Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2019-11-20 — TX
Operator
Enterprise Products Operating Llc
Cause
Corrosion Failure
Commodity
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$75,000
Incident datetime
2019-11-20 07:17
Report number
Location
TX
Narrative
At 7:17 on november 20, 2019, enterprise personnel identified a small pin hole leak inside the chime on tank 1024 in el dorado terminal that resulted in a 4 gallon release of gasoline. During the evaluation of the costs of emptying and cleaning the tank in order to perform analysis and repairs, it was determined that the costs would surpass $50,000 on november 21, 2019, making it a reportable nrc leak. The tank will remain out of service until it is inspected and repairs are made. Investigation and metallurgical analysis determined that under-deposit oxygen corrosion was the likely cause. Repairs are underway to return to service. A liner will be installed to prevent recurrence. Initial nrc update was placed on november 21, 2019 at 10:45. 48 hour nrc update #1264577 was placed on november 22, 2019 at 08:28.
Detailed record list
Report Received Date
2019-12-04 00:00:00
Iyear
2019
Report Number
20190364
Supplemental Number
34102
Report Type
Supplemental Final
Operator Id
31618
Name
Enterprise Products Operating Llc
Operator Street Address
1100 Louisiana Street
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77002
Local Datetime
2019-11-20 07:17:00
Location Latitude
33.2619503
Location Longitude
-92.6275734
Commodity Released Type
Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions
Commodity Subtype
Gasoline (Non-Ethanol)
Unintentional Release Bbls
0.1
Recovered Bbls
0.1
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2019-11-20 07:17:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Tank Shut In, Terminal Operations Not Affected
On Site Datetime
2019-11-20 07:17:00
Nrc Rpt Datetime
2019-11-21 10:45:00
Nrc Rpt Num
1264492
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
El Dorado Terminal
Segment Name
Tank 1024
Onshore State Abbreviation
Ar
Onshore Postal Code
71730
Onshore City Name
El Dorado
Onshore County Name
Union
Designated Location
Milepost/valve Station
Designated Name
Mp 246.6
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Tank, Including Attached Appurtenances
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Tank/vessel
Tank Vessel Subtype
Chime
Api Std Out Of Service Year
2020
Api Std No In Service Ind
Yes
Installation Year
1951
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
0
Est Cost Prop Damage
75000
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
75000
Accident Psig
0
Mop Psig
0
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Controller actions did not contribute to the release
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Other Corrosion Ind
Yes
Int Corrosion Type Details
Under-Deposit Oxygen Corrosion
Int Metallurgical Basis Ind
Yes
Int Other Loc Ind
Yes
Corrosion Location Details
Tank Bottom
Corrosion Inhibitors
No
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Preparer Name
D**** B*****
Preparer Title
Pipeline Compliance Engineer
Preparer Email
D*******@e****.com
Preparer Telephone
713-381-5647
Prepared Date
2020-08-04 00:00:00
Authorizer Name
D**** B*****
Authorizer Telephone
713-381-5647
Authorizer Title
Pipeline Compliance Engineer
Authorizer Email
D*******@e****.com
Narrative
At 7:17 on november 20, 2019, enterprise personnel identified a small pin hole leak inside the chime on tank 1024 in el dorado terminal that resulted in a 4 gallon release of gasoline. During the evaluation of the costs of emptying and cleaning the tank in order to perform analysis and repairs, it was determined that the costs would surpass $50,000 on november 21, 2019, making it a reportable nrc leak. The tank will remain out of service until it is inspected and repairs are made. Investigation and metallurgical analysis determined that under-deposit oxygen corrosion was the likely cause. Repairs are underway to return to service. A liner will be installed to prevent recurrence. Initial nrc update was placed on november 21, 2019 at 10:45. 48 hour nrc update #1264577 was placed on november 22, 2019 at 08:28.
| Report Received Date | 2019-12-04 00:00:00 |
|---|---|
| Iyear | 2019 |
| Report Number | 20190364 |
| Supplemental Number | 34102 |
| Report Type | Supplemental Final |
| Operator Id | 31618 PHMSA Enforcement |
| Name | Enterprise Products Operating Llc |
| Operator Street Address | 1100 Louisiana Street |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77002 |
| Local Datetime | 2019-11-20 07:17:00 |
| Location Latitude | 33.2619503 Google Maps OpenStreetMap |
| Location Longitude | -92.6275734 Google Maps OpenStreetMap |
| Commodity Released Type | Refined And/or Petroleum Product (Non-Hvl) Which Is A Liquid At Ambient Conditions |
| Commodity Subtype | Gasoline (Non-Ethanol) |
| Unintentional Release Bbls | 0.1 |
| Recovered Bbls | 0.1 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2019-11-20 07:17:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Tank Shut In, Terminal Operations Not Affected |
| On Site Datetime | 2019-11-20 07:17:00 |
| Nrc Rpt Datetime | 2019-11-21 10:45:00 |
| Nrc Rpt Num | 1264492 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | El Dorado Terminal |
| Segment Name | Tank 1024 |
| Onshore State Abbreviation | Ar |
| Onshore Postal Code | 71730 |
| Onshore City Name | El Dorado |
| Onshore County Name | Union |
| Designated Location | Milepost/valve Station |
| Designated Name | Mp 246.6 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Tank, Including Attached Appurtenances |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Tank/vessel |
| Tank Vessel Subtype | Chime |
| Api Std Out Of Service Year | 2020 |
| Api Std No In Service Ind | Yes |
| Installation Year | 1951 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Pinhole |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 0 |
| Est Cost Prop Damage | 75000 |
| Est Cost Emergency | 0 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 75000 |
| Accident Psig | 0 |
| Mop Psig | 0 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Controller actions did not contribute to the release |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | Internal Corrosion |
| Internal External | Internal Corrosion |
| Int Visual Exam Results | Localized Pitting |
| Int Other Corrosion Ind | Yes |
| Int Corrosion Type Details | Under-Deposit Oxygen Corrosion |
| Int Metallurgical Basis Ind | Yes |
| Int Other Loc Ind | Yes |
| Corrosion Location Details | Tank Bottom |
| Corrosion Inhibitors | No |
| Corrosion Lining | No |
| Cleaning Dewatering | Not Applicable - Not Mainline Pipe |
| Corrosion Coupons | Not Applicable - Not Mainline Pipe |
| Preparer Name | D**** B***** |
| Preparer Title | Pipeline Compliance Engineer |
| Preparer Email | D*******@e****.com |
| Preparer Telephone | 713-381-5647 |
| Prepared Date | 2020-08-04 00:00:00 |
| Authorizer Name | D**** B***** |
| Authorizer Telephone | 713-381-5647 |
| Authorizer Title | Pipeline Compliance Engineer |
| Authorizer Email | D*******@e****.com |
| Narrative | At 7:17 on november 20, 2019, enterprise personnel identified a small pin hole leak inside the chime on tank 1024 in el dorado terminal that resulted in a 4 gallon release of gasoline. During the evaluation of the costs of emptying and cleaning the tank in order to perform analysis and repairs, it was determined that the costs would surpass $50,000 on november 21, 2019, making it a reportable nrc leak. The tank will remain out of service until it is inspected and repairs are made. Investigation and metallurgical analysis determined that under-deposit oxygen corrosion was the likely cause. Repairs are underway to return to service. A liner will be installed to prevent recurrence. Initial nrc update was placed on november 21, 2019 at 10:45. 48 hour nrc update #1264577 was placed on november 22, 2019 at 08:28. |