GD incident on 2020-08-06 — TX

Operator
Atmos Energy Corporation - Mid-Tex
Cause
Locating Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$19,392
Incident datetime
2020-08-06 11:22
Report number
Location
TX, COLLIN
Narrative
On august 6, 2020, a third-party excavator installing telecommunications fiber-optic cable bored into an end cap on a 12-inch high pressure steel line resulting in mechanical puncture. Crews initially thought a 6-inch poly line in the vicinity was hit and squeezed off that line at 4:15 pm on the same day, august 6, 2020. One residential customer lost service at that time. When the leak did not stop after squeezing off the 6-inch poly line, crews realized the 12-inch steel line had been hit. At approximately 10:35 pm on august 6, 2020, the leak on the 12-inch steel line was isolated using valves. At 8:00 am on august 7, 2020, gas was restored to the customer that lost service when the 6-inch was squeezed off. The gas to the 12-inch steel line was reinstated at 4:04 pm on august 7, 2020. Internal investigation indicated that the line locator failed to properly locate the line resulting in a portion of the line not being marked. Nrc update # 1284052.
Detailed record list
Occurred At
2020-08-06 11:22:00
Year
2020
Report Received Date
2020-09-04 00:00:00
Iyear
2020.0
Report Number
20200084.0
Supplemental Number
34313.0
Report Type
Supplemental Final
Operator Id
Name
Atmos Energy Corporation - Mid-Tex
Operator Street Address
5430 Lbj Freeway Suite 1800
Operator City Name
Dallas
Operator State Abbreviation
TX
Operator Postal Code
75240
Local Datetime
2020-08-06 20:00:00
Location Street Address
W Parker Rd At Ranchero Rd
Location City Name
Plano
Location County Name
Collin
Location State Abbreviation
TX
Location Postal Code
75093
Location Latitude
Location Longitude
-96.80544499
Nrc Rpt Datetime
2020-08-06 20:27:00
Nrc Rpt Num
Commodity Released Type
Natural Gas
Unintentional Release
927.3
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2020-08-06 11:22:00
On Site Datetime
2020-08-06 11:22:00
Federal
No
Location Type
Utility Right-Of-Way / Easement
Incident Area Type
Underground
Incident Area Subtype
Under Pavement
Depth Of Cover
60.0
Crossing
No
Pipe Facility Type
Investor Owned
System Part Involved
Main
Installation Year
1973.0
Pipe Diameter
12.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Unknown
Wt Steel
0.25
Release Type
Mechanical Puncture
Puncture Axial
1.0
Puncture Circum
1.0
Class Location Type
Class 3 Location
Est Cost Oper Paid
7560.0
Est Cost Prop Damage
19392.0
Est Cost Emergency
23108.0
Est Cost Other
0.0
Est Cost Unintentional Release
4582.0
Prpty
54642.0
Commercial Affected
0.0
Industrial Affected
0.0
Residences Affected
1.0
Accident Psig
148.0
Normal Psig
155.0
Mop Psig
175.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Notification From Third Party That Caused The Incident
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Due to the fact that this was a third party excavation damage and the operating pressure at the time of the incident was below the maop.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
Yes
One Call System Ind
Yes
Notify Cga Dirt
No
Public Util Easement Row Ind
Yes
Excavator Type
Contractor
Excavator Equipment
Boring
Work Performed
Telecommunications
One Call Notified Ind
Yes
One Call Ticket Num
2071713728
One Call Center Name
Texas811
Locator Type
Contract Locator
Visible Marks
No
Service Interruption
Yes
Service Interruption Hours
16.0
Root Cause Category
Locating Issue
Root Cause Type
Facility Not Marked Due To Incomplete Marks At Damage Location
Preparer Name
Q**** N****
Preparer Title
Operations Supervisor
Preparer Email
Q**********@a**********.com
Preparer Telephone
469-426-6575
Authorizer Name
M**** S*****
Authorizer Title
V.p. Technical Services
Authorizer Telephone
214-206-2033
Authorizer Email
M***********@a**********.com
Narrative
On august 6, 2020, a third-party excavator installing telecommunications fiber-optic cable bored into an end cap on a 12-inch high pressure steel line resulting in mechanical puncture. Crews initially thought a 6-inch poly line in the vicinity was hit and squeezed off that line at 4:15 pm on the same day, august 6, 2020. One residential customer lost service at that time. When the leak did not stop after squeezing off the 6-inch poly line, crews realized the 12-inch steel line had been hit. At approximately 10:35 pm on august 6, 2020, the leak on the 12-inch steel line was isolated using valves. At 8:00 am on august 7, 2020, gas was restored to the customer that lost service when the 6-inch was squeezed off. The gas to the 12-inch steel line was reinstated at 4:04 pm on august 7, 2020. Internal investigation indicated that the line locator failed to properly locate the line resulting in a portion of the line not being marked. Nrc update # 1284052.
Occurred At 2020-08-06 11:22:00
Year 2020
Report Received Date 2020-09-04 00:00:00
Iyear 2020.0
Report Number 20200084.0
Supplemental Number 34313.0
Report Type Supplemental Final
Operator Id 31348 PHMSA Enforcement
Name Atmos Energy Corporation - Mid-Tex
Operator Street Address 5430 Lbj Freeway Suite 1800
Operator City Name Dallas
Operator State Abbreviation TX
Operator Postal Code 75240
Local Datetime 2020-08-06 20:00:00
Location Street Address W Parker Rd At Ranchero Rd
Location City Name Plano
Location County Name Collin
Location State Abbreviation TX
Location Postal Code 75093
Location Latitude 33.04269314 Google Maps OpenStreetMap
Location Longitude -96.80544499 Google Maps OpenStreetMap
Nrc Rpt Datetime 2020-08-06 20:27:00
Nrc Rpt Num 1283939 NRC Report How to search
Commodity Released Type Natural Gas
Unintentional Release 927.3
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Ignite Ind No
Explode Ind No
Num Pub Evacuated 0.0
Incident Identified Datetime 2020-08-06 11:22:00
On Site Datetime 2020-08-06 11:22:00
Federal No
Location Type Utility Right-Of-Way / Easement
Incident Area Type Underground
Incident Area Subtype Under Pavement
Depth Of Cover 60.0
Crossing No
Pipe Facility Type Investor Owned
System Part Involved Main
Installation Year 1973.0
Pipe Diameter 12.0
Pipe Specification Unknown
Pipe Manufacturer Unknown
Material Involved Steel
Steel Seam Type Other
Steel Seam Type Details Unknown
Wt Steel 0.25
Release Type Mechanical Puncture
Puncture Axial 1.0
Puncture Circum 1.0
Class Location Type Class 3 Location
Est Cost Oper Paid 7560.0
Est Cost Prop Damage 19392.0
Est Cost Emergency 23108.0
Est Cost Other 0.0
Est Cost Unintentional Release 4582.0
Prpty 54642.0
Commercial Affected 0.0
Industrial Affected 0.0
Residences Affected 1.0
Accident Psig 148.0
Normal Psig 155.0
Mop Psig 175.0
Accident Pressure Pressure Did Not Exceed Maop
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Accident Identifier Notification From Third Party That Caused The Incident
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Due to the fact that this was a third party excavation damage and the operating pressure at the time of the incident was below the maop.
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Excavation Damage
Cause Details Excavation Damage By Third Party
Ex Party Type Excavation Damage By Third Party
Prior Notification Ind Yes
One Call System Ind Yes
Notify Cga Dirt No
Public Util Easement Row Ind Yes
Excavator Type Contractor
Excavator Equipment Boring
Work Performed Telecommunications
One Call Notified Ind Yes
One Call Ticket Num 2071713728
One Call Center Name Texas811
Locator Type Contract Locator
Visible Marks No
Service Interruption Yes
Service Interruption Hours 16.0
Root Cause Category Locating Issue
Root Cause Type Facility Not Marked Due To Incomplete Marks At Damage Location
Preparer Name Q**** N****
Preparer Title Operations Supervisor
Preparer Email Q**********@a**********.com
Preparer Telephone 469-426-6575
Authorizer Name M**** S*****
Authorizer Title V.p. Technical Services
Authorizer Telephone 214-206-2033
Authorizer Email M***********@a**********.com
Narrative On august 6, 2020, a third-party excavator installing telecommunications fiber-optic cable bored into an end cap on a 12-inch high pressure steel line resulting in mechanical puncture. Crews initially thought a 6-inch poly line in the vicinity was hit and squeezed off that line at 4:15 pm on the same day, august 6, 2020. One residential customer lost service at that time. When the leak did not stop after squeezing off the 6-inch poly line, crews realized the 12-inch steel line had been hit. At approximately 10:35 pm on august 6, 2020, the leak on the 12-inch steel line was isolated using valves. At 8:00 am on august 7, 2020, gas was restored to the customer that lost service when the 6-inch was squeezed off. The gas to the 12-inch steel line was reinstated at 4:04 pm on august 7, 2020. Internal investigation indicated that the line locator failed to properly locate the line resulting in a portion of the line not being marked. Nrc update # 1284052.