Incident details
Operator, cause, commodity and consequences with raw source fields.
HL incident on 2019-10-07 — TX
Operator
Nustar Logistics, L.p.
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$15,000
Incident datetime
2019-10-07 16:44
Report number
Location
TX
Narrative
A leak was discovered inside nustar's corpus christi crude terminal by nustar operations personnel, who noticed an odor while working inside the facility. The leak originated at a below-grade 10-inch steel pipe that was designed to assist with the circulation of crude oil within tk 400m-1. The segment containing the leak was immediately isolated by nustar operations personnel using valves at an adjacent manifold on tk 400m-1. A section of pipe containing the leak has been removed and will be sent for analysis to determine the cause of failure. Update - the failure occurred due to through wall corrosion caused by corrosion cells associated with solids deposits on the pipe id. Stagnant conditions allowed solids and water to accumulated on the bottom of the pipe. Chlorine and sulfur were present as corrosion promoters.
Detailed record list
Report Received Date
2019-11-06 00:00:00
Iyear
2019
Report Number
20190334
Supplemental Number
33228
Report Type
Supplemental Final
Operator Id
31454
Name
Nustar Logistics, L.p.
Operator Street Address
8111 Westchester Drive
Operator City Name
Dallas
Operator State Abbreviation
TX
Operator Postal Code
75225
Local Datetime
2019-10-07 16:44:00
Location Latitude
27.81748
Location Longitude
-97.40699
Commodity Released Type
Crude Oil
Unintentional Release Bbls
18.75
Recovered Bbls
18.75
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2019-10-07 16:44:00
System Part Involved
Onshore Terminal/tank Farm Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Booster Pumps Were Shut Down, Terminal Facility Remained In Operation
On Site Datetime
2019-10-07 16:44:00
Nrc Rpt Datetime
2019-10-07 17:41:00
Nrc Rpt Num
1260511
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
45p Oakville Pipeline System
Segment Name
Corpus Christi North Beach Crude Terminal
Onshore State Abbreviation
Tx
Onshore Postal Code
78402
Onshore City Name
Not Within A Municipality
Onshore County Name
Nueces
Designated Location
Milepost/valve Station
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Underground
Incident Area Subtype
Under Soil
Depth Of Cover
60
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Pipe
Pipe Type
Pipe Body
Pipe Diameter
10
Pipe Wall Thickness
0.365
Pipe Smys
52000
Pipe Specification
Api 5l
Pipe Seam Type
Erw - High Frequency
Pipe Manufacturer
Unknown
Pipe Coating Type
Fusion Bonded Epoxy(Fbe)
Installation Year
2012
Manufactured Year
Unknown
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Pinhole
Wildlife Impact Ind
No
Soil Contamination
Yes
Long Term Assessment
No
Remediation Ind
Yes
Soil Remed Ind
Yes
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
1004
Est Cost Prop Damage
15000
Est Cost Emergency
6089
Est Cost Environmental
55308
Est Cost Other
4667
Est Cost Other Details
Metallurgical Lab
Prpty
82068
Accident Psig
114
Mop Psig
285
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Neither controller action nor control room issues contributed to the accident.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Localized Pitting
Int Other Corrosion Ind
Yes
Int Corrosion Type Details
Corrosion Under Deposit
Int Metallurgical Basis Ind
Yes
Int Low Point Pipe Loc Ind
Yes
Corrosion Inhibitors
Yes
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Collected Data Ind
No
Has Hydrtst Conduc Before Ind
No
Direct Asmnt Conducted
No
Non Destructive Exam Ind
No
Preparer Name
R****** P****
Preparer Title
Pipeline Safety Supervisor
Preparer Email
R************@n***********.com
Preparer Telephone
361-249-9417
Preparer Fax
210-918-7007
Prepared Date
2020-01-23 00:00:00
Authorizer Name
W** G***
Authorizer Telephone
361-249-9402
Authorizer Title
Vice President And General Manager
Authorizer Email
W*******@n***********.com
Narrative
A leak was discovered inside nustar's corpus christi crude terminal by nustar operations personnel, who noticed an odor while working inside the facility. The leak originated at a below-grade 10-inch steel pipe that was designed to assist with the circulation of crude oil within tk 400m-1. The segment containing the leak was immediately isolated by nustar operations personnel using valves at an adjacent manifold on tk 400m-1. A section of pipe containing the leak has been removed and will be sent for analysis to determine the cause of failure. Update - the failure occurred due to through wall corrosion caused by corrosion cells associated with solids deposits on the pipe id. Stagnant conditions allowed solids and water to accumulated on the bottom of the pipe. Chlorine and sulfur were present as corrosion promoters.
| Report Received Date | 2019-11-06 00:00:00 |
|---|---|
| Iyear | 2019 |
| Report Number | 20190334 |
| Supplemental Number | 33228 |
| Report Type | Supplemental Final |
| Operator Id | 31454 PHMSA Enforcement |
| Name | Nustar Logistics, L.p. |
| Operator Street Address | 8111 Westchester Drive |
| Operator City Name | Dallas |
| Operator State Abbreviation | TX |
| Operator Postal Code | 75225 |
| Local Datetime | 2019-10-07 16:44:00 |
| Location Latitude | 27.81748 Google Maps OpenStreetMap |
| Location Longitude | -97.40699 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 18.75 |
| Recovered Bbls | 18.75 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2019-10-07 16:44:00 |
| System Part Involved | Onshore Terminal/tank Farm Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Booster Pumps Were Shut Down, Terminal Facility Remained In Operation |
| On Site Datetime | 2019-10-07 16:44:00 |
| Nrc Rpt Datetime | 2019-10-07 17:41:00 |
| Nrc Rpt Num | 1260511 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | 45p Oakville Pipeline System |
| Segment Name | Corpus Christi North Beach Crude Terminal |
| Onshore State Abbreviation | Tx |
| Onshore Postal Code | 78402 |
| Onshore City Name | Not Within A Municipality |
| Onshore County Name | Nueces |
| Designated Location | Milepost/valve Station |
| Designated Name | 0 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Underground |
| Incident Area Subtype | Under Soil |
| Depth Of Cover | 60 |
| Crossing | No |
| Pipe Facility Type | Intrastate |
| Item Involved | Pipe |
| Pipe Type | Pipe Body |
| Pipe Diameter | 10 |
| Pipe Wall Thickness | 0.365 |
| Pipe Smys | 52000 |
| Pipe Specification | Api 5l |
| Pipe Seam Type | Erw - High Frequency |
| Pipe Manufacturer | Unknown |
| Pipe Coating Type | Fusion Bonded Epoxy(Fbe) |
| Installation Year | 2012 |
| Manufactured Year | Unknown |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Pinhole |
| Wildlife Impact Ind | No |
| Soil Contamination | Yes |
| Long Term Assessment | No |
| Remediation Ind | Yes |
| Soil Remed Ind | Yes |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 1004 |
| Est Cost Prop Damage | 15000 |
| Est Cost Emergency | 6089 |
| Est Cost Environmental | 55308 |
| Est Cost Other | 4667 |
| Est Cost Other Details | Metallurgical Lab |
| Prpty | 82068 |
| Accident Psig | 114 |
| Mop Psig | 285 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Neither controller action nor control room issues contributed to the accident. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | Internal Corrosion |
| Internal External | Internal Corrosion |
| Int Visual Exam Results | Localized Pitting |
| Int Other Corrosion Ind | Yes |
| Int Corrosion Type Details | Corrosion Under Deposit |
| Int Metallurgical Basis Ind | Yes |
| Int Low Point Pipe Loc Ind | Yes |
| Corrosion Inhibitors | Yes |
| Corrosion Lining | No |
| Cleaning Dewatering | Not Applicable - Not Mainline Pipe |
| Corrosion Coupons | Not Applicable - Not Mainline Pipe |
| Collected Data Ind | No |
| Has Hydrtst Conduc Before Ind | No |
| Direct Asmnt Conducted | No |
| Non Destructive Exam Ind | No |
| Preparer Name | R****** P**** |
| Preparer Title | Pipeline Safety Supervisor |
| Preparer Email | R************@n***********.com |
| Preparer Telephone | 361-249-9417 |
| Preparer Fax | 210-918-7007 |
| Prepared Date | 2020-01-23 00:00:00 |
| Authorizer Name | W** G*** |
| Authorizer Telephone | 361-249-9402 |
| Authorizer Title | Vice President And General Manager |
| Authorizer Email | W*******@n***********.com |
| Narrative | A leak was discovered inside nustar's corpus christi crude terminal by nustar operations personnel, who noticed an odor while working inside the facility. The leak originated at a below-grade 10-inch steel pipe that was designed to assist with the circulation of crude oil within tk 400m-1. The segment containing the leak was immediately isolated by nustar operations personnel using valves at an adjacent manifold on tk 400m-1. A section of pipe containing the leak has been removed and will be sent for analysis to determine the cause of failure. Update - the failure occurred due to through wall corrosion caused by corrosion cells associated with solids deposits on the pipe id. Stagnant conditions allowed solids and water to accumulated on the bottom of the pipe. Chlorine and sulfur were present as corrosion promoters. |