GD incident on 2020-09-18 — TX

Operator
Atmos Energy Corporation - Mid-Tex
Cause
Excavation Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$61,349
Incident datetime
2020-09-18 13:20
Report number
Location
TX, TARRANT
Narrative
On september 18, 2020, excavator was boring telecommunications at 900 forrest park at rosedale and damaged a 6-inch poly main near 928 northton street. Atmos energy technician arrived at 1:25 pm and requested assistance at 1:30 pm. The technician evacuated the business at 928 northton street and, with the help of fire department personnel, a hotel nearby. Forrest park was blocked north of rosedale, and westbound rosedale was blocked off as well. Crews responded, arriving at 1:40 pm and determined that the 12-inch steel main the 6-inch tied into would have to be shut off using short stop fittings. Atmos energy contractor was called in to assist. During the course of repairs, the gas was shut off at 5:20 am on 9/20/2020. Two restaurants were out of service. Service was restored at 11:58 am on 9/21/2020. Per atmos energy's investigation, line locates were completed correctly, and the damaged main was marked accurately. It was determined that this incident will reach the reportable criteria at 4:00 pm on 9/18/20. Initial report #1287736 made to the nrc at 4:53 pm on 9/18/20. The 48-hour update #1287837 was provided at 2:14 pm on 9/20/20.
Detailed record list
Occurred At
2020-09-18 13:20:00
Year
2020
Report Received Date
2020-10-16 00:00:00
Iyear
2020.0
Report Number
20200099.0
Supplemental Number
34394.0
Report Type
Original Final
Operator Id
Name
Atmos Energy Corporation - Mid-Tex
Operator Street Address
5430 Lbj Freeway Suite 1800
Operator City Name
Dallas
Operator State Abbreviation
TX
Operator Postal Code
75240
Local Datetime
2020-09-18 16:00:00
Location Street Address
928 Northton
Location City Name
Fort Worth
Location County Name
Tarrant
Location State Abbreviation
TX
Location Postal Code
76110
Location Latitude
Location Longitude
-97.35241204
Nrc Rpt Datetime
2020-09-18 16:53:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
38308.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
175.0
Incident Identified Datetime
2020-09-18 13:20:00
On Site Datetime
2020-09-18 13:30:00
Federal
No
Location Type
Public Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
47.0
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
2011.0
Pipe Diameter
6.0
Pipe Specification
Astm D2513
Pipe Manufacturer
Performance Pipe
Material Involved
Plastic
Plastic Type
Polyethylene (Pe)
Plastic Sdr
11
Material Pe Pipe Code
2406
Release Type
Rupture
Rupture Orient
Circumferential
Rupture Length
3
Rupture Width
6
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
61349.0
Est Cost Emergency
135698.0
Est Cost Other
0.0
Est Cost Unintentional Release
219353.0
Prpty
416400.0
Commercial Affected
2.0
Industrial Affected
0.0
Residences Affected
0.0
Accident Psig
23.0
Normal Psig
23.0
Mop Psig
60.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
No
Accident Identifier
Notification From Emergency Responder
Investigation Status
No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Ex Hydrotest Leak Survey Date
2020-01-24 00:00:00
Ex Hydrotest Conducted Ind
No
Prior Notification Ind
Yes
One Call System Ind
Yes
Notify Cga Dirt
No
Public Row Ind
Yes
Public Subtype
City Street
Excavator Type
Utility
Excavator Equipment
Boring
Work Performed
Telecommunications
One Call Notified Ind
Yes
One Call Ticket Num
2075314339
One Call Center Name
Texas811
Locator Type
Contract Locator
Visible Marks
Yes
Service Interruption
Yes
Service Interruption Hours
41.0
Root Cause Category
Excavation Issue
Root Cause Type
Improper Excavation Practice Not Listed Above
Preparer Name
T*** M*****
Preparer Title
Operations Supervisor
Preparer Email
T**********@a**********.com
Preparer Telephone
469-261-2074
Authorizer Name
M**** S*****
Authorizer Title
V.p. Technical Services
Authorizer Telephone
214-206-2033
Authorizer Email
M***********@a**********.com
Narrative
On september 18, 2020, excavator was boring telecommunications at 900 forrest park at rosedale and damaged a 6-inch poly main near 928 northton street. Atmos energy technician arrived at 1:25 pm and requested assistance at 1:30 pm. The technician evacuated the business at 928 northton street and, with the help of fire department personnel, a hotel nearby. Forrest park was blocked north of rosedale, and westbound rosedale was blocked off as well. Crews responded, arriving at 1:40 pm and determined that the 12-inch steel main the 6-inch tied into would have to be shut off using short stop fittings. Atmos energy contractor was called in to assist. During the course of repairs, the gas was shut off at 5:20 am on 9/20/2020. Two restaurants were out of service. Service was restored at 11:58 am on 9/21/2020. Per atmos energy's investigation, line locates were completed correctly, and the damaged main was marked accurately. It was determined that this incident will reach the reportable criteria at 4:00 pm on 9/18/20. Initial report #1287736 made to the nrc at 4:53 pm on 9/18/20. The 48-hour update #1287837 was provided at 2:14 pm on 9/20/20.
Occurred At 2020-09-18 13:20:00
Year 2020
Report Received Date 2020-10-16 00:00:00
Iyear 2020.0
Report Number 20200099.0
Supplemental Number 34394.0
Report Type Original Final
Operator Id 31348 PHMSA Enforcement
Name Atmos Energy Corporation - Mid-Tex
Operator Street Address 5430 Lbj Freeway Suite 1800
Operator City Name Dallas
Operator State Abbreviation TX
Operator Postal Code 75240
Local Datetime 2020-09-18 16:00:00
Location Street Address 928 Northton
Location City Name Fort Worth
Location County Name Tarrant
Location State Abbreviation TX
Location Postal Code 76110
Location Latitude 32.73388311 Google Maps OpenStreetMap
Location Longitude -97.35241204 Google Maps OpenStreetMap
Nrc Rpt Datetime 2020-09-18 16:53:00
Nrc Rpt Num 1287736 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 38308.0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind No
Explode Ind No
Num Pub Evacuated 175.0
Incident Identified Datetime 2020-09-18 13:20:00
On Site Datetime 2020-09-18 13:30:00
Federal No
Location Type Public Property
Incident Area Type Underground
Incident Area Subtype Under Soil
Depth Of Cover 47.0
Crossing No
Pipe Facility Type Investor Owned
System Part Involved Main
Installation Year 2011.0
Pipe Diameter 6.0
Pipe Specification Astm D2513
Pipe Manufacturer Performance Pipe
Material Involved Plastic
Plastic Type Polyethylene (Pe)
Plastic Sdr 11
Material Pe Pipe Code 2406
Release Type Rupture
Rupture Orient Circumferential
Rupture Length 3
Rupture Width 6
Class Location Type Class 3 Location
Est Cost Oper Paid 0.0
Est Cost Prop Damage 61349.0
Est Cost Emergency 135698.0
Est Cost Other 0.0
Est Cost Unintentional Release 219353.0
Prpty 416400.0
Commercial Affected 2.0
Industrial Affected 0.0
Residences Affected 0.0
Accident Psig 23.0
Normal Psig 23.0
Mop Psig 60.0
Accident Pressure Pressure Did Not Exceed Maop
Scada In Place Ind No
Accident Identifier Notification From Emergency Responder
Investigation Status No, the facility was not monitored by a controller(s) at the time of the incident
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Excavation Damage
Cause Details Excavation Damage By Third Party
Ex Party Type Excavation Damage By Third Party
Ex Hydrotest Leak Survey Date 2020-01-24 00:00:00
Ex Hydrotest Conducted Ind No
Prior Notification Ind Yes
One Call System Ind Yes
Notify Cga Dirt No
Public Row Ind Yes
Public Subtype City Street
Excavator Type Utility
Excavator Equipment Boring
Work Performed Telecommunications
One Call Notified Ind Yes
One Call Ticket Num 2075314339
One Call Center Name Texas811
Locator Type Contract Locator
Visible Marks Yes
Service Interruption Yes
Service Interruption Hours 41.0
Root Cause Category Excavation Issue
Root Cause Type Improper Excavation Practice Not Listed Above
Preparer Name T*** M*****
Preparer Title Operations Supervisor
Preparer Email T**********@a**********.com
Preparer Telephone 469-261-2074
Authorizer Name M**** S*****
Authorizer Title V.p. Technical Services
Authorizer Telephone 214-206-2033
Authorizer Email M***********@a**********.com
Narrative On september 18, 2020, excavator was boring telecommunications at 900 forrest park at rosedale and damaged a 6-inch poly main near 928 northton street. Atmos energy technician arrived at 1:25 pm and requested assistance at 1:30 pm. The technician evacuated the business at 928 northton street and, with the help of fire department personnel, a hotel nearby. Forrest park was blocked north of rosedale, and westbound rosedale was blocked off as well. Crews responded, arriving at 1:40 pm and determined that the 12-inch steel main the 6-inch tied into would have to be shut off using short stop fittings. Atmos energy contractor was called in to assist. During the course of repairs, the gas was shut off at 5:20 am on 9/20/2020. Two restaurants were out of service. Service was restored at 11:58 am on 9/21/2020. Per atmos energy's investigation, line locates were completed correctly, and the damaged main was marked accurately. It was determined that this incident will reach the reportable criteria at 4:00 pm on 9/18/20. Initial report #1287736 made to the nrc at 4:53 pm on 9/18/20. The 48-hour update #1287837 was provided at 2:14 pm on 9/20/20.

All rights reserved. Copyright © by ClearPHMSA