Incident details
Operator, cause, commodity and consequences with raw source fields.
GD incident on 2020-12-18 — FL
Operator
Florida Public Utilities Co
Cause
Other Outside Force Damage
Commodity
Natural Gas
Program
GD
Damage and Injuries
1 fatality
1 injury
Property damage (nominal)
$6,500
Incident datetime
2020-12-18 10:52
Report number
Location
FL, PALM BEACH
Narrative
At approximately 10:45 am on friday, 12/18/20, a 2008 hino box truck was heading north on south ocean blvd. In manalapan, fl. For unknown reasons the driver veered left and crossed over the south bound lane and left the roadway and travelled in the landscaped shoulder for approximately 100', striking multiple trees, a power utility box and a gas meter set. The gas meter set riser was snapped off under the service regulator and the escaping gas ignited. According to the first bystander on the scene, the driver was unresponsive and could not be removed from the truck which was engulfed in flames. The driver was pronounced deceased at the scene. One passenger in the truck was ejected through the windshield and was taken to st. Mary's hospital for treatment. Emergency responders from palm beach county fire department and florida public utilities extinguished the flames and plugged the broken riser at 12:10 pm on 12/18/20. As of 1/15/2021, the palm beach sheriff's office vehicle homicide report is incomplete and a determination of the drivers condition at the time of the crash is not available. There did not appear to be braking or skid marks at the scene of the crash and a medical emergency may have occurred. Update 9/9/2021 - obtained pbso vehicle homicide investigation report on 9/3/2021. According to the report, impairment is unknown due to negative blood, tissue, and/or urine volatile. It is unknown if the driver was distracted or using a mobile device while operating the vehicle. No citations were issued to the driver due to being deceased. Report states that actions of the driver caused his own death. The service was repaired by installing approx. 7' of 1 1/4" pe pipe, an efv, new riser and meter set. The meter was moved next to a wall and crash posts were installed on 12/22/2020.
Detailed record list
Occurred At
2020-12-18 10:52:00
Year
2020
Report Received Date
2021-01-15 00:00:00
Iyear
2020.0
Report Number
20210009.0
Supplemental Number
35724.0
Report Type
Supplemental Final
Operator Id
5330
Name
Florida Public Utilities Co
Operator Street Address
208 Wildlight Ave
Operator City Name
Yulee
Operator State Abbreviation
FL
Operator Postal Code
32097
Local Datetime
2020-12-18 13:05:00
Time Zone
Eastern
Daylight Savings Ind
Yes
Location Street Address
3040 S. Ocean Blvd.
Location City Name
Manalapan
Location County Name
Palm Beach
Location State Abbreviation
FL
Location Postal Code
33462-6211
Location Latitude
26.54792
Location Longitude
-80.04302
Flow Cont Other Ind
Yes
Flow Cont Other Detail
Plug In Riser.
Nrc Rpt Datetime
2020-12-18 13:05:00
Nrc Rpt Num
1294572
Additional Nrc Report Numbers
1294661
Commodity Released Type
Natural Gas
Unintentional Release
63.0
Intentional Release
0.0
Fatality Ind
Yes
Num Emp Fatalities
0
Num Contr Fatalities
0
Num Er Fatalities
0
Num Worker Fatalities
0
Num Gp Fatalities
1
Fatal
1
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
0
Num Er Injuries
0
Num Worker Injuries
0
Num Gp Injuries
1
Injure
1
Ignite Ind
Yes
Ignite Datetime
2020-12-18 10:45:00
How Extinguished
Local/state/federal Emergency Responder
Gas Consumed By Fire In Mcf
62
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2020-12-18 10:52:00
On Site Datetime
2020-12-18 11:15:00
Federal
No
Location Type
Utility Right-Of-Way / Easement
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set)
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Outside Meter/regulator Set
Installation Year
2002.0
Manufactured Year
2002.0
Customer Type
Single Family Residential
Was Efv Installed Before Ind
No
Curb Valve Inst Before Inc Ind
No
Material Involved
Other
Material Details
1.25" Anodeless Service Riser
Release Type
Other
Release Type Details
1.25" Anodeless Service Riser Broken Off Under Service Regulator At Meter Set.
Class Location Type
Class 3 Location
Est Cost Oper Paid
40000.0
Est Cost Prop Damage
6500.0
Est Cost Emergency
3600.0
Est Cost Other
0.0
Gas Cost In Mcf
36.8
Est Cost Unintentional Release
2318.0
Est Cost Intentional Release
0.0
Prpty
52418.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
1.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
1.0
Num Resident Building Affctd
1.0
Num Business Building Affctd
0.0
Accident Psig
20.0
Normal Psig
20.0
Mop Psig
60.0
Mop Cfr Section
192.619(A)(2)
Maop Established Date
2002-06-07 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Other Outside Force Damage
Cause Details
Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Outside Force Type
Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation
Vehicle Subtype
Third Party
Driver Issued Citation Ind
No
Driver In Control Ind
Unknown
Estimated Speed
35
Vehicle Type
Large Truck
Vehicle Travel From
Roadway
Vehicle Travel Distance Ft
50
Protections Installed Ind
Yes
Protection Ingress Regress Ind
Yes
Protection Other Ind
Yes
Protection Other Detail
Meter Set Was Behind Several Trees And Next To A Wall
Preparer Name
M****** M******
Preparer Title
Director Measurement And Compliance
Preparer Email
M*******@f***.com
Preparer Telephone
8638457005
Preparer Fax
8632940629
Local Contact Name
M****** P*******
Local Contact Email
M********@f***.com
Local Contact Telephone
5612150159
Authorizer Name
M****** M******
Authorizer Title
Director Measurement And Compliance
Authorizer Telephone
8638457005
Authorizer Email
M*******@f***.com
Narrative
At approximately 10:45 am on friday, 12/18/20, a 2008 hino box truck was heading north on south ocean blvd. In manalapan, fl. For unknown reasons the driver veered left and crossed over the south bound lane and left the roadway and travelled in the landscaped shoulder for approximately 100', striking multiple trees, a power utility box and a gas meter set. The gas meter set riser was snapped off under the service regulator and the escaping gas ignited. According to the first bystander on the scene, the driver was unresponsive and could not be removed from the truck which was engulfed in flames. The driver was pronounced deceased at the scene. One passenger in the truck was ejected through the windshield and was taken to st. Mary's hospital for treatment. Emergency responders from palm beach county fire department and florida public utilities extinguished the flames and plugged the broken riser at 12:10 pm on 12/18/20. As of 1/15/2021, the palm beach sheriff's office vehicle homicide report is incomplete and a determination of the drivers condition at the time of the crash is not available. There did not appear to be braking or skid marks at the scene of the crash and a medical emergency may have occurred. Update 9/9/2021 - obtained pbso vehicle homicide investigation report on 9/3/2021. According to the report, impairment is unknown due to negative blood, tissue, and/or urine volatile. It is unknown if the driver was distracted or using a mobile device while operating the vehicle. No citations were issued to the driver due to being deceased. Report states that actions of the driver caused his own death. The service was repaired by installing approx. 7' of 1 1/4" pe pipe, an efv, new riser and meter set. The meter was moved next to a wall and crash posts were installed on 12/22/2020.
| Occurred At | 2020-12-18 10:52:00 |
|---|---|
| Year | 2020 |
| Report Received Date | 2021-01-15 00:00:00 |
| Iyear | 2020.0 |
| Report Number | 20210009.0 |
| Supplemental Number | 35724.0 |
| Report Type | Supplemental Final |
| Operator Id | 5330 PHMSA Enforcement |
| Name | Florida Public Utilities Co |
| Operator Street Address | 208 Wildlight Ave |
| Operator City Name | Yulee |
| Operator State Abbreviation | FL |
| Operator Postal Code | 32097 |
| Local Datetime | 2020-12-18 13:05:00 |
| Time Zone | Eastern |
| Daylight Savings Ind | Yes |
| Location Street Address | 3040 S. Ocean Blvd. |
| Location City Name | Manalapan |
| Location County Name | Palm Beach |
| Location State Abbreviation | FL |
| Location Postal Code | 33462-6211 |
| Location Latitude | 26.54792 Google Maps OpenStreetMap |
| Location Longitude | -80.04302 Google Maps OpenStreetMap |
| Flow Cont Other Ind | Yes |
| Flow Cont Other Detail | Plug In Riser. |
| Nrc Rpt Datetime | 2020-12-18 13:05:00 |
| Nrc Rpt Num | 1294572 NRC Report How to search |
| Additional Nrc Report Numbers | 1294661 |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 63.0 |
| Intentional Release | 0.0 |
| Fatality Ind | Yes |
| Num Emp Fatalities | 0 |
| Num Contr Fatalities | 0 |
| Num Er Fatalities | 0 |
| Num Worker Fatalities | 0 |
| Num Gp Fatalities | 1 |
| Fatal | 1 |
| Injury Ind | Yes |
| Num Emp Injuries | 0 |
| Num Contr Injuries | 0 |
| Num Er Injuries | 0 |
| Num Worker Injuries | 0 |
| Num Gp Injuries | 1 |
| Injure | 1 |
| Ignite Ind | Yes |
| Ignite Datetime | 2020-12-18 10:45:00 |
| How Extinguished | Local/state/federal Emergency Responder |
| Gas Consumed By Fire In Mcf | 62 |
| Explode Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2020-12-18 10:52:00 |
| On Site Datetime | 2020-12-18 11:15:00 |
| Federal | No |
| Location Type | Utility Right-Of-Way / Easement |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance (E.g. Value Or Regulator Station, Outdoor Meter Set) |
| Crossing | No |
| Pipe Facility Type | Investor Owned |
| System Part Involved | Outside Meter/regulator Set |
| Installation Year | 2002.0 |
| Manufactured Year | 2002.0 |
| Customer Type | Single Family Residential |
| Was Efv Installed Before Ind | No |
| Curb Valve Inst Before Inc Ind | No |
| Material Involved | Other |
| Material Details | 1.25" Anodeless Service Riser |
| Release Type | Other |
| Release Type Details | 1.25" Anodeless Service Riser Broken Off Under Service Regulator At Meter Set. |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 40000.0 |
| Est Cost Prop Damage | 6500.0 |
| Est Cost Emergency | 3600.0 |
| Est Cost Other | 0.0 |
| Gas Cost In Mcf | 36.8 |
| Est Cost Unintentional Release | 2318.0 |
| Est Cost Intentional Release | 0.0 |
| Prpty | 52418.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 1.0 |
| Num Persons Hosp Not Ovnght | 0.0 |
| Num Injured Treated By Emt | 1.0 |
| Num Resident Building Affctd | 1.0 |
| Num Business Building Affctd | 0.0 |
| Accident Psig | 20.0 |
| Normal Psig | 20.0 |
| Mop Psig | 60.0 |
| Mop Cfr Section | 192.619(A)(2) View CFR 49 §192 |
| Maop Established Date | 2002-06-07 00:00:00 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Gas Odorized System Type | Injection Pump |
| Gas Odorized Lvl Not Msrd Ind | Yes |
| Scada In Place Ind | No |
| Accident Identifier | Notification From Emergency Responder |
| Investigation Status | No, the facility was not monitored by a controller(s) at the time of the incident |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Other Outside Force Damage |
| Cause Details | Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation |
| Outside Force Type | Damage By Car, Truck, Or Other Motorized Vehicle/equipment Not Engaged In Excavation |
| Vehicle Subtype | Third Party |
| Driver Issued Citation Ind | No |
| Driver In Control Ind | Unknown |
| Estimated Speed | 35 |
| Vehicle Type | Large Truck |
| Vehicle Travel From | Roadway |
| Vehicle Travel Distance Ft | 50 |
| Protections Installed Ind | Yes |
| Protection Ingress Regress Ind | Yes |
| Protection Other Ind | Yes |
| Protection Other Detail | Meter Set Was Behind Several Trees And Next To A Wall |
| Preparer Name | M****** M****** |
| Preparer Title | Director Measurement And Compliance |
| Preparer Email | M*******@f***.com |
| Preparer Telephone | 8638457005 |
| Preparer Fax | 8632940629 |
| Local Contact Name | M****** P******* |
| Local Contact Email | M********@f***.com |
| Local Contact Telephone | 5612150159 |
| Authorizer Name | M****** M****** |
| Authorizer Title | Director Measurement And Compliance |
| Authorizer Telephone | 8638457005 |
| Authorizer Email | M*******@f***.com |
| Narrative | At approximately 10:45 am on friday, 12/18/20, a 2008 hino box truck was heading north on south ocean blvd. In manalapan, fl. For unknown reasons the driver veered left and crossed over the south bound lane and left the roadway and travelled in the landscaped shoulder for approximately 100', striking multiple trees, a power utility box and a gas meter set. The gas meter set riser was snapped off under the service regulator and the escaping gas ignited. According to the first bystander on the scene, the driver was unresponsive and could not be removed from the truck which was engulfed in flames. The driver was pronounced deceased at the scene. One passenger in the truck was ejected through the windshield and was taken to st. Mary's hospital for treatment. Emergency responders from palm beach county fire department and florida public utilities extinguished the flames and plugged the broken riser at 12:10 pm on 12/18/20. As of 1/15/2021, the palm beach sheriff's office vehicle homicide report is incomplete and a determination of the drivers condition at the time of the crash is not available. There did not appear to be braking or skid marks at the scene of the crash and a medical emergency may have occurred. Update 9/9/2021 - obtained pbso vehicle homicide investigation report on 9/3/2021. According to the report, impairment is unknown due to negative blood, tissue, and/or urine volatile. It is unknown if the driver was distracted or using a mobile device while operating the vehicle. No citations were issued to the driver due to being deceased. Report states that actions of the driver caused his own death. The service was repaired by installing approx. 7' of 1 1/4" pe pipe, an efv, new riser and meter set. The meter was moved next to a wall and crash posts were installed on 12/22/2020. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company