HL incident on 2019-10-22 — TX

Operator
Boardwalk Louisiana Midstream, Llc
Cause
Equipment Failure
Commodity
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Program
HL
Damage and Injuries
0 fatalities 0 injuries
Property damage (nominal)
$60
Incident datetime
2019-10-22 18:30
Report number
Location
TX
Narrative
During flare outage, contractor was grinding on pipe when, due to a valve stem emission leak, sparks flew and ignited a small candle-like flame on the valve stem leak. The candle-like fire was immediately extinguished. The valve was de-pressured and fire blankets were used to prevent this from recurring. Block valves were isolated, piping upstream of the valve stem leak was flared to zero psig and a slip blind was installed to double block the associated segment. The answer to part a question 9 is shown as 0.1 barrels because this is the lowest value the system would allow; the product loss was, actually, so minimal it was not measurable. 1-10-2020 updated following further investigation. The response to part e, question 1 is 300 psig; however, this is only an estimate. The exact pressure is unknown. Also updated response to part e, question 5e.
Detailed record list
Report Received Date
2019-11-06 00:00:00
Iyear
2019
Report Number
20190333
Supplemental Number
33175
Report Type
Supplemental Final
Operator Id
Name
Boardwalk Louisiana Midstream, Llc
Operator Street Address
9 Greenway Plaza
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77046
Local Datetime
2019-10-22 18:30:00
Location Latitude
Location Longitude
Commodity Released Type
Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype
Other Hvl
Commodity Details
Ethylene
Unintentional Release Bbls
0.1
Intentional Release Bbls
0
Recovered Bbls
0
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Contractor Working For The Operator
Incident Identified Datetime
2019-10-22 18:30:00
System Part Involved
Onshore Pipeline, Including Valve Sites
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Minor Flame That Was Quickly Extinguished
On Site Datetime
2019-10-22 18:30:00
Nrc Rpt Datetime
2019-10-22 19:21:00
Nrc Rpt Num
Ignite Ind
Yes
Explode Ind
No
Upstream Valve Type Ind
Manual
Downstream Valve Type Ind
Manual
Num Pub Evacuated
0
Pipe Fac Name
Choctaw Terminal
Segment Name
Facility Piping
Onshore State Abbreviation
La
Onshore Postal Code
70764
Onshore City Name
Plaquemine
Onshore County Name
Iberville
Designated Location
Milepost/valve Station
Designated Name
1+49
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Intrastate
Item Involved
Valve
Valve Type
Auxiliary Or Other Valve
Installation Year
Unknown
Material Involved
Carbon Steel
Release Type
Other
Release Type Details
Emission Leak On Valve Stem While Grinding Pipe Prior To Welding Resulted In A Small, Candle-Like Flame On The Valve Stem Leak.
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
1
Est Cost Prop Damage
60
Est Cost Emergency
0
Est Cost Environmental
0
Est Cost Other
0
Prpty
61
Accident Psig
300
Mop Psig
1440
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Length Segment Isolated
100
Internal Inspection Ind
No
Diameter Change Ind
Yes
Operation Complications Ind
Yes
Low Op Pressure Ind
Yes
Low Flow Ind
Yes
Incompat Commod Ind
Yes
Other Complications Ind
Yes
Inspect Comp Details
Manifold Header System
Pipeline Function
< 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind
Yes
Invest No Controller Ind
Yes
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Malfunction Of Control/relief Equipment
Eq Failure Type
Malfunction Of Control/relief Equipment
Block Valve Ind
Yes
Eq Additional Other Ind
Yes
Eq Additional Other Details
Packing Leak
Preparer Name
S****** M********
Preparer Title
Pa Oq And Event Program Leader
Preparer Email
S****************@b**********.com
Preparer Telephone
270-688-6357
Prepared Date
2020-01-10 00:00:00
Authorizer Name
T*** B****
Authorizer Telephone
270-688-6497
Authorizer Title
Manager Compliance Services
Authorizer Email
T*********@b**********.com
Narrative
During flare outage, contractor was grinding on pipe when, due to a valve stem emission leak, sparks flew and ignited a small candle-like flame on the valve stem leak. The candle-like fire was immediately extinguished. The valve was de-pressured and fire blankets were used to prevent this from recurring. Block valves were isolated, piping upstream of the valve stem leak was flared to zero psig and a slip blind was installed to double block the associated segment. The answer to part a question 9 is shown as 0.1 barrels because this is the lowest value the system would allow; the product loss was, actually, so minimal it was not measurable. 1-10-2020 updated following further investigation. The response to part e, question 1 is 300 psig; however, this is only an estimate. The exact pressure is unknown. Also updated response to part e, question 5e.
Report Received Date 2019-11-06 00:00:00
Iyear 2019
Report Number 20190333
Supplemental Number 33175
Report Type Supplemental Final
Operator Id 39138 PHMSA Enforcement
Name Boardwalk Louisiana Midstream, Llc
Operator Street Address 9 Greenway Plaza
Operator City Name Houston
Operator State Abbreviation TX
Operator Postal Code 77046
Local Datetime 2019-10-22 18:30:00
Location Latitude 30.318165 Google Maps OpenStreetMap
Location Longitude -91.309541 Google Maps OpenStreetMap
Commodity Released Type Hvl Or Other Flammable Or Toxic Fluid Which Is A Gas At Ambient Conditions
Commodity Subtype Other Hvl
Commodity Details Ethylene
Unintentional Release Bbls 0.1
Intentional Release Bbls 0
Recovered Bbls 0
Fatality Ind No
Fatal 0
Injury Ind No
Injure 0
Accident Identifier Local Operating Personnel, Including Contractors
Operator Type Contractor Working For The Operator
Incident Identified Datetime 2019-10-22 18:30:00
System Part Involved Onshore Pipeline, Including Valve Sites
On Off Shore Onshore
Shutdown Due Accident Ind No
Shutdown Explain Minor Flame That Was Quickly Extinguished
On Site Datetime 2019-10-22 18:30:00
Nrc Rpt Datetime 2019-10-22 19:21:00
Nrc Rpt Num 1261903 NRC Report How to search
Ignite Ind Yes
Explode Ind No
Upstream Valve Type Ind Manual
Downstream Valve Type Ind Manual
Num Pub Evacuated 0
Pipe Fac Name Choctaw Terminal
Segment Name Facility Piping
Onshore State Abbreviation La
Onshore Postal Code 70764
Onshore City Name Plaquemine
Onshore County Name Iberville
Designated Location Milepost/valve Station
Designated Name 1+49
Federal No
Location Type Totally Contained On Operator-Controlled Property
Incident Area Type Aboveground
Incident Area Subtype Typical Aboveground Facility Piping Or Appurtenance
Crossing No
Pipe Facility Type Intrastate
Item Involved Valve
Valve Type Auxiliary Or Other Valve
Installation Year Unknown
Material Involved Carbon Steel
Release Type Other
Release Type Details Emission Leak On Valve Stem While Grinding Pipe Prior To Welding Resulted In A Small, Candle-Like Flame On The Valve Stem Leak.
Wildlife Impact Ind No
Soil Contamination No
Long Term Assessment No
Remediation Ind No
Water Contam Ind No
Could Be Hca No
Commodity Reached Hca No
Est Cost Oper Paid 0
Est Cost Gas Released 1
Est Cost Prop Damage 60
Est Cost Emergency 0
Est Cost Environmental 0
Est Cost Other 0
Prpty 61
Accident Psig 300
Mop Psig 1440
Accident Pressure Pressure Did Not Exceed Mop
Pressure Restriction Ind No
Length Segment Isolated 100
Internal Inspection Ind No
Diameter Change Ind Yes
Operation Complications Ind Yes
Low Op Pressure Ind Yes
Low Flow Ind Yes
Incompat Commod Ind Yes
Other Complications Ind Yes
Inspect Comp Details Manifold Header System
Pipeline Function < 20% Smys Regulated Transmission
Scada In Place Ind Yes
Scada Operating Ind Yes
Scada Functional Ind Yes
Scada Detection Ind No
Scada Conf Ind No
Cpm In Place Ind No
Investigation Status Yes, specify investigation result(s): (select all that apply)
Invest No Control Room Ind Yes
Invest No Controller Ind Yes
Employee Drug Test Ind No
Contractor Drug Test Ind No
Cause Equipment Failure
Cause Details Malfunction Of Control/relief Equipment
Eq Failure Type Malfunction Of Control/relief Equipment
Block Valve Ind Yes
Eq Additional Other Ind Yes
Eq Additional Other Details Packing Leak
Preparer Name S****** M********
Preparer Title Pa Oq And Event Program Leader
Preparer Email S****************@b**********.com
Preparer Telephone 270-688-6357
Prepared Date 2020-01-10 00:00:00
Authorizer Name T*** B****
Authorizer Telephone 270-688-6497
Authorizer Title Manager Compliance Services
Authorizer Email T*********@b**********.com
Narrative During flare outage, contractor was grinding on pipe when, due to a valve stem emission leak, sparks flew and ignited a small candle-like flame on the valve stem leak. The candle-like fire was immediately extinguished. The valve was de-pressured and fire blankets were used to prevent this from recurring. Block valves were isolated, piping upstream of the valve stem leak was flared to zero psig and a slip blind was installed to double block the associated segment. The answer to part a question 9 is shown as 0.1 barrels because this is the lowest value the system would allow; the product loss was, actually, so minimal it was not measurable. 1-10-2020 updated following further investigation. The response to part e, question 1 is 300 psig; however, this is only an estimate. The exact pressure is unknown. Also updated response to part e, question 5e.