GD incident on 2020-12-03 — FL

Operator
Peoples Gas System Inc
Cause
Miscellaneous Root Causes
Commodity
Natural Gas
Program
GD
Damage and Injuries
1 fatality 1 injury
Property damage (nominal)
$25,928
Incident datetime
2020-12-03 11:20
Report number
Location
FL, MANATEE
Narrative
Damaged 2" pe main by third party next generation management inc. Bore crew. The damaged gas line resulted in gas migrating into a severed sewer line which was also damaged by next generation management inc. In the same excavation. It appears the gas migrated from the county sewer system through the home's sewer system and unexpectedly into the home where the gas ignited, resulting in an explosion. Additional notes: part a question 21c - the amount of gas reported is an estimate of .55. The PHMSA portal rounded the amount to 1.0. Part a question 22 - the number of general public evacuated is an estimate based on a review of the responding fire departments' incident reports and assuming that there were 2 occupants per residential building and 5 occupants per business building. Part d question 6 - the number of residential buildings affected is an estimate based on a review of the responding fire departments' incident reports. Part d question 7 - the number of business buildings affected is an estimate based on a review of the responding fire departments' incident reports.
Detailed record list
Occurred At
2020-12-03 11:20:00
Year
2020
Report Received Date
2021-01-02 00:00:00
Iyear
2020.0
Report Number
20210001.0
Supplemental Number
35863.0
Report Type
Supplemental Final
Operator Id
Name
Peoples Gas System Inc
Operator Street Address
Po Box 2562
Operator City Name
Tampa
Operator State Abbreviation
FL
Operator Postal Code
33601
Local Datetime
2020-12-03 17:11:00
Time Zone
Eastern
Daylight Savings Ind
No
Location Street Address
8*******************@ ****************
Location City Name
Bradenton
Location County Name
Manatee
Location State Abbreviation
FL
Location Postal Code
34205
Location Latitude
Location Longitude
Flow Cont Squeeze Off Ind
Yes
Nrc Rpt Datetime
2020-12-03 17:11:00
Nrc Rpt Num
Additional Nrc Report Numbers
1293605
Commodity Released Type
Natural Gas
Unintentional Release
224.0
Intentional Release
0.0
Fatality Ind
Yes
Num Emp Fatalities
0
Num Contr Fatalities
0
Num Er Fatalities
0
Num Worker Fatalities
0
Num Gp Fatalities
1
Fatal
1
Injury Ind
Yes
Num Emp Injuries
0
Num Contr Injuries
0
Num Er Injuries
0
Num Worker Injuries
0
Num Gp Injuries
1
Injure
1
Ignite Ind
Yes
Ignite Datetime
2020-12-03 13:50:00
How Extinguished
Local/state/federal Emergency Responder
Gas Consumed By Fire In Mcf
1
Explode Ind
Yes
Num Pub Evacuated
205.0
Incident Identified Datetime
2020-12-03 11:20:00
Communication State Fed Ind
Yes
Party Initiated Communication
Operator
Initial Responder Com Datetime
2020-12-03 11:37:00
On Site Datetime
2020-12-03 11:37:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
84.0
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
2014.0
Pipe Diameter
2.0
Pipe Specification
Drisco Plex 6500
Pipe Manufacturer
Performance Pipe
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Plastic Sdr
11
Material Pe Pipe Code
2406
Release Type
Leak
Leak Type
Other
Leak Type Other
Damage By 3rd Party To Line
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
25928.0
Est Cost Emergency
2400.0
Est Cost Other
100000.0
Est Cost Other Details
Estimated Other Costs Includes Estimated Value Of Damaged Home.
Gas Cost In Mcf
2.88
Est Cost Unintentional Release
645.0
Est Cost Intentional Release
0.0
Prpty
128973.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Num Persons Hosp Not Ovnght
1.0
Num Injured Treated By Emt
1.0
Num Resident Building Affctd
95.0
Num Business Building Affctd
3.0
Accident Psig
43.0
Normal Psig
47.0
Mop Psig
60.0
Mop Cfr Section
192.619(A)(2)
Maop Established Date
2014-04-24 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Combination Of Odorization Types
Gas Odorized Level
0.1
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Notification From Third Party That Caused The Incident
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
This was a 3rd party line strike to operator's system.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
Yes
One Call System Ind
Yes
State Law Exempt Ind
No
Notify Cga Dirt
Yes
Public Row Ind
Yes
Public Subtype
City Street
Excavator Type
Contractor
Excavator Equipment
Boring
Work Performed
Telecommunications
One Call Notified Ind
Yes
One Call Ticket Num
330000015
Locator Type
Utility Owner
Visible Marks
Yes
Service Interruption
No
Root Cause Category
Miscellaneous Root Causes
Root Cause Type
Root Cause Not Listed (Comment Required)
Root Cause Type Other
Data Not Collected
Preparer Name
S***** P****
Preparer Title
Manager Safety Mgmt Systems And Quality Assurance
Preparer Email
S******@t*********.com
Preparer Telephone
(813) 275-3730
Local Contact Name
T**** J*****
Local Contact Email
T*******@t*********.com
Local Contact Telephone
(813) 275-3736
Authorizer Name
S***** P****
Authorizer Title
Manager Safety Mgmt Systems And Quality Assurance
Authorizer Telephone
(813) 275-3730
Authorizer Email
S******@t*********.com
Narrative
Damaged 2" pe main by third party next generation management inc. Bore crew. The damaged gas line resulted in gas migrating into a severed sewer line which was also damaged by next generation management inc. In the same excavation. It appears the gas migrated from the county sewer system through the home's sewer system and unexpectedly into the home where the gas ignited, resulting in an explosion. Additional notes: part a question 21c - the amount of gas reported is an estimate of .55. The PHMSA portal rounded the amount to 1.0. Part a question 22 - the number of general public evacuated is an estimate based on a review of the responding fire departments' incident reports and assuming that there were 2 occupants per residential building and 5 occupants per business building. Part d question 6 - the number of residential buildings affected is an estimate based on a review of the responding fire departments' incident reports. Part d question 7 - the number of business buildings affected is an estimate based on a review of the responding fire departments' incident reports.
Occurred At 2020-12-03 11:20:00
Year 2020
Report Received Date 2021-01-02 00:00:00
Iyear 2020.0
Report Number 20210001.0
Supplemental Number 35863.0
Report Type Supplemental Final
Operator Id 15348 PHMSA Enforcement
Name Peoples Gas System Inc
Operator Street Address Po Box 2562
Operator City Name Tampa
Operator State Abbreviation FL
Operator Postal Code 33601
Local Datetime 2020-12-03 17:11:00
Time Zone Eastern
Daylight Savings Ind No
Location Street Address 8*******************@ ****************
Location City Name Bradenton
Location County Name Manatee
Location State Abbreviation FL
Location Postal Code 34205
Location Latitude 27.4737805 Google Maps OpenStreetMap
Location Longitude -82.5704721 Google Maps OpenStreetMap
Flow Cont Squeeze Off Ind Yes
Nrc Rpt Datetime 2020-12-03 17:11:00
Nrc Rpt Num 1293475 NRC Report How to search
Additional Nrc Report Numbers 1293605
Commodity Released Type Natural Gas
Unintentional Release 224.0
Intentional Release 0.0
Fatality Ind Yes
Num Emp Fatalities 0
Num Contr Fatalities 0
Num Er Fatalities 0
Num Worker Fatalities 0
Num Gp Fatalities 1
Fatal 1
Injury Ind Yes
Num Emp Injuries 0
Num Contr Injuries 0
Num Er Injuries 0
Num Worker Injuries 0
Num Gp Injuries 1
Injure 1
Ignite Ind Yes
Ignite Datetime 2020-12-03 13:50:00
How Extinguished Local/state/federal Emergency Responder
Gas Consumed By Fire In Mcf 1
Explode Ind Yes
Num Pub Evacuated 205.0
Incident Identified Datetime 2020-12-03 11:20:00
Communication State Fed Ind Yes
Party Initiated Communication Operator
Initial Responder Com Datetime 2020-12-03 11:37:00
On Site Datetime 2020-12-03 11:37:00
Federal No
Location Type Public Property
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 84.0
Other Underground Facilities No
Crossing No
Pipe Facility Type Investor Owned
System Part Involved Main
Installation Year 2014.0
Pipe Diameter 2.0
Pipe Specification Drisco Plex 6500
Pipe Manufacturer Performance Pipe
Material Involved Plastic
Plastic Type Polyethylene (Pe)
Plastic Sdr 11
Material Pe Pipe Code 2406
Release Type Leak
Leak Type Other
Leak Type Other Damage By 3rd Party To Line
Class Location Type Class 3 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 25928.0
Est Cost Emergency 2400.0
Est Cost Other 100000.0
Est Cost Other Details Estimated Other Costs Includes Estimated Value Of Damaged Home.
Gas Cost In Mcf 2.88
Est Cost Unintentional Release 645.0
Est Cost Intentional Release 0.0
Prpty 128973.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 0.0
Num Persons Hosp Not Ovnght 1.0
Num Injured Treated By Emt 1.0
Num Resident Building Affctd 95.0
Num Business Building Affctd 3.0
Accident Psig 43.0
Normal Psig 47.0
Mop Psig 60.0
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 2014-04-24 00:00:00
Accident Pressure Pressure Did Not Exceed Maop
Gas Odorized System Type Combination Of Odorization Types
Gas Odorized Level 0.1
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Notification From Third Party That Caused The Incident
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details This was a 3rd party line strike to operator's system.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Excavation Damage
Cause Details Excavation Damage By Third Party
Ex Party Type Excavation Damage By Third Party
Prior Notification Ind Yes
One Call System Ind Yes
State Law Exempt Ind No
Notify Cga Dirt Yes
Public Row Ind Yes
Public Subtype City Street
Excavator Type Contractor
Excavator Equipment Boring
Work Performed Telecommunications
One Call Notified Ind Yes
One Call Ticket Num 330000015
Locator Type Utility Owner
Visible Marks Yes
Service Interruption No
Root Cause Category Miscellaneous Root Causes
Root Cause Type Root Cause Not Listed (Comment Required)
Root Cause Type Other Data Not Collected
Preparer Name S***** P****
Preparer Title Manager Safety Mgmt Systems And Quality Assurance
Preparer Email S******@t*********.com
Preparer Telephone (813) 275-3730
Local Contact Name T**** J*****
Local Contact Email T*******@t*********.com
Local Contact Telephone (813) 275-3736
Authorizer Name S***** P****
Authorizer Title Manager Safety Mgmt Systems And Quality Assurance
Authorizer Telephone (813) 275-3730
Authorizer Email S******@t*********.com
Narrative Damaged 2" pe main by third party next generation management inc. Bore crew. The damaged gas line resulted in gas migrating into a severed sewer line which was also damaged by next generation management inc. In the same excavation. It appears the gas migrated from the county sewer system through the home's sewer system and unexpectedly into the home where the gas ignited, resulting in an explosion. Additional notes: part a question 21c - the amount of gas reported is an estimate of .55. The PHMSA portal rounded the amount to 1.0. Part a question 22 - the number of general public evacuated is an estimate based on a review of the responding fire departments' incident reports and assuming that there were 2 occupants per residential building and 5 occupants per business building. Part d question 6 - the number of residential buildings affected is an estimate based on a review of the responding fire departments' incident reports. Part d question 7 - the number of business buildings affected is an estimate based on a review of the responding fire departments' incident reports.

All rights reserved. Copyright © by ClearPHMSA