HL incident on 2019-06-09 — IN
Operator
Countrymark Refining And Logistics, Llc
Cause
Equipment Failure
Commodity
Crude Oil
Program
HL
Damage and Injuries
0 fatalities
0 injuries
Property damage (nominal)
$0
Incident datetime
2019-06-09 06:00
Report number
Location
IN
Narrative
At 6:00 am cst countrymark gauger was called by an employee of the terminal about a leak around our pump area. The gauger called the pipeline control room and spoke with the pipeline controller at 6:05 am to notify him of the situation. Pipeline controller dispatched the gauger to the site to get a handle on what was going on. Pipeline controller then called the pipeline operations supervisor to notify him at 6:15am. Operations supervisor then called the gauger to find out what the cause was and what the site might need. The gauger had found a braided hose to be leaking off the pump 1 mainline discharge at the hose crimped end. Operations supervisor then called a mechanical tech and the pipeline maintenance supervisor to send crews to clean up. Operations supervisor and mechanical tech arrived at 9:30 am. Pumps were already down as the batch was completed the prior day. Operations supervisor called the pipeline control room to notify them that equipment would be de-energized and loto placed to isolate the leaking hose and drain. Pipeline maintenance personnel arrived to assist in cleanup at approx. 9:45am. The line was drained and leaking hose removed. A plug installed and cleanup of the oil on pumps and ground. An estimated .5 bbl was released. The cause of the failure was determined to be fatigue fracture in the core tube caused by excessive vibration. The hose manufacturer's evaluation report confirmed this determination.
Detailed record list
Report Received Date
2019-07-05 00:00:00
Iyear
2019
Report Number
20190215
Supplemental Number
32472
Report Type
Supplemental Final
Operator Id
26049
Name
Countrymark Refining And Logistics, Llc
Operator Street Address
225 S.e. St. , Suite 44
Operator City Name
Indianapolis
Operator State Abbreviation
IN
Operator Postal Code
46202
Local Datetime
2019-06-08 22:00:00
Location Latitude
38.790784
Location Longitude
-89.069841
Commodity Released Type
Crude Oil
Unintentional Release Bbls
0.5
Recovered Bbls
0.5
Fatality Ind
No
Fatal
0
Injury Ind
No
Injure
0
Accident Identifier
Other
Accident Details
Employee Of The Pipeline Terminal Notified Countrymark Of The Incident
Incident Identified Datetime
2019-06-09 06:00:00
System Part Involved
Onshore Pump/meter Station Equipment And Piping
On Off Shore
Onshore
Shutdown Due Accident Ind
No
Shutdown Explain
Pipeline Was Already Shutdown When The Incident Occurred
On Site Datetime
2019-06-09 09:30:00
Nrc Rpt Num
Nrc Notification Not Required
Ignite Ind
No
Explode Ind
No
Num Pub Evacuated
0
Pipe Fac Name
Patoka To Mt Vernon System
Segment Name
Patoka Pump Station
Onshore State Abbreviation
Il
Onshore Postal Code
62892
Onshore City Name
Not Within A Municipality
Onshore County Name
Marion
Designated Location
Milepost/valve Station
Designated Name
0
Federal
No
Location Type
Totally Contained On Operator-Controlled Property
Incident Area Type
Aboveground
Incident Area Subtype
Typical Aboveground Facility Piping Or Appurtenance
Crossing
No
Pipe Facility Type
Interstate
Item Involved
Auxiliary Piping (E.g. Drain Lines)
Installation Year
2019
Material Involved
Material Other Than Carbon Steel
Material Details
Stainless Steel
Release Type
Leak
Leak Type
Connection Failure
Wildlife Impact Ind
No
Soil Contamination
No
Long Term Assessment
No
Remediation Ind
No
Water Contam Ind
No
Could Be Hca
Yes
Commodity Reached Hca
Yes
Usa Drinking Ind
Yes
Usa Drinking Yes No
Yes
Est Cost Oper Paid
0
Est Cost Gas Released
30
Est Cost Prop Damage
0
Est Cost Emergency
3797
Est Cost Environmental
0
Est Cost Other
0
Prpty
3827
Accident Psig
7
Mop Psig
1440
Accident Pressure
Pressure Did Not Exceed Mop
Pressure Restriction Ind
No
Pipeline Function
> 20% Smys Regulated Transmission
Scada In Place Ind
Yes
Scada Operating Ind
Yes
Scada Functional Ind
Yes
Scada Detection Ind
No
Scada Conf Ind
No
Cpm In Place Ind
No
Investigation Status
No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate)
Investigation Status Details
The small amount would not be detectable by the current scada system. This was a slow leak that occurred while the pumps were shutdown.
Employee Drug Test Ind
No
Contractor Drug Test Ind
No
Cause
Equipment Failure
Cause Details
Failure Of Equipment Body (Except Pump), Tank Plate, Or Other Material
Eq Failure Type
Failure Of Equipment Body (Except Pump), Tank Plate, Or Other Material
Additional Vibration Ind
Yes
Preparer Name
B**** C*****
Preparer Title
Manager Of Pipeline Integrity
Preparer Email
B***********@c**********.com
Preparer Telephone
8128388555
Prepared Date
2019-07-26 00:00:00
Authorizer Name
A** T*****
Authorizer Telephone
8128388152
Authorizer Title
Manager Crude Gathering And Transportation
Authorizer Email
A*********@c**********.com
Narrative
At 6:00 am cst countrymark gauger was called by an employee of the terminal about a leak around our pump area. The gauger called the pipeline control room and spoke with the pipeline controller at 6:05 am to notify him of the situation. Pipeline controller dispatched the gauger to the site to get a handle on what was going on. Pipeline controller then called the pipeline operations supervisor to notify him at 6:15am. Operations supervisor then called the gauger to find out what the cause was and what the site might need. The gauger had found a braided hose to be leaking off the pump 1 mainline discharge at the hose crimped end. Operations supervisor then called a mechanical tech and the pipeline maintenance supervisor to send crews to clean up. Operations supervisor and mechanical tech arrived at 9:30 am. Pumps were already down as the batch was completed the prior day. Operations supervisor called the pipeline control room to notify them that equipment would be de-energized and loto placed to isolate the leaking hose and drain. Pipeline maintenance personnel arrived to assist in cleanup at approx. 9:45am. The line was drained and leaking hose removed. A plug installed and cleanup of the oil on pumps and ground. An estimated .5 bbl was released. The cause of the failure was determined to be fatigue fracture in the core tube caused by excessive vibration. The hose manufacturer's evaluation report confirmed this determination.
| Report Received Date | 2019-07-05 00:00:00 |
|---|---|
| Iyear | 2019 |
| Report Number | 20190215 |
| Supplemental Number | 32472 |
| Report Type | Supplemental Final |
| Operator Id | 26049 PHMSA Enforcement |
| Name | Countrymark Refining And Logistics, Llc |
| Operator Street Address | 225 S.e. St. , Suite 44 |
| Operator City Name | Indianapolis |
| Operator State Abbreviation | IN |
| Operator Postal Code | 46202 |
| Local Datetime | 2019-06-08 22:00:00 |
| Location Latitude | 38.790784 Google Maps OpenStreetMap |
| Location Longitude | -89.069841 Google Maps OpenStreetMap |
| Commodity Released Type | Crude Oil |
| Unintentional Release Bbls | 0.5 |
| Recovered Bbls | 0.5 |
| Fatality Ind | No |
| Fatal | 0 |
| Injury Ind | No |
| Injure | 0 |
| Accident Identifier | Other |
| Accident Details | Employee Of The Pipeline Terminal Notified Countrymark Of The Incident |
| Incident Identified Datetime | 2019-06-09 06:00:00 |
| System Part Involved | Onshore Pump/meter Station Equipment And Piping |
| On Off Shore | Onshore |
| Shutdown Due Accident Ind | No |
| Shutdown Explain | Pipeline Was Already Shutdown When The Incident Occurred |
| On Site Datetime | 2019-06-09 09:30:00 |
| Nrc Rpt Num | Nrc Notification Not Required NRC Report How to search |
| Ignite Ind | No |
| Explode Ind | No |
| Num Pub Evacuated | 0 |
| Pipe Fac Name | Patoka To Mt Vernon System |
| Segment Name | Patoka Pump Station |
| Onshore State Abbreviation | Il |
| Onshore Postal Code | 62892 |
| Onshore City Name | Not Within A Municipality |
| Onshore County Name | Marion |
| Designated Location | Milepost/valve Station |
| Designated Name | 0 |
| Federal | No |
| Location Type | Totally Contained On Operator-Controlled Property |
| Incident Area Type | Aboveground |
| Incident Area Subtype | Typical Aboveground Facility Piping Or Appurtenance |
| Crossing | No |
| Pipe Facility Type | Interstate |
| Item Involved | Auxiliary Piping (E.g. Drain Lines) |
| Installation Year | 2019 |
| Material Involved | Material Other Than Carbon Steel |
| Material Details | Stainless Steel |
| Release Type | Leak |
| Leak Type | Connection Failure |
| Wildlife Impact Ind | No |
| Soil Contamination | No |
| Long Term Assessment | No |
| Remediation Ind | No |
| Water Contam Ind | No |
| Could Be Hca | Yes |
| Commodity Reached Hca | Yes |
| Usa Drinking Ind | Yes |
| Usa Drinking Yes No | Yes |
| Est Cost Oper Paid | 0 |
| Est Cost Gas Released | 30 |
| Est Cost Prop Damage | 0 |
| Est Cost Emergency | 3797 |
| Est Cost Environmental | 0 |
| Est Cost Other | 0 |
| Prpty | 3827 |
| Accident Psig | 7 |
| Mop Psig | 1440 |
| Accident Pressure | Pressure Did Not Exceed Mop |
| Pressure Restriction Ind | No |
| Pipeline Function | > 20% Smys Regulated Transmission |
| Scada In Place Ind | Yes |
| Scada Operating Ind | Yes |
| Scada Functional Ind | Yes |
| Scada Detection Ind | No |
| Scada Conf Ind | No |
| Cpm In Place Ind | No |
| Investigation Status | No, the operator did not find that an investigation of the controller(s) actions or control room issues was necessary due to: (provide an explanation for why the operator did not investigate) |
| Investigation Status Details | The small amount would not be detectable by the current scada system. This was a slow leak that occurred while the pumps were shutdown. |
| Employee Drug Test Ind | No |
| Contractor Drug Test Ind | No |
| Cause | Equipment Failure |
| Cause Details | Failure Of Equipment Body (Except Pump), Tank Plate, Or Other Material |
| Eq Failure Type | Failure Of Equipment Body (Except Pump), Tank Plate, Or Other Material |
| Additional Vibration Ind | Yes |
| Preparer Name | B**** C***** |
| Preparer Title | Manager Of Pipeline Integrity |
| Preparer Email | B***********@c**********.com |
| Preparer Telephone | 8128388555 |
| Prepared Date | 2019-07-26 00:00:00 |
| Authorizer Name | A** T***** |
| Authorizer Telephone | 8128388152 |
| Authorizer Title | Manager Crude Gathering And Transportation |
| Authorizer Email | A*********@c**********.com |
| Narrative | At 6:00 am cst countrymark gauger was called by an employee of the terminal about a leak around our pump area. The gauger called the pipeline control room and spoke with the pipeline controller at 6:05 am to notify him of the situation. Pipeline controller dispatched the gauger to the site to get a handle on what was going on. Pipeline controller then called the pipeline operations supervisor to notify him at 6:15am. Operations supervisor then called the gauger to find out what the cause was and what the site might need. The gauger had found a braided hose to be leaking off the pump 1 mainline discharge at the hose crimped end. Operations supervisor then called a mechanical tech and the pipeline maintenance supervisor to send crews to clean up. Operations supervisor and mechanical tech arrived at 9:30 am. Pumps were already down as the batch was completed the prior day. Operations supervisor called the pipeline control room to notify them that equipment would be de-energized and loto placed to isolate the leaking hose and drain. Pipeline maintenance personnel arrived to assist in cleanup at approx. 9:45am. The line was drained and leaking hose removed. A plug installed and cleanup of the oil on pumps and ground. An estimated .5 bbl was released. The cause of the failure was determined to be fatigue fracture in the core tube caused by excessive vibration. The hose manufacturer's evaluation report confirmed this determination. |