GD incident on 2020-12-24 — TX

Operator
Hempstead, City Of
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 1 injury
Property damage (nominal)
$0
Incident datetime
2020-12-24 22:30
Report number
Location
TX, TX
Narrative
On december 22, 2020 we received a leak call by a non-customer occupant of a residence. We found the occupant had enclosed his front porch entirely. We detected gas and pulled the electric meter. We told the occupant he could not stay there and must leave the door to the enclosure open to vent any gas. We called the 811 number to get a locate for 1335 5th st.. We had a crew there waiting on the utility locate from the telephone company. We could not get to the locate wire because the customer's enclosure contained a concrete floor constructed around the riser. We tried to dig outside the concrete put could not because of the excessive tree roots on the property. We went out to the road and dug behind the curb, in line with the meter, and could not find the pipe to squeeze off. We went south a few feet found the 1" plastic pipe, which we squeezed off and caped, and check for leaks. We tried to verify the gas was off and retrieve the gas meter inside the enclosure but the customer had already left and locked the door so we could not get in. We were called on december 24, 2020 stating the house blew up. Because the explosion blew away the concrete exterior wall down, we were able to dig next to the concrete and squeeze off the service line. This stopped the gas flow. I went to call the texas railroad commission to inform them of the accident."
Detailed record list
Occurred At
2020-12-24 22:30:00
Year
2020
Report Received Date
2021-01-22 00:00:00
Iyear
2020.0
Report Number
20210012.0
Supplemental Number
36934.0
Report Type
Supplemental Final
Operator Id
Name
Hempstead, City Of
Operator Street Address
1125 Austin St.
Operator City Name
Hempstead
Operator State Abbreviation
TX
Operator Postal Code
77445
Local Datetime
2020-12-24 23:40:00
Time Zone
Central
Daylight Savings Ind
No
Location Street Address
1337 5th
Location City Name
Hempstead
Location County Name
Tx
Location State Abbreviation
TX
Location Postal Code
77445
Location Latitude
Location Longitude
Flow Cont Squeeze Off Ind
Yes
Nrc Rpt Datetime
2020-12-30 11:12:00
Nrc Rpt Num
Additional Nrc Report Numbers
1295391
Commodity Released Type
Natural Gas
Unintentional Release
9.0
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
0
Num Er Injuries
0
Num Worker Injuries
0
Num Gp Injuries
1
Injure
1
Ignite Ind
Yes
Ignite Datetime
2020-12-24 22:30:00
How Extinguished
Operator/contractor
Gas Consumed By Fire In Mcf
9
Explode Ind
Yes
Num Pub Evacuated
3.0
Incident Identified Datetime
2020-12-24 22:30:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2020-12-25 00:30:00
On Site Datetime
2020-12-24 22:40:00
Federal
No
Location Type
Private Property
Incident Area Type
Aboveground
Incident Area Subtype
In Other Enclosed Space
Crossing
No
Pipe Facility Type
Municipally Owned
System Part Involved
Service Riser
Customer Type
Single Family Residential
Was Efv Installed Before Ind
No
Curb Valve Inst Before Inc Ind
No
Material Involved
Steel
Steel Seam Type
Seamless
Release Type
Other
Release Type Details
Steel Riser Was Intentionally Cut By A Person With A Power-Tool.
Class Location Type
Class 3 Location
Est Cost Oper Paid
120000.0
Est Cost Prop Damage
0.0
Est Cost Emergency
1000.0
Est Cost Other
0.0
Gas Cost In Mcf
10.18
Est Cost Unintentional Release
92.0
Est Cost Intentional Release
0.0
Prpty
121092.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
1.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
4.0
Num Business Building Affctd
0.0
Accident Psig
19.0
Normal Psig
19.0
Mop Psig
25.0
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1978-01-05 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
By-Pass
Gas Odorized Level
0.8
Scada In Place Ind
No
Accident Identifier
Notification From Public
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Intentional Damage
Outside Force Type
Intentional Damage
Intentional Subtype
Other
Intentional Details
The Analytical Data Is Consistent With Vandalism. The Evidence Shows A Person Cut Through The Customer-Side Pipe With The Intent To Remove The Gas Meter Entirely, But Caused A Leak When They Cut Through The Pipe Upstream Of The Locked Riser Valve Beneath The Regulator. The Riser Was Found Wrapped In Painters Tape, Meanwhile The Pipe On The Customer-Side Of The Meter Was Cut Through Intentionally. Metallurgy Tests Reveal The Corrosion Occurred After The Explosion. This Is Vandalism!
Preparer Name
R****** S****
Preparer Title
Chief Staff
Preparer Email
R************@y****.com
Preparer Telephone
979 8262486
Local Contact Name
R****** S****
Local Contact Email
R************@y****.com
Local Contact Telephone
979 826-2486
Authorizer Name
R****** S****
Authorizer Title
Chief Staff
Authorizer Telephone
979 826-2486
Authorizer Email
R************@y****.com
Narrative
On december 22, 2020 we received a leak call by a non-customer occupant of a residence. We found the occupant had enclosed his front porch entirely. We detected gas and pulled the electric meter. We told the occupant he could not stay there and must leave the door to the enclosure open to vent any gas. We called the 811 number to get a locate for 1335 5th st.. We had a crew there waiting on the utility locate from the telephone company. We could not get to the locate wire because the customer's enclosure contained a concrete floor constructed around the riser. We tried to dig outside the concrete put could not because of the excessive tree roots on the property. We went out to the road and dug behind the curb, in line with the meter, and could not find the pipe to squeeze off. We went south a few feet found the 1" plastic pipe, which we squeezed off and caped, and check for leaks. We tried to verify the gas was off and retrieve the gas meter inside the enclosure but the customer had already left and locked the door so we could not get in. We were called on december 24, 2020 stating the house blew up. Because the explosion blew away the concrete exterior wall down, we were able to dig next to the concrete and squeeze off the service line. This stopped the gas flow. I went to call the texas railroad commission to inform them of the accident."
Occurred At 2020-12-24 22:30:00
Year 2020
Report Received Date 2021-01-22 00:00:00
Iyear 2020.0
Report Number 20210012.0
Supplemental Number 36934.0
Report Type Supplemental Final
Operator Id 7210 PHMSA Enforcement
Name Hempstead, City Of
Operator Street Address 1125 Austin St.
Operator City Name Hempstead
Operator State Abbreviation TX
Operator Postal Code 77445
Local Datetime 2020-12-24 23:40:00
Time Zone Central
Daylight Savings Ind No
Location Street Address 1337 5th
Location City Name Hempstead
Location County Name Tx
Location State Abbreviation TX
Location Postal Code 77445
Location Latitude 30.092136 Google Maps OpenStreetMap
Location Longitude -96.072948 Google Maps OpenStreetMap
Flow Cont Squeeze Off Ind Yes
Nrc Rpt Datetime 2020-12-30 11:12:00
Nrc Rpt Num 1295221 NRC Report How to search
Additional Nrc Report Numbers 1295391
Commodity Released Type Natural Gas
Unintentional Release 9.0
Intentional Release 0.0
Fatality Ind No
Fatal 0
Injury Ind Yes
Num Emp Injuries 0
Num Contr Injuries 0
Num Er Injuries 0
Num Worker Injuries 0
Num Gp Injuries 1
Injure 1
Ignite Ind Yes
Ignite Datetime 2020-12-24 22:30:00
How Extinguished Operator/contractor
Gas Consumed By Fire In Mcf 9
Explode Ind Yes
Num Pub Evacuated 3.0
Incident Identified Datetime 2020-12-24 22:30:00
Communication State Fed Ind Yes
Party Initiated Communication Operator
Initial Responder Com Datetime 2020-12-25 00:30:00
On Site Datetime 2020-12-24 22:40:00
Federal No
Location Type Private Property
Incident Area Type Aboveground
Incident Area Subtype In Other Enclosed Space
Crossing No
Pipe Facility Type Municipally Owned
System Part Involved Service Riser
Customer Type Single Family Residential
Was Efv Installed Before Ind No
Curb Valve Inst Before Inc Ind No
Material Involved Steel
Steel Seam Type Seamless
Release Type Other
Release Type Details Steel Riser Was Intentionally Cut By A Person With A Power-Tool.
Class Location Type Class 3 Location
Est Cost Oper Paid 120000.0
Est Cost Prop Damage 0.0
Est Cost Emergency 1000.0
Est Cost Other 0.0
Gas Cost In Mcf 10.18
Est Cost Unintentional Release 92.0
Est Cost Intentional Release 0.0
Prpty 121092.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 1.0
Num Persons Hosp Not Ovnght 0.0
Num Injured Treated By Emt 0.0
Num Resident Building Affctd 4.0
Num Business Building Affctd 0.0
Accident Psig 19.0
Normal Psig 19.0
Mop Psig 25.0
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 1978-01-05 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type By-Pass
Gas Odorized Level 0.8
Scada In Place Ind No
Accident Identifier Notification From Public
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Other Outside Force Damage
Cause Details Intentional Damage
Outside Force Type Intentional Damage
Intentional Subtype Other
Intentional Details The Analytical Data Is Consistent With Vandalism. The Evidence Shows A Person Cut Through The Customer-Side Pipe With The Intent To Remove The Gas Meter Entirely, But Caused A Leak When They Cut Through The Pipe Upstream Of The Locked Riser Valve Beneath The Regulator. The Riser Was Found Wrapped In Painters Tape, Meanwhile The Pipe On The Customer-Side Of The Meter Was Cut Through Intentionally. Metallurgy Tests Reveal The Corrosion Occurred After The Explosion. This Is Vandalism!
Preparer Name R****** S****
Preparer Title Chief Staff
Preparer Email R************@y****.com
Preparer Telephone 979 8262486
Local Contact Name R****** S****
Local Contact Email R************@y****.com
Local Contact Telephone 979 826-2486
Authorizer Name R****** S****
Authorizer Title Chief Staff
Authorizer Telephone 979 826-2486
Authorizer Email R************@y****.com
Narrative On december 22, 2020 we received a leak call by a non-customer occupant of a residence. We found the occupant had enclosed his front porch entirely. We detected gas and pulled the electric meter. We told the occupant he could not stay there and must leave the door to the enclosure open to vent any gas. We called the 811 number to get a locate for 1335 5th st.. We had a crew there waiting on the utility locate from the telephone company. We could not get to the locate wire because the customer's enclosure contained a concrete floor constructed around the riser. We tried to dig outside the concrete put could not because of the excessive tree roots on the property. We went out to the road and dug behind the curb, in line with the meter, and could not find the pipe to squeeze off. We went south a few feet found the 1" plastic pipe, which we squeezed off and caped, and check for leaks. We tried to verify the gas was off and retrieve the gas meter inside the enclosure but the customer had already left and locked the door so we could not get in. We were called on december 24, 2020 stating the house blew up. Because the explosion blew away the concrete exterior wall down, we were able to dig next to the concrete and squeeze off the service line. This stopped the gas flow. I went to call the texas railroad commission to inform them of the accident."

All rights reserved. Copyright © by ClearPHMSA