GD incident on 2020-10-08 — TX
Operator
Texas Gas Service Company, A Division Of One Gas, Inc.
Cause
Notification Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$8,000
Incident datetime
2020-10-08 10:33
Report number
Location
TX, HILDAGO
Narrative
At 10:33 am october 8th texas gas service (tgs) dispatch received a call from manuel derueda notifying them of a damage to a tgs facility. Tgs's 12" coated steel gas main was damaged by a 3rd party contractor (city of mcallen public works department). The city of mcallen was conducting road and drainage work with a road grader near the intersection of stewart rd and mile 8 in north mcallen, tx. The road grader was making deep cuts of soil to complete a new road construction project. Texas gas service facilities had 24" to 30" depth of cover in this area. The road grader struck the 12" pipeline causing a 4" x 5" triangular hole in its facilities. The city of mcallen did not make notification to the one-call center to perform this work. At 4:31 pm on october 8th texas gas service confirmed that the gas loss was over the 3000 mcf PHMSA reportable threshold. At 4:45 pm october 8th texas gas service reported the incident to the nrc (#1289317) and conducted the 48 hr update per PHMSA requirements at 9:34 am october 10th nrc (#1289424). Supplemental information 3/5/21 the city of mcallen has been contacted electronically concerning this incident. Also, after safety protocols allow US to (due to the pandemic), texas gas service will meet with the city of mcallen to review texas utility cody 251, specifically chapter 18, section 18.3 excavator notice to notification center, section 18.4 excavator obligation to avoid damage to underground pipelines, section 18.5 operator and excavator obligations with respect to positive response in an effort to prevent future damages. Texas gas service damage prevention group reviews all excavation damages to track and monitor repeat offenders for at-fault excavation damages, currently the city of mcallen has not yet met the repeat offender list. Texas gas service will require safe excavation meetings with the city of mcallen if additional at-fault excavation damages are experienced.
Detailed record list
Occurred At
2020-10-08 10:33:00
Year
2020
Report Received Date
2020-11-04 00:00:00
Iyear
2020.0
Report Number
20200111.0
Supplemental Number
35003.0
Report Type
Supplemental Final
Operator Id
18532
Name
Texas Gas Service Company, A Division Of One Gas, Inc.
Operator Street Address
1301 Mopac Expressway Suite 400
Operator City Name
Austin
Operator State Abbreviation
TX
Operator Postal Code
78746
Local Datetime
2020-10-08 16:31:00
Time Zone
Central
Daylight Savings Ind
No
Location Street Address
Near Intersection (Stewart Rd And Mile 8)
Location City Name
Mcallen
Location County Name
Hildago
Location State Abbreviation
TX
Location Postal Code
78573
Location Latitude
26.32707
Location Longitude
-98.28078
Flow Cont Key Crit Ind
Yes
Nrc Rpt Datetime
2020-10-08 16:45:00
Nrc Rpt Num
1289317
Commodity Released Type
Natural Gas
Unintentional Release
10000.0
Intentional Release
0.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2020-10-08 10:33:00
Communication State Fed Ind
No
On Site Datetime
2020-10-08 11:20:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
30.0
Other Underground Facilities
No
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
1927.0
Pipe Diameter
12.75
Pipe Specification
Api-5l
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Erw
Wt Steel
0.25
Release Type
Mechanical Puncture
Puncture Axial
4.0
Puncture Circum
5.0
Class Location Type
Class 2 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
8000.0
Est Cost Emergency
2000.0
Est Cost Other
0.0
Gas Cost In Mcf
2.3031
Est Cost Unintentional Release
23031.0
Est Cost Intentional Release
0.0
Prpty
33031.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
0.0
Num Persons Hosp Not Ovnght
0.0
Num Injured Treated By Emt
0.0
Num Resident Building Affctd
0.0
Num Business Building Affctd
0.0
Accident Psig
170.0
Normal Psig
170.0
Mop Psig
188.0
Mop Cfr Section
192.619(A)(2)
Maop Established Date
2004-10-13 00:00:00
Accident Pressure
Pressure Did Not Exceed Maop
Gas Odorized System Type
Injection Pump
Gas Odorized Lvl Not Msrd Ind
Yes
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Accident Identifier
Other
Accident Details
Call From Manuel Derueda To Texas Gas Service Dispatch At 10:33 Am
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
An inquiry to the control room timelines occurred. First alarm came in at 10:49 am via scada. Control room call to our dispatch occurred at 10:51 am, pressure & measurement technician personnel routed to job site at 10:58 am. No additional inquiries are necessary to the controller(s) actions.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
No
State Law Exempt Ind
Unknown
Notify Cga Dirt
Yes
Public Row Ind
Yes
Public Subtype
City Street
Excavator Type
Municipality
Excavator Equipment
Grader/scraper
Work Performed
Road Work
One Call Notified Ind
No
Service Interruption
No
Root Cause Category
Notification Issue
Root Cause Type
No Notification Made To The One-Call Center/811
Preparer Name
D*** L*******
Preparer Title
Director Engineering Texas Gas Service
Preparer Email
D************@o*****.com
Preparer Telephone
512-370-8213
Authorizer Name
D*** L*******
Authorizer Title
Director Engineering Texas Gas Service
Authorizer Telephone
512-370-8213
Authorizer Email
D************@o*****.com
Narrative
At 10:33 am october 8th texas gas service (tgs) dispatch received a call from manuel derueda notifying them of a damage to a tgs facility. Tgs's 12" coated steel gas main was damaged by a 3rd party contractor (city of mcallen public works department). The city of mcallen was conducting road and drainage work with a road grader near the intersection of stewart rd and mile 8 in north mcallen, tx. The road grader was making deep cuts of soil to complete a new road construction project. Texas gas service facilities had 24" to 30" depth of cover in this area. The road grader struck the 12" pipeline causing a 4" x 5" triangular hole in its facilities. The city of mcallen did not make notification to the one-call center to perform this work. At 4:31 pm on october 8th texas gas service confirmed that the gas loss was over the 3000 mcf PHMSA reportable threshold. At 4:45 pm october 8th texas gas service reported the incident to the nrc (#1289317) and conducted the 48 hr update per PHMSA requirements at 9:34 am october 10th nrc (#1289424). Supplemental information 3/5/21 the city of mcallen has been contacted electronically concerning this incident. Also, after safety protocols allow US to (due to the pandemic), texas gas service will meet with the city of mcallen to review texas utility cody 251, specifically chapter 18, section 18.3 excavator notice to notification center, section 18.4 excavator obligation to avoid damage to underground pipelines, section 18.5 operator and excavator obligations with respect to positive response in an effort to prevent future damages. Texas gas service damage prevention group reviews all excavation damages to track and monitor repeat offenders for at-fault excavation damages, currently the city of mcallen has not yet met the repeat offender list. Texas gas service will require safe excavation meetings with the city of mcallen if additional at-fault excavation damages are experienced.
| Occurred At | 2020-10-08 10:33:00 |
|---|---|
| Year | 2020 |
| Report Received Date | 2020-11-04 00:00:00 |
| Iyear | 2020.0 |
| Report Number | 20200111.0 |
| Supplemental Number | 35003.0 |
| Report Type | Supplemental Final |
| Operator Id | 18532 PHMSA Enforcement |
| Name | Texas Gas Service Company, A Division Of One Gas, Inc. |
| Operator Street Address | 1301 Mopac Expressway Suite 400 |
| Operator City Name | Austin |
| Operator State Abbreviation | TX |
| Operator Postal Code | 78746 |
| Local Datetime | 2020-10-08 16:31:00 |
| Time Zone | Central |
| Daylight Savings Ind | No |
| Location Street Address | Near Intersection (Stewart Rd And Mile 8) |
| Location City Name | Mcallen |
| Location County Name | Hildago |
| Location State Abbreviation | TX |
| Location Postal Code | 78573 |
| Location Latitude | 26.32707 Google Maps OpenStreetMap |
| Location Longitude | -98.28078 Google Maps OpenStreetMap |
| Flow Cont Key Crit Ind | Yes |
| Nrc Rpt Datetime | 2020-10-08 16:45:00 |
| Nrc Rpt Num | 1289317 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 10000.0 |
| Intentional Release | 0.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2020-10-08 10:33:00 |
| Communication State Fed Ind | No |
| On Site Datetime | 2020-10-08 11:20:00 |
| Federal | No |
| Location Type | Public Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Soil |
| Depth Of Cover | 30.0 |
| Other Underground Facilities | No |
| Crossing | No |
| Pipe Facility Type | Investor Owned |
| System Part Involved | Main |
| Installation Year | 1927.0 |
| Pipe Diameter | 12.75 |
| Pipe Specification | Api-5l |
| Pipe Manufacturer | Unknown |
| Material Involved | Steel |
| Steel Seam Type | Other |
| Steel Seam Type Details | Erw |
| Wt Steel | 0.25 |
| Release Type | Mechanical Puncture |
| Puncture Axial | 4.0 |
| Puncture Circum | 5.0 |
| Class Location Type | Class 2 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 8000.0 |
| Est Cost Emergency | 2000.0 |
| Est Cost Other | 0.0 |
| Gas Cost In Mcf | 2.3031 |
| Est Cost Unintentional Release | 23031.0 |
| Est Cost Intentional Release | 0.0 |
| Prpty | 33031.0 |
| Commercial Affected | 0.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 0.0 |
| Num Persons Hosp Not Ovnght | 0.0 |
| Num Injured Treated By Emt | 0.0 |
| Num Resident Building Affctd | 0.0 |
| Num Business Building Affctd | 0.0 |
| Accident Psig | 170.0 |
| Normal Psig | 170.0 |
| Mop Psig | 188.0 |
| Mop Cfr Section | 192.619(A)(2) View CFR 49 §192 |
| Maop Established Date | 2004-10-13 00:00:00 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Gas Odorized System Type | Injection Pump |
| Gas Odorized Lvl Not Msrd Ind | Yes |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Accident Identifier | Other |
| Accident Details | Call From Manuel Derueda To Texas Gas Service Dispatch At 10:33 Am |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | An inquiry to the control room timelines occurred. First alarm came in at 10:49 am via scada. Control room call to our dispatch occurred at 10:51 am, pressure & measurement technician personnel routed to job site at 10:58 am. No additional inquiries are necessary to the controller(s) actions. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Excavation Damage |
| Cause Details | Excavation Damage By Third Party |
| Ex Party Type | Excavation Damage By Third Party |
| Prior Notification Ind | No |
| State Law Exempt Ind | Unknown |
| Notify Cga Dirt | Yes |
| Public Row Ind | Yes |
| Public Subtype | City Street |
| Excavator Type | Municipality |
| Excavator Equipment | Grader/scraper |
| Work Performed | Road Work |
| One Call Notified Ind | No |
| Service Interruption | No |
| Root Cause Category | Notification Issue |
| Root Cause Type | No Notification Made To The One-Call Center/811 |
| Preparer Name | D*** L******* |
| Preparer Title | Director Engineering Texas Gas Service |
| Preparer Email | D************@o*****.com |
| Preparer Telephone | 512-370-8213 |
| Authorizer Name | D*** L******* |
| Authorizer Title | Director Engineering Texas Gas Service |
| Authorizer Telephone | 512-370-8213 |
| Authorizer Email | D************@o*****.com |
| Narrative | At 10:33 am october 8th texas gas service (tgs) dispatch received a call from manuel derueda notifying them of a damage to a tgs facility. Tgs's 12" coated steel gas main was damaged by a 3rd party contractor (city of mcallen public works department). The city of mcallen was conducting road and drainage work with a road grader near the intersection of stewart rd and mile 8 in north mcallen, tx. The road grader was making deep cuts of soil to complete a new road construction project. Texas gas service facilities had 24" to 30" depth of cover in this area. The road grader struck the 12" pipeline causing a 4" x 5" triangular hole in its facilities. The city of mcallen did not make notification to the one-call center to perform this work. At 4:31 pm on october 8th texas gas service confirmed that the gas loss was over the 3000 mcf PHMSA reportable threshold. At 4:45 pm october 8th texas gas service reported the incident to the nrc (#1289317) and conducted the 48 hr update per PHMSA requirements at 9:34 am october 10th nrc (#1289424). Supplemental information 3/5/21 the city of mcallen has been contacted electronically concerning this incident. Also, after safety protocols allow US to (due to the pandemic), texas gas service will meet with the city of mcallen to review texas utility cody 251, specifically chapter 18, section 18.3 excavator notice to notification center, section 18.4 excavator obligation to avoid damage to underground pipelines, section 18.5 operator and excavator obligations with respect to positive response in an effort to prevent future damages. Texas gas service damage prevention group reviews all excavation damages to track and monitor repeat offenders for at-fault excavation damages, currently the city of mcallen has not yet met the repeat offender list. Texas gas service will require safe excavation meetings with the city of mcallen if additional at-fault excavation damages are experienced. |