HL incident on 2020-09-18 — OK

Operator
Magellan Pipeline Company, Lp
Cause
Equipment Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$150
Incident datetime
2020-09-18 10:40
Report number
Location
OK
Narrative
At 10:40 on 9/18/20, magellan operations personnel noticed product leaking from a quick connect fitting on the 1/2" tubing from a thermal relief. The tubing was immediate isolated and cleanup activities were initiated. Upon further investigation it was discovered that the quick connect fitting o-ring did not seat properly. This was a malfunction of the device and is not anticipated to be a systemic issue. The fitting was replaced and the line was placed back into service. Supplemental/final 10/20/20: updated part h.
Detailed record list
Report Received Date
2020-10-15 00:00:00
Iyear
2020
Report Number
20200279
Supplemental Number
34401
Report Type
Supplemental Final
Operator Id
Name
Magellan Pipeline Company, Lp
Operator Street Address
100 West 5th Street
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2020-09-18 10:40:00
Location Latitude
Location Longitude
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
0.12
Recovered Bbls
0.12
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2020-09-18 10:40:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Leak Was Effectively Isolated Without The Line Being Shut Down
On Site Datetime
2020-09-18 10:40:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Cheyenne Terminal
Segment Name
Terminal No. 419
Onshore State Abbreviation
Wy
Onshore Postal Code
82007
Onshore City Name
Not Within A Municipality
Onshore County Name
Laramie
Designated Location
Milepost/valve Station
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Tubing
Installation Year
1995
Material Involved
Material Other Than Carbon Steel
Material Details
Stainless Steel Quick Connect Fitting
Release Type
Leak
Leak Type
Seal Or Packing
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
High Pop Ind
Yes
High Pop Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
150
Est Cost Emergency
800
Est Cost Environmental
0
Est Cost Other
0
Prpty
950
Accident Psig
65
Mop Psig
275
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The release was isolated to the facility which is not monitored via scada or cpm within the operations control center.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Non-Threaded Connection Failure
Eq Failure Type
Non-Threaded Connection Failure
Other Non Threaded Ind
O-Ring
Eq Additional Other Ind
Yes
Eq Additional Other Details
O-Ring On Quick Connect Fitting Did Not Seat Correctly
Preparer Name
S****** L******
Preparer Title
Ai Analyst
Preparer Email
S**************@m*********.com
Preparer Telephone
918-574-7327
Preparer Fax
918-574-7376
Prepared Date
2020-10-20 00:00:00
Authorizer Name
G**** R****
Authorizer Telephone
918-574-7165
Authorizer Title
Supervisor Integrity Management
Authorizer Email
G**********@m*********.com
Narrative
At 10:40 on 9/18/20, magellan operations personnel noticed product leaking from a quick connect fitting on the 1/2" tubing from a thermal relief. The tubing was immediate isolated and cleanup activities were initiated. Upon further investigation it was discovered that the quick connect fitting o-ring did not seat properly. This was a malfunction of the device and is not anticipated to be a systemic issue. The fitting was replaced and the line was placed back into service. Supplemental/final 10/20/20: updated part h.
Report Received Date 2020-10-15 00:00:00
Iyear 2020
Report Number 20200279
Supplemental Number 34401
Report Type Supplemental Final
Operator Id 22610 PHMSA Enforcement
Name Magellan Pipeline Company, Lp
Operator Street Address 100 West 5th Street
Operator City Name Tulsa
Operator State Abbreviation OK
Operator Postal Code 74103
Local Datetime 2020-09-18 10:40:00
Location Latitude 41.107091 Google Maps OpenStreetMap
Location Longitude -104.833188 Google Maps OpenStreetMap
Commodity Released Type Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype Gasoline (Non-Ethanol)
Unintentional Release Bbls 0.12
Recovered Bbls 0.12
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2020-09-18 10:40:00
System Part Involved Onshore Terminal/tank Farm Equipment And Piping
On Off Shore Onshore
Shutdown Due Accident Ind No
Shutdown Explain Leak Was Effectively Isolated Without The Line Being Shut Down
On Site Datetime 2020-09-18 10:40:00
Nrc Rpt Num Nrc Notification Not Required NRC Report How to search
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0
Pipe Fac Name Cheyenne Terminal
Segment Name Terminal No. 419
Onshore State Abbreviation Wy
Onshore Postal Code 82007
Onshore City Name Not Within A Municipality
Onshore County Name Laramie
Designated Location Milepost/valve Station
Designated Name 0
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Interstate
Item Involved Tubing
Installation Year 1995
Material Involved Material Other Than Carbon Steel
Material Details Stainless Steel Quick Connect Fitting
Release Type Leak
Leak Type Seal Or Packing
Wildlife Impact Ind No
Soil Contamination Yes
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca Yes
Commodity Reached Hca Yes
High Pop Ind Yes
High Pop Yes No Yes
Est Cost Oper Paid 0
Est Cost Gas Released 0
Est Cost Prop Damage 150
Est Cost Emergency 800
Est Cost Environmental 0
Est Cost Other 0
Prpty 950
Accident Psig 65
Mop Psig 275
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind No
Cpm In Place Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details The release was isolated to the facility which is not monitored via scada or cpm within the operations control center.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Non-Threaded Connection Failure
Eq Failure Type Non-Threaded Connection Failure
Other Non Threaded Ind O-Ring
Eq Additional Other Ind Yes
Eq Additional Other Details O-Ring On Quick Connect Fitting Did Not Seat Correctly
Preparer Name S****** L******
Preparer Title Ai Analyst
Preparer Email S**************@m*********.com
Preparer Telephone 918-574-7327
Preparer Fax 918-574-7376
Prepared Date 2020-10-20 00:00:00
Authorizer Name G**** R****
Authorizer Telephone 918-574-7165
Authorizer Title Supervisor Integrity Management
Authorizer Email G**********@m*********.com
Narrative At 10:40 on 9/18/20, magellan operations personnel noticed product leaking from a quick connect fitting on the 1/2" tubing from a thermal relief. The tubing was immediate isolated and cleanup activities were initiated. Upon further investigation it was discovered that the quick connect fitting o-ring did not seat properly. This was a malfunction of the device and is not anticipated to be a systemic issue. The fitting was replaced and the line was placed back into service. Supplemental/final 10/20/20: updated part h.

All rights reserved. Copyright © by ClearPHMSA