GTG incident on 2020-09-11 — TX

Operator
Enbridge Offshore (Gas Gathering) L.l.c.
Cause
Corrosion Failure
Commodity
Natural Gas
Program
GTG
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$111,000
Incident datetime
2020-09-11 13:00
Report number
Location
TX
Narrative
At approximately 1:00 pm. Cdt on september 11, 2020, enbridge offshore gas gathering l.L.C.'s (enbridge offshore) discovered a leak on a 2-inch diameter by-pass line on a platform (smi 76) located on sm 76p in the gulf of mexico. Enbridge offshore subsequently depressurized the line after attempting to isolate the pipeline and stop the leak. Enbridge offshore notified the nrc at 3:55 cdt after making attempts to isolate the line and stop the leak. The pipeline remains out of service at this time due to hurricane laura and hurricane delta. The preliminary direct cause of the leak is atmospheric corrosion. Updated 4-8-2021 garden banks, smi-76 experienced a pinhole leak on a 2-inch bypass line located upstream of the 30-inch at a platform shutdown valve. The 2-inch pipe was covered with a composite reinforcement wrap. After removing the composite reinforcement wrap it was determined that the leak was the result of an external corrosion pin hole beneath the composite reinforcement wrap. The line has been replaced and recoated.
Detailed record list
Report Received Date
2020-10-08 00:00:00
Iyear
2020
Report Number
20200104
Supplemental Number
35153
Report Type
Supplemental Final
Operator Id
Name
Enbridge Offshore (Gas Gathering) L.l.c.
Operator Street Address
915 North Eldridge Parkway
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77079
Local Datetime
2020-09-11 13:00:00
Time Zone
Central
Daylight Savings Ind
Yes
Location Latitude
Location Longitude
-91.95944444
Nrc Rpt Num
Nrc Rpt Datetime
2020-09-11 15:55:00
Additional Nrc Report Numbers
1287227
Commodity Released Type
Natural Gas
Unintentional Release
65
Intentional Release
48181
Accompanying Liquid
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Status When Identified
Routine Start-Up
Shutdown Due Accident Ind
No
Shutdown Explain
The Platform Was Shut-In Due To Hurricane Laura
Communication State Fed Ind
No
Ignite Ind
No
Num Pub Evacuated
0
Incident Identified Datetime
2020-09-11 13:00:00
On Site Datetime
2020-09-11 13:00:00
On Off Shore
Offshore
Pipe Fac Name
Enbridge Offshore Gas Gathering, L.l.c.
Segment Name
Phmsa Opid #: 31485
Off Water Depth
140
Off Accident Origin
On The Outer Continental Shelf (Ocs)
Ocs Type
Ocs-Gulf Of Mexico
Off Ocs Area
Sm
Off Ocs Block
76p
Off Area Accident Type
Platform
Pipe Facility Type
Interstate
System Part Involved
Offshore Platform, Including Platform-Mounted Equipment And Piping
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
2
Puddle Weld Ind
No
Pipe Wall Thickness
0.218
Pipe Smys
35000
Pipe Specification
Unknown
Pipe Seam Type
Seamless
Pipe Manufacturer
Unknown
Pipe Coating Type
Paint
Coating Applied Ind
Yes
Installation Year
1997
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Class Location Type
Class 1 Location
Could Be Hca
No
Pir Radius
73
Heat Damage Ind
No
Non Heat Damage Ind
No
Est Cost Oper Paid
0
Est Cost Unintentional Release
153
Est Cost Intentional Release
113240
Est Cost Prop Damage
111000
Est Cost Emergency
0
Est Cost Other
0
Est Cost Other Details
Cost Of $83,000 For Contractors, $28,000 For Boat Service.
Gas Cost In Mcf
2.3503
Prpty
224393
Num Persons Hosp Not Ovnght
0
Num Injured Treated By Emt
0
Num Resident Building Affctd
0
Num Business Building Affctd
0
Wildlife Impact Ind
No
Accident Psig
788
Gas Flow In Pipe In Mcf
0
Mop Psig
1975
Mop Cfr Section
192.619(A)(2)
Maop Established Date
1997-02-17 00:00:00
Maop Reversal Flow Ind
No
Accident Pressure
Pressure Did Not Exceed Maop
Pressure Restriction Ind
No
Gas Required Odorized Ind
No
Pipeline Function
Transmission System
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
It was determined the controllers actions did not contribute to the incident. The leak was too small to be identified by the control room personnel.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
External Corrosion
Internal External
External Corrosion
Visual Exam Results
General Corrosion
Atmosphere Corrosion Ind
Yes
Field Exam Basis Ind
Yes
Underground Location
No
Externally Coated
Yes
Prior Damage
No
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Extrnl Cor Atmospheric Ind
Yes
Preparer Name
M****** M******
Preparer Title
Engineer Specialist Operational Compliance
Preparer Email
M**************@e*******.com
Preparer Telephone
612-805-6542
Authorizer Name
N***** A****
Authorizer Title
Manager - Operational Compliance
Authorizer Telephone
713-627-5008
Authorizer Email
N***********@e*******.com
Narrative
At approximately 1:00 pm. Cdt on september 11, 2020, enbridge offshore gas gathering l.L.C.'s (enbridge offshore) discovered a leak on a 2-inch diameter by-pass line on a platform (smi 76) located on sm 76p in the gulf of mexico. Enbridge offshore subsequently depressurized the line after attempting to isolate the pipeline and stop the leak. Enbridge offshore notified the nrc at 3:55 cdt after making attempts to isolate the line and stop the leak. The pipeline remains out of service at this time due to hurricane laura and hurricane delta. The preliminary direct cause of the leak is atmospheric corrosion. Updated 4-8-2021 garden banks, smi-76 experienced a pinhole leak on a 2-inch bypass line located upstream of the 30-inch at a platform shutdown valve. The 2-inch pipe was covered with a composite reinforcement wrap. After removing the composite reinforcement wrap it was determined that the leak was the result of an external corrosion pin hole beneath the composite reinforcement wrap. The line has been replaced and recoated.
Report Received Date 2020-10-08 00:00:00
Iyear 2020
Report Number 20200104
Supplemental Number 35153
Report Type Supplemental Final
Operator Id 31485 PHMSA Enforcement
Name Enbridge Offshore (Gas Gathering) L.l.c.
Operator Street Address 915 North Eldridge Parkway
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77079
Local Datetime 2020-09-11 13:00:00
Time Zone Central
Daylight Savings Ind Yes
Location Latitude 28.57352778 Google Maps OpenStreetMap
Location Longitude -91.95944444 Google Maps OpenStreetMap
Nrc Rpt Num 1287127 NRC Report How to search
Nrc Rpt Datetime 2020-09-11 15:55:00
Additional Nrc Report Numbers 1287227
Commodity Released Type Natural Gas
Unintentional Release 65
Intentional Release 48181
Accompanying Liquid 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Status When Identified Routine Start-Up
Shutdown Due Accident Ind No
Shutdown Explain The Platform Was Shut-In Due To Hurricane Laura
Communication State Fed Ind No
Ignite Ind No
Num Pub Evacuated 0
Incident Identified Datetime 2020-09-11 13:00:00
On Site Datetime 2020-09-11 13:00:00
On Off Shore Offshore
Pipe Fac Name Enbridge Offshore Gas Gathering, L.l.c.
Segment Name Phmsa Opid #: 31485
Off Water Depth 140
Off Accident Origin On The Outer Continental Shelf (Ocs)
Ocs Type Ocs-Gulf Of Mexico
Off Ocs Area Sm
Off Ocs Block 76p
Off Area Accident Type Platform
Pipe Facility Type Interstate
System Part Involved Offshore Platform, Including Platform-Mounted Equipment And Piping
Item Involved Pipe
Pipe Type Pipe Body
Pipe Diameter 2
Puddle Weld Ind No
Pipe Wall Thickness 0.218
Pipe Smys 35000
Pipe Specification Unknown
Pipe Seam Type Seamless
Pipe Manufacturer Unknown
Pipe Coating Type Paint
Coating Applied Ind Yes
Installation Year 1997
Manufactured Year Unknown
Material Involved Carbon Steel
Release Type Leak
Leak Type Pinhole
Class Location Type Class 1 Location
Could Be Hca No
Pir Radius 73
Heat Damage Ind No
Non Heat Damage Ind No
Est Cost Oper Paid 0
Est Cost Unintentional Release 153
Est Cost Intentional Release 113240
Est Cost Prop Damage 111000
Est Cost Emergency 0
Est Cost Other 0
Est Cost Other Details Cost Of $83,000 For Contractors, $28,000 For Boat Service.
Gas Cost In Mcf 2.3503
Prpty 224393
Num Persons Hosp Not Ovnght 0
Num Injured Treated By Emt 0
Num Resident Building Affctd 0
Num Business Building Affctd 0
Wildlife Impact Ind No
Accident Psig 788
Gas Flow In Pipe In Mcf 0
Mop Psig 1975
Mop Cfr Section 192.619(A)(2) View CFR 49 §192
Maop Established Date 1997-02-17 00:00:00
Maop Reversal Flow Ind No
Accident Pressure Pressure Did Not Exceed Maop
Pressure Restriction Ind No
Gas Required Odorized Ind No
Pipeline Function Transmission System
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details It was determined the controllers actions did not contribute to the incident. The leak was too small to be identified by the control room personnel.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Corrosion Failure
Cause Details External Corrosion
Internal External External Corrosion
Visual Exam Results General Corrosion
Atmosphere Corrosion Ind Yes
Field Exam Basis Ind Yes
Underground Location No
Externally Coated Yes
Prior Damage No
Collected Data Ind No
Has Hydrtst Conduc Before Ind No
Direct Asmnt Conducted No
Non Destructive Exam Ind No
Extrnl Cor Atmospheric Ind Yes
Preparer Name M****** M******
Preparer Title Engineer Specialist Operational Compliance
Preparer Email M**************@e*******.com
Preparer Telephone 612-805-6542
Authorizer Name N***** A****
Authorizer Title Manager - Operational Compliance
Authorizer Telephone 713-627-5008
Authorizer Email N***********@e*******.com
Narrative At approximately 1:00 pm. Cdt on september 11, 2020, enbridge offshore gas gathering l.L.C.'s (enbridge offshore) discovered a leak on a 2-inch diameter by-pass line on a platform (smi 76) located on sm 76p in the gulf of mexico. Enbridge offshore subsequently depressurized the line after attempting to isolate the pipeline and stop the leak. Enbridge offshore notified the nrc at 3:55 cdt after making attempts to isolate the line and stop the leak. The pipeline remains out of service at this time due to hurricane laura and hurricane delta. The preliminary direct cause of the leak is atmospheric corrosion. Updated 4-8-2021 garden banks, smi-76 experienced a pinhole leak on a 2-inch bypass line located upstream of the 30-inch at a platform shutdown valve. The 2-inch pipe was covered with a composite reinforcement wrap. After removing the composite reinforcement wrap it was determined that the leak was the result of an external corrosion pin hole beneath the composite reinforcement wrap. The line has been replaced and recoated.