Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2019-11-30 — TX
Operator
Dcp Midstream
Cause
Incorrect Operation
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$13,000
Incident datetime
2019-11-30 18:10
Report number
Location
TX
Narrative
At approximately 1810 on november 30, 2019, as technicians were completing a seal change on the outboard seal of pump 310 at brackettville pump station, a fire ignited on the outer edge of the seal cartridge. The incident occurred at startup of the unit. The station fire eye caught the flame and activated the esd loop, shutting the pump station down for approximately 20 minutes. The technicians onsite were able to quickly extinguish the incipient stage fire and there were no injuries sustained. (the station was restarted with the other pump [2 pump units at this station] at 1830 hours). It was determined that this incident was caused by friction of the seal clips rubbing against the locking collar between the seal and the pump shaft along with a potential atmospheric leak of the seal. It was also determined that the seal clips were potentially not completely pulled out and thus could have been partially engaged on the seal sleeve. During the repair following the fire, it was determined that there was not enough clearance between the seal cartridge and the locking collar allowing for the clips to potentially rub against the collar. There was no measurable release and it is estimated at less than one gallon. This incident was reported because of the incipient fire. Redipump llc performed a site report on this seal failure and determined that the mechanical seal p310 was found set to the shaft in an unloaded position. The set clips were not properly engaged in run position. To prevent this from reoccurring, dcp will start with a visual inspection of the clips. They must be fully engaged in the seal sleeve. No gap between clip and gland register face. Sleeve groove must be fully visible with back edge even with gland face. Clips must be squarely moved into the run position dcp will also ensure that existing procedures be modified to add the correct level of detail for seal repair for all of the different types of pumps we have at our stations. Nrc and rrc notified by john pontious for the fire - spill volume did not meet reportable criteria.
Detailed record list
Report Received Date
2019-12-29 00:00:00
Iyear
2019
Report Number
20190398
Supplemental Number
33132
Report Type
Original Final
Operator Id
31130
Name
Dcp Midstream
Operator Street Address
2331 Citywest Blvd. Hq-08-S812-02
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77042
Local Datetime
2019-11-30 18:10:00
Location Latitude
29.34572
Location Longitude
-100.562198
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid)
Unintentional Release Bbls
0.1
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2019-11-30 18:10:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
Yes
Shutdown Datetime
2019-11-30 18:10:00
Restart Datetime
2019-11-30 18:30:00
On Site Datetime
2019-11-30 18:10:00
Nrc Rpt Datetime
2019-11-30 19:01:00
Nrc Rpt Num
1265210
Ignite Ind
Yes
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Bracketville Pump Station
Segment Name
Bracketville Pump Station P-310
Onshore State Abbreviation
Tx
Onshore Postal Code
78832
Onshore City Name
Bracketville
Onshore County Name
Kinney
Designated Location
Milepost/valve Station
Designated Name
Pump Station
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Other
Item Involved Details
Mechanical Seal And Clips
Installation Year
2018
Material Involved
Material Other Than Carbon Steel
Material Details
Stainless Steel
Release Type
Other
Release Type Details
Friction Fire On The Outer Edge Of The Seal Cartridge Of Pump 310 (Small Fire Occurred That Was Quickly Extinguished)
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
13000
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
13000
Accident Psig
30
Mop Psig
1440
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
Yes
Scada Conf Ind
Yes
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Dcp field technicians were changing the seal on pump p-310 due to seal failure. Seal was replaced and upon startup there was a small fire in incipient stage. Station fire eye detected flame and activated esd loop shutting the pump station down. Onsite field technician was able to extinguish fire immediately - no injuries. Controller did not contribute to this fire.
Employee Drug Test Ind
Yes
Contractor Drug Test Ind
No
Num Employees Tested
2
Num Employees Failed
0
Cause
Incorrect Operation
Cause Details
Other Incorrect Operation
Operation Type
Other Incorrect Operation
Operation Details
Field Technicians Did Not Ensure Proper Clearance Between The Cartridge And The Locking Collar While Performing A Seal Change On The Outboard Seal Of Pump 310. Clips Were Not Fully Engaged In The Seal Sleeve And Not Squarely Moved Into The Run Position.
Related Inadequate Proc Ind
Yes
Category Type
Other Maintenance
Operator Qualification Ind
No
Preparer Name
C**** L****
Preparer Title
Sr. Pipeline Compliance Specialist
Preparer Email
C******@d***********.com
Preparer Telephone
361-584-8518
Prepared Date
2019-12-29 00:00:00
Authorizer Name
J*** D P*******
Authorizer Telephone
405-605-3859
Authorizer Title
Manager - Pipeline Compliance
Authorizer Email
J*********@d***********.com
Narrative
At approximately 1810 on november 30, 2019, as technicians were completing a seal change on the outboard seal of pump 310 at brackettville pump station, a fire ignited on the outer edge of the seal cartridge. The incident occurred at startup of the unit. The station fire eye caught the flame and activated the esd loop, shutting the pump station down for approximately 20 minutes. The technicians onsite were able to quickly extinguish the incipient stage fire and there were no injuries sustained. (the station was restarted with the other pump [2 pump units at this station] at 1830 hours). It was determined that this incident was caused by friction of the seal clips rubbing against the locking collar between the seal and the pump shaft along with a potential atmospheric leak of the seal. It was also determined that the seal clips were potentially not completely pulled out and thus could have been partially engaged on the seal sleeve. During the repair following the fire, it was determined that there was not enough clearance between the seal cartridge and the locking collar allowing for the clips to potentially rub against the collar. There was no measurable release and it is estimated at less than one gallon. This incident was reported because of the incipient fire. Redipump llc performed a site report on this seal failure and determined that the mechanical seal p310 was found set to the shaft in an unloaded position. The set clips were not properly engaged in run position. To prevent this from reoccurring, dcp will start with a visual inspection of the clips. They must be fully engaged in the seal sleeve. No gap between clip and gland register face. Sleeve groove must be fully visible with back edge even with gland face. Clips must be squarely moved into the run position dcp will also ensure that existing procedures be modified to add the correct level of detail for seal repair for all of the different types of pumps we have at our stations. Nrc and rrc notified by john pontious for the fire - spill volume did not meet reportable criteria.
| Report Received Date | 2019-12-29 00:00:00 |
|---|---|
| Iyear | 2019 |
| Report Number | 20190398 |
| Supplemental Number | 33132 |
| Report Type | Original Final |
| Operator Id | 31130 PHMSA Enforcement |
| Name | Dcp Midstream |
| Operator Street Address | 2331 Citywest Blvd. Hq-08-S812-02 |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77042 |
| Local Datetime | 2019-11-30 18:10:00 |
| Location Latitude | 29.34572 Google Maps OpenStreetMap |
| Location Longitude | -100.562198 Google Maps OpenStreetMap |
| Commodity Released Type | Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions |
| Commodity Subtype | Lpg (Liquefied Petroleum Gas) / Ngl (Natural Gas Liquid) |
| Unintentional Release Bbls | 0.1 |
| Intentional Release Bbls | 0 |
| Recovered Bbls | 0 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2019-11-30 18:10:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | Yes |
| Shutdown Datetime | 2019-11-30 18:10:00 |
| Restart Datetime | 2019-11-30 18:30:00 |
| On Site Datetime | 2019-11-30 18:10:00 |
| Nrc Rpt Datetime | 2019-11-30 19:01:00 |
| Nrc Rpt Num | 1265210 NRC Report How to search |
| Ignite Ind | Yes |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Bracketville Pump Station |
| Segment Name | Bracketville Pump Station P-310 |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 78832 |
| Onshore City Name | Bracketville |
| Onshore County Name | Kinney |
| Designated Location | Milepost/valve Station |
| Designated Name | Pump Station |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| Item Involved | Other |
| Item Involved Details | Mechanical Seal And Clips |
| Installation Year | 2018 |
| Material Involved | Material Other Than Carbon Steel |
| Material Details | Stainless Steel |
| Release Type | Other |
| Release Type Details | Friction Fire On The Outer Edge Of The Seal Cartridge Of Pump 310 (Small Fire Occurred That Was Quickly Extinguished) |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 0 |
| Est Cost Prop Damage | 13000 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 13000 |
| Accident Psig | 30 |
| Mop Psig | 1440 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | Yes |
| Scada Conf Ind | Yes |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Dcp field technicians were changing the seal on pump p-310 due to seal failure. Seal was replaced and upon startup there was a small fire in incipient stage. Station fire eye detected flame and activated esd loop shutting the pump station down. Onsite field technician was able to extinguish fire immediately - no injuries. Controller did not contribute to this fire. |
| Employee Drug Test Ind | Yes |
| Contractor Drug Test Ind | No |
| Num Employees Tested | 2 |
| Num Employees Failed | 0 |
| Cause | Incorrect Operation |
| Cause Details | Other Incorrect Operation |
| Operation Type | Other Incorrect Operation |
| Operation Details | Field Technicians Did Not Ensure Proper Clearance Between The Cartridge And The Locking Collar While Performing A Seal Change On The Outboard Seal Of Pump 310. Clips Were Not Fully Engaged In The Seal Sleeve And Not Squarely Moved Into The Run Position. |
| Related Inadequate Proc Ind | Yes |
| Category Type | Other Maintenance |
| Operator Qualification Ind | No |
| Preparer Name | C**** L**** |
| Preparer Title | Sr. Pipeline Compliance Specialist |
| Preparer Email | C******@d***********.com |
| Preparer Telephone | 361-584-8518 |
| Prepared Date | 2019-12-29 00:00:00 |
| Authorizer Name | J*** D P******* |
| Authorizer Telephone | 405-605-3859 |
| Authorizer Title | Manager - Pipeline Compliance |
| Authorizer Email | J*********@d***********.com |
| Narrative | At approximately 1810 on november 30, 2019, as technicians were completing a seal change on the outboard seal of pump 310 at brackettville pump station, a fire ignited on the outer edge of the seal cartridge. The incident occurred at startup of the unit. The station fire eye caught the flame and activated the esd loop, shutting the pump station down for approximately 20 minutes. The technicians onsite were able to quickly extinguish the incipient stage fire and there were no injuries sustained. (the station was restarted with the other pump [2 pump units at this station] at 1830 hours). It was determined that this incident was caused by friction of the seal clips rubbing against the locking collar between the seal and the pump shaft along with a potential atmospheric leak of the seal. It was also determined that the seal clips were potentially not completely pulled out and thus could have been partially engaged on the seal sleeve. During the repair following the fire, it was determined that there was not enough clearance between the seal cartridge and the locking collar allowing for the clips to potentially rub against the collar. There was no measurable release and it is estimated at less than one gallon. This incident was reported because of the incipient fire. Redipump llc performed a site report on this seal failure and determined that the mechanical seal p310 was found set to the shaft in an unloaded position. The set clips were not properly engaged in run position. To prevent this from reoccurring, dcp will start with a visual inspection of the clips. They must be fully engaged in the seal sleeve. No gap between clip and gland register face. Sleeve groove must be fully visible with back edge even with gland face. Clips must be squarely moved into the run position dcp will also ensure that existing procedures be modified to add the correct level of detail for seal repair for all of the different types of pumps we have at our stations. Nrc and rrc notified by john pontious for the fire - spill volume did not meet reportable criteria. |