HL incident on 2020-05-06 — OK
Operator
Enlink Permian, Llc
Cause
Incorrect Operation
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2020-05-06 10:00
Report number
Location
OK
Narrative
On may 6, 2020 at approximately 10:00 a.M., operations personnel discovered a spill of crude oil from the meter skid at bartholomew pump station. The spill was the result of a low drain 1" ball valve being opened allowing oil to free flow into a site sump which ultimately overflowed into a skid pan. Once at capacity, the skid pan then allowed the free-flowing oil to spill onto the landscape in the facility. Due to a recent rainfall event, the oil then flowed offsite through a culvert into a roadside ditch before finally being contained in a section of a drainage ditch on an adjacent landowner's property. At a later time enlink performed a root cause analysis and reviewed all pertinent data and concluded, since no one had done any maintenance or repairs on this skid, operator error was not a factor. The facility perimeter fencing shows no signs of breaking and entering, ruling out sabotage/vandalism. The team determined the root cause was more likely than not caused by a failed high-level sump switch, along with the valve going to atmosphere not being properly locked or car sealed, allowed product to overfill the sump, in turn allowing product to escape into a nearby non-flowing drainage ditch.
Detailed record list
Report Received Date
2020-06-04 00:00:00
Iyear
2020
Report Number
20200160
Supplemental Number
33968
Report Type
Supplemental Final
Operator Id
32634
Name
Enlink Permian, Llc
Operator Street Address
100 West 5th St.
Operator City Name
Tulsa
Operator State Abbreviation
OK
Operator Postal Code
74103
Local Datetime
2020-05-06 12:37:00
Location Latitude
29.124953
Location Longitude
-97.387109
Commodity Released Type
Crude Oil
Unintentional Release Bbls
55
Recovered Bbls
55
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Cpm Leak Detection System Or Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Calculations)
Incident Identified Datetime
2020-05-06 10:00:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2020-05-06 09:00:00
Restart Datetime
2020-05-06 16:00:00
On Site Datetime
2020-05-06 15:00:00
Nrc Rpt Datetime
2020-05-06 13:37:00
Nrc Rpt Num
1276759
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Victoria Express Pipeline
Segment Name
540000y
Onshore State Abbreviation
Tx
Onshore Postal Code
77954
Onshore City Name
Cuero
Onshore County Name
Dewitt
Designated Location
Milepost/valve Station
Designated Name
Bartholomew
Federal
No
Location Type
Originated On Operator-Controlled Property, But Then Flowed Or Migrated Off The Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Valve
Valve Type
Auxiliary Or Other Valve
Installation Year
2014
Material Involved
Carbon Steel
Release Type
Overfill Or Overflow
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
Yes
Surface Contam Ind
Yes
Amount Released
3
Rel Water Name
Drainage Ditch
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
1600
Est Cost Prop Damage
0
Est Cost Emergency
10000
Est Cost Environmental
11100
Est Cost Other
0
Prpty
22700
Accident Psig
150
Mop Psig
720
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
Yes
Cpm Conf Ind
Yes
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Leak detection was working properly and pipeline control was able to notify operations to investigate the pipeline for leaks.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Incorrect Operation
Cause Details
Tank, Vessel, Or Sump/separator Allowed Or Caused To Overfill Or Overflow
Operation Type
Tank, Vessel, Or Sump/separator Allowed Or Caused To Overfill Or Overflow
Overflow Other Ind
Valve Misalignment
Related Inadequate Proc Ind
Yes
Related No Proc Ind
Yes
Category Type
Normal Operating Conditions
Operator Qualification Ind
Yes
Qualified Individuals
Yes, They Were Qualified For The Task(S)
Preparer Name
J*** R****
Preparer Title
Senior Dot Pipeline Complaince Specialist
Preparer Email
J*******@e*****.com
Preparer Telephone
9406831112
Prepared Date
2020-06-29 00:00:00
Authorizer Name
B****** M*****
Authorizer Telephone
4323129609
Authorizer Title
Pipeline Integrity Specialist
Authorizer Email
B*************@e*****.com
Narrative
On may 6, 2020 at approximately 10:00 a.M., operations personnel discovered a spill of crude oil from the meter skid at bartholomew pump station. The spill was the result of a low drain 1" ball valve being opened allowing oil to free flow into a site sump which ultimately overflowed into a skid pan. Once at capacity, the skid pan then allowed the free-flowing oil to spill onto the landscape in the facility. Due to a recent rainfall event, the oil then flowed offsite through a culvert into a roadside ditch before finally being contained in a section of a drainage ditch on an adjacent landowner's property. At a later time enlink performed a root cause analysis and reviewed all pertinent data and concluded, since no one had done any maintenance or repairs on this skid, operator error was not a factor. The facility perimeter fencing shows no signs of breaking and entering, ruling out sabotage/vandalism. The team determined the root cause was more likely than not caused by a failed high-level sump switch, along with the valve going to atmosphere not being properly locked or car sealed, allowed product to overfill the sump, in turn allowing product to escape into a nearby non-flowing drainage ditch.
| Report Received Date | 2020-06-04 00:00:00 |
|---|---|
| Iyear | 2020 |
| Report Number | 20200160 |
| Supplemental Number | 33968 |
| Report Type | Supplemental Final |
| Operator Id | 32634 PHMSA Enforcement |
| Name | Enlink Permian, Llc |
| Operator Street Address | 100 West 5th St. |
| Operator City Name | Tulsa |
| Operator State Abbreviation | OK |
| Operator Postal Code | 74103 |
| Local Datetime | 2020-05-06 12:37:00 |
| Location Latitude | 29.124953 Google Maps OpenStreetMap |
| Location Longitude | -97.387109 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 55 |
| Recovered Bbls | 55 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Cpm Leak Detection System Or Scada-Based Information (Such As Alarm(S), Alert(S), Event(S), And/or Volume Calculations) |
| Incident Identified Datetime | 2020-05-06 10:00:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2020-05-06 09:00:00 |
| Restart Datetime | 2020-05-06 16:00:00 |
| On Site Datetime | 2020-05-06 15:00:00 |
| Nrc Rpt Datetime | 2020-05-06 13:37:00 |
| Nrc Rpt Num | 1276759 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Victoria Express Pipeline |
| Segment Name | 540000y |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 77954 |
| Onshore City Name | Cuero |
| Onshore County Name | Dewitt |
| Designated Location | Milepost/valve Station |
| Designated Name | Bartholomew |
| Federal | No |
| Location Type | Originated On Operator-Controlled Property, But Then Flowed Or Migrated Off The Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| Item Involved | Valve |
| Valve Type | Auxiliary Or Other Valve |
| Installation Year | 2014 |
| Material Involved | Carbon Steel |
| Release Type | Overfill Or Overflow |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | Yes |
| Soil Remed Ind | Yes |
| Water Contam Ind | Yes |
| Surface Contam Ind | Yes |
| Amount Released | 3 |
| Rel Water Name | Drainage Ditch |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 1600 |
| Est Cost Prop Damage | 0 |
| Est Cost Emergency | 10000 |
| Est Cost Environmental | 11100 |
| Est Cost Other | 0 |
| Prpty | 22700 |
| Accident Psig | 150 |
| Mop Psig | 720 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | Yes |
| Cpm Conf Ind | Yes |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Leak detection was working properly and pipeline control was able to notify operations to investigate the pipeline for leaks. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Incorrect Operation |
| Cause Details | Tank, Vessel, Or Sump/separator Allowed Or Caused To Overfill Or Overflow |
| Operation Type | Tank, Vessel, Or Sump/separator Allowed Or Caused To Overfill Or Overflow |
| Overflow Other Ind | Valve Misalignment |
| Related Inadequate Proc Ind | Yes |
| Related No Proc Ind | Yes |
| Category Type | Normal Operating Conditions |
| Operator Qualification Ind | Yes |
| Qualified Individuals | Yes, They Were Qualified For The Task(S) |
| Preparer Name | J*** R**** |
| Preparer Title | Senior Dot Pipeline Complaince Specialist |
| Preparer Email | J*******@e*****.com |
| Preparer Telephone | 9406831112 |
| Prepared Date | 2020-06-29 00:00:00 |
| Authorizer Name | B****** M***** |
| Authorizer Telephone | 4323129609 |
| Authorizer Title | Pipeline Integrity Specialist |
| Authorizer Email | B*************@e*****.com |
| Narrative | On may 6, 2020 at approximately 10:00 a.M., operations personnel discovered a spill of crude oil from the meter skid at bartholomew pump station. The spill was the result of a low drain 1" ball valve being opened allowing oil to free flow into a site sump which ultimately overflowed into a skid pan. Once at capacity, the skid pan then allowed the free-flowing oil to spill onto the landscape in the facility. Due to a recent rainfall event, the oil then flowed offsite through a culvert into a roadside ditch before finally being contained in a section of a drainage ditch on an adjacent landowner's property. At a later time enlink performed a root cause analysis and reviewed all pertinent data and concluded, since no one had done any maintenance or repairs on this skid, operator error was not a factor. The facility perimeter fencing shows no signs of breaking and entering, ruling out sabotage/vandalism. The team determined the root cause was more likely than not caused by a failed high-level sump switch, along with the valve going to atmosphere not being properly locked or car sealed, allowed product to overfill the sump, in turn allowing product to escape into a nearby non-flowing drainage ditch. |
External Resources
PHMSA pipeline safety insights.
Product
Features
Company
All rights reserved. Copyright © by ClearPHMSA