GD incident on 2020-01-24 — OK
Operator
Oklahoma Natural Gas Company, A Division Of One Gas, Inc.
Cause
Notification Issue
Commodity
Natural Gas
Program
GD
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2020-01-24 13:13
Report number
Location
OK, TULSA
Narrative
The city of tulsa damaged ong's 12" dm 100 with a bulldozer grader while performing a silt removal process in mingo creek as required by the army corp of engineers. Ong shut valves at 11th and memorial and 11th and mingo. Ong isolated and capped the pipe on the east and west side of mingo creek. Repairs complete and service restored next day at 10:30am.
Detailed record list
Occurred At
2020-01-24 13:13:00
Year
2020
Report Received Date
2020-02-21 00:00:00
Iyear
2020.0
Report Number
20200026.0
Supplemental Number
33791.0
Report Type
Supplemental Final
Operator Id
14210
Name
Oklahoma Natural Gas Company, A Division Of One Gas, Inc.
Operator Street Address
401 N. Harvey Ave
Operator City Name
Oklahoma City
Operator State Abbreviation
OK
Operator Postal Code
73102
Local Datetime
2020-01-24 13:00:00
Location Street Address
Mingo Creek, 11th And Mingo
Location City Name
Tulsa
Location County Name
Tulsa
Location State Abbreviation
OK
Location Postal Code
74128
Location Latitude
36.14814
Location Longitude
-95.87196
Nrc Rpt Datetime
2020-01-24 19:00:00
Nrc Rpt Num
1269516
Commodity Released Type
Natural Gas
Unintentional Release
85162.0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0.0
Incident Identified Datetime
2020-01-24 13:13:00
On Site Datetime
2020-01-24 13:25:00
Federal
No
Location Type
Utility Right-Of-Way / Easement
Incident Area Type
Underground
Incident Area Subtype
Exposed Due To Excavation
Crossing
Yes
Water Crossing Ind
Yes
Water Type
Uncased
Water Name
Mingo Creek
Water Depth
1
Pipe Facility Type
Privately Owned
System Part Involved
Main
Installation Year
1976.0
Pipe Diameter
12.0
Pipe Specification
Unknown
Pipe Manufacturer
Unknown
Material Involved
Steel
Steel Seam Type
Other
Steel Seam Type Details
Erw
Wt Steel
0.375
Release Type
Mechanical Puncture
Puncture Axial
5.0
Puncture Circum
12.0
Class Location Type
Class 3 Location
Est Cost Oper Paid
0.0
Est Cost Prop Damage
0.0
Est Cost Emergency
118391.0
Est Cost Other
0.0
Est Cost Unintentional Release
269966.0
Prpty
388357.0
Commercial Affected
7.0
Industrial Affected
0.0
Residences Affected
3.0
Accident Psig
120.0
Normal Psig
120.0
Mop Psig
125.0
Accident Pressure
Pressure Did Not Exceed Maop
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Accident Identifier
Notification From Third Party That Caused The Incident
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Excavation Damage
Cause Details
Excavation Damage By Third Party
Ex Party Type
Excavation Damage By Third Party
Prior Notification Ind
No
Notify Cga Dirt
No
Public Row Ind
Yes
Public Subtype
State Highway
Excavator Type
Municipality
Excavator Equipment
Grader/scraper
Work Performed
Grading
One Call Notified Ind
No
Service Interruption
Yes
Service Interruption Hours
8.0
Root Cause Category
Notification Issue
Root Cause Type
No Notification Made To The One-Call Center/811
Preparer Name
S*** S*****
Preparer Title
Sr. Compliance Specialist
Preparer Email
S**********@o*****.com
Preparer Telephone
4052487018
Authorizer Name
M***** B*****
Authorizer Title
Director Of Engineering
Authorizer Telephone
4052390573
Authorizer Email
M************@o*****.com
Narrative
The city of tulsa damaged ong's 12" dm 100 with a bulldozer grader while performing a silt removal process in mingo creek as required by the army corp of engineers. Ong shut valves at 11th and memorial and 11th and mingo. Ong isolated and capped the pipe on the east and west side of mingo creek. Repairs complete and service restored next day at 10:30am.
| Occurred At | 2020-01-24 13:13:00 |
|---|---|
| Year | 2020 |
| Report Received Date | 2020-02-21 00:00:00 |
| Iyear | 2020.0 |
| Report Number | 20200026.0 |
| Supplemental Number | 33791.0 |
| Report Type | Supplemental Final |
| Operator Id | 14210 PHMSA Enforcement |
| Name | Oklahoma Natural Gas Company, A Division Of One Gas, Inc. |
| Operator Street Address | 401 N. Harvey Ave |
| Operator City Name | Oklahoma City |
| Operator State Abbreviation | OK |
| Operator Postal Code | 73102 |
| Local Datetime | 2020-01-24 13:00:00 |
| Location Street Address | Mingo Creek, 11th And Mingo |
| Location City Name | Tulsa |
| Location County Name | Tulsa |
| Location State Abbreviation | OK |
| Location Postal Code | 74128 |
| Location Latitude | 36.14814 Google Maps OpenStreetMap |
| Location Longitude | -95.87196 Google Maps OpenStreetMap |
| Nrc Rpt Datetime | 2020-01-24 19:00:00 |
| Nrc Rpt Num | 1269516 NRC Report How to search |
| Commodity Released Type | Natural Gas |
| Unintentional Release | 85162.0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0.0 |
| Incident Identified Datetime | 2020-01-24 13:13:00 |
| On Site Datetime | 2020-01-24 13:25:00 |
| Federal | No |
| Location Type | Utility Right-Of-Way / Easement |
| Incident Area Type | Underground |
| Incident Area Subtype | Exposed Due To Excavation |
| Crossing | Yes |
| Water Crossing Ind | Yes |
| Water Type | Uncased |
| Water Name | Mingo Creek |
| Water Depth | 1 |
| Pipe Facility Type | Privately Owned |
| System Part Involved | Main |
| Installation Year | 1976.0 |
| Pipe Diameter | 12.0 |
| Pipe Specification | Unknown |
| Pipe Manufacturer | Unknown |
| Material Involved | Steel |
| Steel Seam Type | Other |
| Steel Seam Type Details | Erw |
| Wt Steel | 0.375 |
| Release Type | Mechanical Puncture |
| Puncture Axial | 5.0 |
| Puncture Circum | 12.0 |
| Class Location Type | Class 3 Location |
| Est Cost Oper Paid | 0.0 |
| Est Cost Prop Damage | 0.0 |
| Est Cost Emergency | 118391.0 |
| Est Cost Other | 0.0 |
| Est Cost Unintentional Release | 269966.0 |
| Prpty | 388357.0 |
| Commercial Affected | 7.0 |
| Industrial Affected | 0.0 |
| Residences Affected | 3.0 |
| Accident Psig | 120.0 |
| Normal Psig | 120.0 |
| Mop Psig | 125.0 |
| Accident Pressure | Pressure Did Not Exceed Maop |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Accident Identifier | Notification From Third Party That Caused The Incident |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Excavation Damage |
| Cause Details | Excavation Damage By Third Party |
| Ex Party Type | Excavation Damage By Third Party |
| Prior Notification Ind | No |
| Notify Cga Dirt | No |
| Public Row Ind | Yes |
| Public Subtype | State Highway |
| Excavator Type | Municipality |
| Excavator Equipment | Grader/scraper |
| Work Performed | Grading |
| One Call Notified Ind | No |
| Service Interruption | Yes |
| Service Interruption Hours | 8.0 |
| Root Cause Category | Notification Issue |
| Root Cause Type | No Notification Made To The One-Call Center/811 |
| Preparer Name | S*** S***** |
| Preparer Title | Sr. Compliance Specialist |
| Preparer Email | S**********@o*****.com |
| Preparer Telephone | 4052487018 |
| Authorizer Name | M***** B***** |
| Authorizer Title | Director Of Engineering |
| Authorizer Telephone | 4052390573 |
| Authorizer Email | M************@o*****.com |
| Narrative | The city of tulsa damaged ong's 12" dm 100 with a bulldozer grader while performing a silt removal process in mingo creek as required by the army corp of engineers. Ong shut valves at 11th and memorial and 11th and mingo. Ong isolated and capped the pipe on the east and west side of mingo creek. Repairs complete and service restored next day at 10:30am. |