HL incident on 2019-11-30 — TX

Operator
Dcp Midstream
Cause
Incorrect Operation
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$13,000
Incident datetime
2019-11-30 18:10
Report number
Location
TX
Narrative
At approximately 1810 on november 30, 2019, as technicians were completing a seal change on the outboard seal of pump 310 at brackettville pump station, a fire ignited on the outer edge of the seal cartridge. The incident occurred at startup of the unit. The station fire eye caught the flame and activated the esd loop, shutting the pump station down for approximately 20 minutes. The technicians onsite were able to quickly extinguish the incipient stage fire and there were no injuries sustained. (the station was restarted with the other pump [2 pump units at this station] at 1830 hours). It was determined that this incident was caused by friction of the seal clips rubbing against the locking collar between the seal and the pump shaft along with a potential atmospheric leak of the seal. It was also determined that the seal clips were potentially not completely pulled out and thus could have been partially engaged on the seal sleeve. During the repair following the fire, it was determined that there was not enough clearance between the seal cartridge and the locking collar allowing for the clips to potentially rub against the collar. There was no measurable release and it is estimated at less than one gallon. This incident was reported because of the incipient fire. Redipump llc performed a site report on this seal failure and determined that the mechanical seal p310 was found set to the shaft in an unloaded position. The set clips were not properly engaged in run position. To prevent this from reoccurring, dcp will start with a visual inspection of the clips. They must be fully engaged in the seal sleeve. No gap between clip and gland register face. Sleeve groove must be fully visible with back edge even with gland face. Clips must be squarely moved into the run position dcp will also ensure that existing procedures be modified to add the correct level of detail for seal repair for all of the different types of pumps we have at our stations. Nrc and rrc notified by john pontious for the fire - spill volume did not meet reportable criteria.
Detailed record list
Report Received Date
2019-12-29 00:00:00
Iyear
2019
Report Number
20190398
Supplemental Number
33132
Report Type
Original Final
Operator Id
Name
Dcp Midstream
Operator Street Address
2331 Citywest Blvd. Hq-08-S812-02
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77042
Local Datetime
2019-11-30 18:10:00
Location Latitude
Location Longitude
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
0.1
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2019-11-30 18:10:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2019-11-30 18:10:00
Restart Datetime
2019-11-30 18:30:00
On Site Datetime
2019-11-30 18:10:00
Nrc Rpt Datetime
2019-11-30 19:01:00
Nrc Rpt Num
Ignite Ind
Yes
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Bracketville Pump Station
Segment Name
Bracketville Pump Station P-310
Onshore State Abbreviation
Tx
Onshore Postal Code
78832
Onshore City Name
Bracketville
Onshore County Name
Kinney
Designated Location
Milepost/valve Station
Designated Name
Pump Station
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Other
Item Involved Details
Mechanical Seal And Clips
Installation Year
2018
Material Involved
Material Other Than Carbon Steel
Material Details
Stainless Steel
Release Type
Other
Release Type Details
Friction Fire On The Outer Edge Of The Seal Cartridge Of Pump 310 (Small Fire Occurred That Was Quickly Extinguished)
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
13000
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
13000
Accident Psig
30
Mop Psig
1440
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Dcp field technicians were changing the seal on pump p-310 due to seal failure. Seal was replaced and upon startup there was a small fire in incipient stage. Station fire eye detected flame and activated esd loop shutting the pump station down. Onsite field technician was able to extinguish fire immediately - no injuries. Controller did not contribute to this fire.
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
2
Num Employees Failed
0
Cause
Incorrect Operation
Cause Details
Other Incorrect Operation
Operation Type
Other Incorrect Operation
Operation Details
Field Technicians Did Not Ensure Proper Clearance Between The Cartridge And The Locking Collar While Performing A Seal Change On The Outboard Seal Of Pump 310. Clips Were Not Fully Engaged In The Seal Sleeve And Not Squarely Moved Into The Run Position.
Related Inadequate Proc Ind
Yes
Category Type
Other Maintenance
Operator Qualification Ind
No
Preparer Name
C**** L****
Preparer Title
Sr. Pipeline Compliance Specialist
Preparer Email
C******@d***********.com
Preparer Telephone
361-584-8518
Prepared Date
2019-12-29 00:00:00
Authorizer Name
J*** D P*******
Authorizer Telephone
405-605-3859
Authorizer Title
Manager - Pipeline Compliance
Authorizer Email
J*********@d***********.com
Narrative
At approximately 1810 on november 30, 2019, as technicians were completing a seal change on the outboard seal of pump 310 at brackettville pump station, a fire ignited on the outer edge of the seal cartridge. The incident occurred at startup of the unit. The station fire eye caught the flame and activated the esd loop, shutting the pump station down for approximately 20 minutes. The technicians onsite were able to quickly extinguish the incipient stage fire and there were no injuries sustained. (the station was restarted with the other pump [2 pump units at this station] at 1830 hours). It was determined that this incident was caused by friction of the seal clips rubbing against the locking collar between the seal and the pump shaft along with a potential atmospheric leak of the seal. It was also determined that the seal clips were potentially not completely pulled out and thus could have been partially engaged on the seal sleeve. During the repair following the fire, it was determined that there was not enough clearance between the seal cartridge and the locking collar allowing for the clips to potentially rub against the collar. There was no measurable release and it is estimated at less than one gallon. This incident was reported because of the incipient fire. Redipump llc performed a site report on this seal failure and determined that the mechanical seal p310 was found set to the shaft in an unloaded position. The set clips were not properly engaged in run position. To prevent this from reoccurring, dcp will start with a visual inspection of the clips. They must be fully engaged in the seal sleeve. No gap between clip and gland register face. Sleeve groove must be fully visible with back edge even with gland face. Clips must be squarely moved into the run position dcp will also ensure that existing procedures be modified to add the correct level of detail for seal repair for all of the different types of pumps we have at our stations. Nrc and rrc notified by john pontious for the fire - spill volume did not meet reportable criteria.
Report Received Date 2019-12-29 00:00:00
Iyear 2019
Report Number 20190398
Supplemental Number 33132
Report Type Original Final
Operator Id 31130 PHMSA Enforcement
Name Dcp Midstream
Operator Street Address 2331 Citywest Blvd. Hq-08-S812-02
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77042
Local Datetime 2019-11-30 18:10:00
Location Latitude 29.34572 Google Maps OpenStreetMap
Location Longitude -100.562198 Google Maps OpenStreetMap
Commodity Released Type Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls 0.1
Intentional Release Bbls 0
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Operator Employee
Incident Identified Datetime 2019-11-30 18:10:00
System Part Involved Onshore Pump/meter Station Equipment And Piping
On Off Shore Onshore
Shutdown Due Accident Ind Yes
Shutdown Datetime 2019-11-30 18:10:00
Restart Datetime 2019-11-30 18:30:00
On Site Datetime 2019-11-30 18:10:00
Nrc Rpt Datetime 2019-11-30 19:01:00
Nrc Rpt Num 1265210 NRC Report How to search
Ignite Ind Yes
Explode Ind No
Num Pub Evacuated 0
Pipe Fac Name Bracketville Pump Station
Segment Name Bracketville Pump Station P-310
Onshore State Abbreviation Tx
Onshore Postal Code 78832
Onshore City Name Bracketville
Onshore County Name Kinney
Designated Location Milepost/valve Station
Designated Name Pump Station
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Intrastate
Item Involved Other
Item Involved Details Mechanical Seal And Clips
Installation Year 2018
Material Involved Material Other Than Carbon Steel
Material Details Stainless Steel
Release Type Other
Release Type Details Friction Fire On The Outer Edge Of The Seal Cartridge Of Pump 310 (Small Fire Occurred That Was Quickly Extinguished)
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 0
Est Cost Prop Damage 13000
Est Cost Emergency 0
Est Cost Environmental 0
Est Cost Other 0
Prpty 13000
Accident Psig 30
Mop Psig 1440
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Pipeline Function > 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind Yes
Scada Conf Ind Yes
Cpm In Place Ind Yes
Cpm Operating Ind Yes
Cpm Functional Ind Yes
Cpm Detection Ind No
Cpm Conf Ind No
Investigation Status No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details Dcp field technicians were changing the seal on pump p-310 due to seal failure. Seal was replaced and upon startup there was a small fire in incipient stage. Station fire eye detected flame and activated esd loop shutting the pump station down. Onsite field technician was able to extinguish fire immediately - no injuries. Controller did not contribute to this fire.
Employee Drug Test Ind Yes
Contractor Drug Test Ind No
Num Employees Tested 2
Num Employees Failed 0
Cause Incorrect Operation
Cause Details Other Incorrect Operation
Operation Type Other Incorrect Operation
Operation Details Field Technicians Did Not Ensure Proper Clearance Between The Cartridge And The Locking Collar While Performing A Seal Change On The Outboard Seal Of Pump 310. Clips Were Not Fully Engaged In The Seal Sleeve And Not Squarely Moved Into The Run Position.
Related Inadequate Proc Ind Yes
Category Type Other Maintenance
Operator Qualification Ind No
Preparer Name C**** L****
Preparer Title Sr. Pipeline Compliance Specialist
Preparer Email C******@d***********.com
Preparer Telephone 361-584-8518
Prepared Date 2019-12-29 00:00:00
Authorizer Name J*** D P*******
Authorizer Telephone 405-605-3859
Authorizer Title Manager - Pipeline Compliance
Authorizer Email J*********@d***********.com
Narrative At approximately 1810 on november 30, 2019, as technicians were completing a seal change on the outboard seal of pump 310 at brackettville pump station, a fire ignited on the outer edge of the seal cartridge. The incident occurred at startup of the unit. The station fire eye caught the flame and activated the esd loop, shutting the pump station down for approximately 20 minutes. The technicians onsite were able to quickly extinguish the incipient stage fire and there were no injuries sustained. (the station was restarted with the other pump [2 pump units at this station] at 1830 hours). It was determined that this incident was caused by friction of the seal clips rubbing against the locking collar between the seal and the pump shaft along with a potential atmospheric leak of the seal. It was also determined that the seal clips were potentially not completely pulled out and thus could have been partially engaged on the seal sleeve. During the repair following the fire, it was determined that there was not enough clearance between the seal cartridge and the locking collar allowing for the clips to potentially rub against the collar. There was no measurable release and it is estimated at less than one gallon. This incident was reported because of the incipient fire. Redipump llc performed a site report on this seal failure and determined that the mechanical seal p310 was found set to the shaft in an unloaded position. The set clips were not properly engaged in run position. To prevent this from reoccurring, dcp will start with a visual inspection of the clips. They must be fully engaged in the seal sleeve. No gap between clip and gland register face. Sleeve groove must be fully visible with back edge even with gland face. Clips must be squarely moved into the run position dcp will also ensure that existing procedures be modified to add the correct level of detail for seal repair for all of the different types of pumps we have at our stations. Nrc and rrc notified by john pontious for the fire - spill volume did not meet reportable criteria.