HL incident on 2019-06-14 — TX
Operator
Enbridge Energy, Limited Partnership
Cause
Corrosion Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$123,674
Incident datetime
2019-06-14 07:15
Report number
Location
TX
Narrative
On june 14, 2019 at 7:15 am cdt, an electrical technician completing morning rounds discovered approximately 3 gallons of crude oil near the line 65 unit 3 pump at the donaldson station. The unit 3 pump was not running at the time the release was discovered. The edmonton control center was contacted and the pump was isolated and locked out. Additional operations personnel were dispatched to investigate the source of the release and begin cleanup of the oil from the concrete pump room floor. Small diameter piping that was welded to the underside of the pump was found to be the source of the release. Once the repair plan was finalized on june 18, 2019 it was determined that the costs would exceed the nrc reporting threshold and an external notification to the nrc was made at 9:52 am cdt (#1249253). A 48-hour update was made to the nrc on june 20. 2019 at 8:10 am cdt (#1249485). In order to repair the small diameter piping and determine the cause of the failure, the entire pump was removed from the station and sent to sulzer for repair, cleaning, and analysis. Once the pump was disassembled and inspected, it was discovered that the cause of the release was due to internal corrosion/erosion within the pump case and balance line. When the cleaning of the pump is completed, the pump will be sent back to the donaldson station for installation. It is anticipated that the pump will be operational by the end of 2019.
Detailed record list
Report Received Date
2019-07-12 00:00:00
Iyear
2019
Report Number
20190223
Supplemental Number
32880
Report Type
Supplemental Final
Operator Id
11169
Name
Enbridge Energy, Limited Partnership
Operator Street Address
915 N Eldridge Parkway, Suite 1100
Operator City Name
Houston
Operator State Abbreviation
TX
Operator Postal Code
77079
Local Datetime
2019-06-14 07:15:00
Location Latitude
48.573929
Location Longitude
-96.935187
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.1
Recovered Bbls
0.1
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Local Operating Personnel, Including Contractors
Operator Type
Operator Employee
Incident Identified Datetime
2019-06-14 07:15:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Unit 3 Pump Was Not Running At The Time Of The Release And Was Locked Out
On Site Datetime
2019-06-14 07:15:00
Nrc Rpt Datetime
2019-06-18 09:52:00
Nrc Rpt Num
1249253
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Donaldson Station
Segment Name
Line 65 Unit 3
Onshore State Abbreviation
Mn
Onshore Postal Code
56720
Onshore City Name
Donaldson
Onshore County Name
Kittson
Designated Location
Milepost/valve Station
Designated Name
814
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Inside A Building
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Pump
Installation Year
1997
Material Involved
Carbon Steel
Release Type
Leak
Leak Type
Crack
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
No
Commodity Reached Hca
No
Est Cost Oper Paid
0
Est Cost Gas Released
4
Est Cost Prop Damage
123674
Est Cost Emergency
124
Est Cost Environmental
0
Est Cost Other
0
Prpty
123802
Accident Psig
657
Mop Psig
1430
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
Yes
Cpm Operating Ind
Yes
Cpm Functional Ind
Yes
Cpm Detection Ind
No
Cpm Conf Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
Lack of control center involvement. Field identified release.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Corrosion Failure
Cause Details
Internal Corrosion
Internal External
Internal Corrosion
Int Visual Exam Results
Other
Int Visual Exam Details
Erosion By Fluid Wash
Int Erosion Ind
Yes
Int Field Exam Basis Ind
Yes
Int Metallurgical Basis Ind
Yes
Int Elbow Loc Ind
Yes
Corrosion Inhibitors
No
Corrosion Lining
No
Cleaning Dewatering
Not Applicable - Not Mainline Pipe
Corrosion Coupons
Not Applicable - Not Mainline Pipe
Preparer Name
S**** S****
Preparer Title
Sr Compliance Analyst
Preparer Email
S**********@e*******.com
Preparer Telephone
715-395-3620
Prepared Date
2019-10-30 00:00:00
Authorizer Name
R** C*******
Authorizer Telephone
715-395-3619
Authorizer Title
Supervisor Us Pipeline Compliance
Authorizer Email
R***********@e*******.com
Narrative
On june 14, 2019 at 7:15 am cdt, an electrical technician completing morning rounds discovered approximately 3 gallons of crude oil near the line 65 unit 3 pump at the donaldson station. The unit 3 pump was not running at the time the release was discovered. The edmonton control center was contacted and the pump was isolated and locked out. Additional operations personnel were dispatched to investigate the source of the release and begin cleanup of the oil from the concrete pump room floor. Small diameter piping that was welded to the underside of the pump was found to be the source of the release. Once the repair plan was finalized on june 18, 2019 it was determined that the costs would exceed the nrc reporting threshold and an external notification to the nrc was made at 9:52 am cdt (#1249253). A 48-hour update was made to the nrc on june 20. 2019 at 8:10 am cdt (#1249485). In order to repair the small diameter piping and determine the cause of the failure, the entire pump was removed from the station and sent to sulzer for repair, cleaning, and analysis. Once the pump was disassembled and inspected, it was discovered that the cause of the release was due to internal corrosion/erosion within the pump case and balance line. When the cleaning of the pump is completed, the pump will be sent back to the donaldson station for installation. It is anticipated that the pump will be operational by the end of 2019.
| Report Received Date | 2019-07-12 00:00:00 |
|---|---|
| Iyear | 2019 |
| Report Number | 20190223 |
| Supplemental Number | 32880 |
| Report Type | Supplemental Final |
| Operator Id | 11169 PHMSA Enforcement |
| Name | Enbridge Energy, Limited Partnership |
| Operator Street Address | 915 N Eldridge Parkway, Suite 1100 |
| Operator City Name | Houston |
| Operator State Abbreviation | TX |
| Operator Postal Code | 77079 |
| Local Datetime | 2019-06-14 07:15:00 |
| Location Latitude | 48.573929 Google Maps OpenStreetMap |
| Location Longitude | -96.935187 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 0.1 |
| Recovered Bbls | 0.1 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Local Operating Personnel, Including Contractors |
| Operator Type | Operator Employee |
| Incident Identified Datetime | 2019-06-14 07:15:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Unit 3 Pump Was Not Running At The Time Of The Release And Was Locked Out |
| On Site Datetime | 2019-06-14 07:15:00 |
| Nrc Rpt Datetime | 2019-06-18 09:52:00 |
| Nrc Rpt Num | 1249253 NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Donaldson Station |
| Segment Name | Line 65 Unit 3 |
| Onshore State Abbreviation | Mn |
| Onshore Postal Code | 56720 |
| Onshore City Name | Donaldson |
| Onshore County Name | Kittson |
| Designated Location | Milepost/valve Station |
| Designated Name | 814 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Inside A Building |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Pump |
| Installation Year | 1997 |
| Material Involved | Carbon Steel |
| Release Type | Leak |
| Leak Type | Crack |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | No |
| Commodity Reached Hca | No |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 4 |
| Est Cost Prop Damage | 123674 |
| Est Cost Emergency | 124 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 123802 |
| Accident Psig | 657 |
| Mop Psig | 1430 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | Yes |
| Cpm Operating Ind | Yes |
| Cpm Functional Ind | Yes |
| Cpm Detection Ind | No |
| Cpm Conf Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | Lack of control center involvement. Field identified release. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Corrosion Failure |
| Cause Details | Internal Corrosion |
| Internal External | Internal Corrosion |
| Int Visual Exam Results | Other |
| Int Visual Exam Details | Erosion By Fluid Wash |
| Int Erosion Ind | Yes |
| Int Field Exam Basis Ind | Yes |
| Int Metallurgical Basis Ind | Yes |
| Int Elbow Loc Ind | Yes |
| Corrosion Inhibitors | No |
| Corrosion Lining | No |
| Cleaning Dewatering | Not Applicable - Not Mainline Pipe |
| Corrosion Coupons | Not Applicable - Not Mainline Pipe |
| Preparer Name | S**** S**** |
| Preparer Title | Sr Compliance Analyst |
| Preparer Email | S**********@e*******.com |
| Preparer Telephone | 715-395-3620 |
| Prepared Date | 2019-10-30 00:00:00 |
| Authorizer Name | R** C******* |
| Authorizer Telephone | 715-395-3619 |
| Authorizer Title | Supervisor Us Pipeline Compliance |
| Authorizer Email | R***********@e*******.com |
| Narrative | On june 14, 2019 at 7:15 am cdt, an electrical technician completing morning rounds discovered approximately 3 gallons of crude oil near the line 65 unit 3 pump at the donaldson station. The unit 3 pump was not running at the time the release was discovered. The edmonton control center was contacted and the pump was isolated and locked out. Additional operations personnel were dispatched to investigate the source of the release and begin cleanup of the oil from the concrete pump room floor. Small diameter piping that was welded to the underside of the pump was found to be the source of the release. Once the repair plan was finalized on june 18, 2019 it was determined that the costs would exceed the nrc reporting threshold and an external notification to the nrc was made at 9:52 am cdt (#1249253). A 48-hour update was made to the nrc on june 20. 2019 at 8:10 am cdt (#1249485). In order to repair the small diameter piping and determine the cause of the failure, the entire pump was removed from the station and sent to sulzer for repair, cleaning, and analysis. Once the pump was disassembled and inspected, it was discovered that the cause of the release was due to internal corrosion/erosion within the pump case and balance line. When the cleaning of the pump is completed, the pump will be sent back to the donaldson station for installation. It is anticipated that the pump will be operational by the end of 2019. |