham gate station. The damaged pipeline segment was replaced with a 5'6" segment of 6" apix62 smaw 6010/7010 pipe with cold applied tape coating early february, 2021. The segment was air tested at 90 psi for 1 hour.
Occurred At 2021-01-17 03:45:00
Year 2021
Report Received Date 2021-02-16 00:00:00
Iyear 2021.0
Report Number 20210019.0
Supplemental Number 34936.0
Report Type Supplemental Final
Operator Id 13480 PHMSA Enforcement
Name Niagara Mohawk Power Corp
Operator Street Address 300 Erie Boulevard West
Operator City Name Syracuse
Operator State Abbreviation NY
Operator Postal Code 13202
Local Datetime 2021-01-17 04:14:00
Time Zone Eastern
Daylight Savings Ind Yes
Location Street Address South Park St Bridge Bet Spring St And Grange Avenue
Location City Name Adams
Location County Name New York
Location State Abbreviation NY
Location Postal Code 13605
Location Latitude 43.80773 Google Maps OpenStreetMap
Location Longitude -76.0193 Google Maps OpenStreetMap
Flow Cont Stopple Fitng Ind Yes
Nrc Rpt Datetime 2021-01-17 12:30:00
Nrc Rpt Num 1296212 NRC Report How to search
Additional Nrc Report Numbers 1296291
Commodity Released Type Natural Gas
Unintentional Release 22.4
Intentional Release 0.0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind Yes
Ignite Datetime 2021-01-17 03:45:00
How Extinguished Allowed To Burn Out
Gas Consumed By Fire In Mcf 22.4
Explode Ind No
Num Pub Evacuated 18.0
Incident Identified Datetime 2021-01-17 03:45:00
On Site Datetime 2021-01-17 04:25:00
Federal No
Location Type Public Property
Incident Area Type Aboveground
Incident Area Subtype Overhead Crossing
Crossing Yes
Bridge Crossing Ind Yes
Bridge Type Uncased
Pipe Facility Type Investor Owned
System Part Involved Main
Installation Year 1955.0
Pipe Diameter 6.0
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Steel
Steel Seam Type Seamless
Wt Steel 0.28
Release Type Leak
Leak Type Pinhole
Class Location Type Class 3 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 12100.0
Est Cost Emergency 39070.0
Est Cost Other 0.0
Gas Cost In Mcf 2.3
Est Cost Unintentional Release 52.0
Est Cost Intentional Release 0.0
Prpty 51222.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 17.0
Num Persons Hosp Not Ovnght 0.0
Num Injured Treated By Emt 0.0
Num Resident Building Affctd 18.0
Num Business Building Affctd 0.0
Accident Psig 20.0
Normal Psig 21.0
Mop Psig 24.0
Mop Cfr Section 192.619(C) View CFR 49 §192
Maop Established Date 1955-01-01 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type Injection Pump
Gas Odorized Lvl Not Msrd Ind Yes
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Notification From Emergency Responder
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The incident was due to inclement weather with winds blowing down a power line and not involving the control room operator.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Outside Force Damage
Cause Details Electrical Arcing From Other Equipment Or Facility
Outside Force Type Electrical Arcing From Other Equipment Or Facility
Preparer Name C****** B*****
Preparer Title Prin Program Manager Regulatory Moc
Preparer Email C*************@n***********.com
Preparer Telephone 5169030596
Local Contact Name C****** B*****
Local Contact Email C*************@n***********.com
Local Contact Telephone 5169030596
Authorizer Name C****** B*****
Authorizer Title Prin. Program Mgr Regulatory Management Of Change
Authorizer Telephone 5164924469
Authorizer Email C*************@n***********.com
Narrative On january 17, national grid received notification of a gas related fire with main blowing gas. The cause of the fire was a primary electrical wire making contact above the 6" steel main resulting in the fire occurring. Approx. 17 houses were evacuated (18 residents), a 2" bypass was run to avoid customer interruptions, and temporary repairs were made. Temporary repairs were completed with a made safe time of 16:25. Additionally, the south park street bridge was closed as a result of this incident. For part e, question 5, odorant is injected at either biddlecum gate station or crogham gate station. The damaged pipeline segment was replaced with a 5'6" segment of 6" apix62 smaw 6010/7010 pipe with cold applied tape coating early february, 2021. The segment was air tested at 90 psi for 1 hour.

All rights reserved. Copyright © by ClearPHMSA